Inductive sensor
NI50U-CK40-VP4X2-H1141/3GD
Type designation NI50U-CK40-VP4X2-H1141/3GD
Ident no. 1514120
Rated switching distance Sn 50 mm
Mounting conditions Non-flush, flush
Secured operating distance
Repeat accuracy
Temperature drift
Hysteresis 3…15 %
Ambient temperature -30…+85 °C
ð (0,81 x Sn) mm
ð 2 % of full scale
ð ± 10 %
ð ± 20 %, ð -25 °C v ï +70 °C
For explosion hazardous areas see instruction
leaflet
■ ATEX category II 3 G, Ex zone 2
■ ATEX category II 3 D, Ex zone 22
■ Rectangular, height 40 mm
■ Variable orientation of active face in 5
directions
■ Plastic, PBT-GF30-V0
■ High luminance corner LEDs
■ Optimum view on supply voltage and
switching state from any position
■ Factor 1 for all metals
■ Increased switching distance
■ Protection class IP68
■ Resistant to magnetic fields
■ Auto-compensation protects against
pre-attenuation
■ Partially embeddable
■ DC 4-wire, 10…65 VDC
■ Changeover contact, PNP output
■ M12 x 1 male connector
Wiring Diagram
Operating voltage 10…65 VDC
Residual ripple
DC rated operational current
No-load current I
Residual current
Isolation test voltage
Short-circuit protection yes
Voltage drop at I
Wire breakage/Reverse polarity protection yes/ Complete
Output function 4-wire, Complementary contact, PNP
Protection class
Switching frequency 0.25 kHz
Approval acc. to ATEX test certificate TURCK Ex-10002M X
Design Rectangular,CK40
Dimensions 65 x 40 x 40 mm
Housing material Plastic, PBT-GF20-V0, Black
Active area material Plastic, PA12-GF30, yellow
Electrical connection Connectors, M12 × 1
Vibration resistance 55 Hz (1 mm)
Shock resistance 30 g (11 ms)
Protection class IP68
MTTF 874 years acc. to SN 29500 (Ed. 99) 40 °C
Packaging unit 1
Power-on indication 2 × LEDs,Green
Switching state 2 × LEDs, Yellow
Included in delivery Fixing clamp BS4-CK40, SC-M12/3GD
0
e
ð 10 % U
ss
ð 200 mA
ð 15 mA
ð 0.1 mA
ð 0.5 kV
ð 1.8 V
÷
variable orientation of active face in 5 directions
Functional principle
Inductive sensors detect metal objects contactless and wear-free. Due to the patented
multi-coil system, uprox®+ sensors have distinct advantages over conventional sensors.
They excel in largest switching distances,
maximum flexibility and operational reliability
as well as efficient standardization.
Edition • 2019-02-15T19:14:46+01:00
1 / 4 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com

Inductive sensor
NI50U-CK40-VP4X2-H1141/3GD
Distance D 240 mm
Distance W 105 mm
Distance S 60 mm
Distance G 300 mm
Distance N 30 mm
Width active area B 40 mm
Flush mounting
1-side mounting: Sr = 35 mm; D = 240 mm
2-side mounting: Sr = 25 mm; D = 240 mm
3-side mounting: Sr = 20 mm; D = 80 mm
4-side mounting: Sr = 15 mm; D = 60 mm
Backside as well as recessed mounting with reduced
switching distance
Recessed mounting in metal:
x = 10 mm: Sr = 20 mm
x = 20 mm: Sr = 20 mm
x = 30 mm: Sr = 20 mm
x = 40 mm: Sr = 20 mm
Protruded mounting:
y = 10 mm: Sr = 40 mm
y = 20 mm: Sr = 50 mm
y = 30 mm: Sr = 50 mm
y = 40 mm: Sr = 50 mm
Mounting in aperture plate:
T = 150 mm:
Sensor with twisted turning angle
On metal Sr = 50 mm
Metal-enclosed on one side Sr = 25 mm
Metal-enclosed on two sides Sr = 15 mm
Metal-enclosed on three sides Sr = 12 mm
The values stated relate to a 1 mm thick steel plate.
Edition • 2019-02-15T19:14:46+01:00
2 / 4 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com

Inductive sensor
NI50U-CK40-VP4X2-H1141/3GD
Accessories
Type code Ident no. Description
BSS-CP40 6901318 Mounting bracket for rectangular devices; material:
Polypropylene
Edition • 2019-02-15T19:14:46+01:00
3 / 4 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com

Inductive sensor
NI50U-CK40-VP4X2-H1141/3GD
Operating manual
Intended use
This device fulfills the directive 2014/34/EU and is suited for use in explosion hazardous areas acc. to EN 60079-0:2012/A11:2013, EN
60079-15:2010 and EN 60079-31:2014.
In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II 3 G and II 3 D (Group II, Category 3 G, electrical equipment for gaseous atmospheres and category 3 D, electrical equipment for dust atmospheres).
Marking (see device or technical data sheet)
É II 3 G Ex nA IIC T4 Gc according to EN 60079-0:2012/A11:2013 and EN 60079-15:2010 and É II 3 D Ex tc IIIC T110 °C Dc acc. to EN
60079-0:2012/A11:2013 and EN 60079-31:2014
Local admissible ambient temperature
-25…+30 °C
Installation/Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection
classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas.
Please verify that the classification and the marking on the device comply with the actual application conditions.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and
avoid build-up of dust deposits on the device.
The devices must be protected against strong magnetic fields.
The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet.
In order to avoid contamination of the device, please remove possible blanking plugs of the cable glands or connectors only shortly before inserting the cable or opening the cable socket.
Special conditions for safe operation
For devices with M12 connectors please use the supplied safety clip SC-M12/3GD.
Do not disconnect the plug-in connection or cable under voltage.
Please attach a warning label permanently in an appropriate fashion in close proximity to the plug-in connection with the following inscription:
Nicht unter Spannung trennen / Do not separate when energized.
The device must be protected against any kind of mechanical damage and degrading UV-radiation.
The IP protection rating of the connectors is given only in combination with a suitable O-ring
Load voltage and operating voltage of this equipment must be supplied from power supplies with safe isolation (IEC 30 364/UL508), to ensure
that the rated voltage of the equipment (24 VDC +20% = 28.8 VDC) is never exceeded by more than 40%.
Service/Maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important
data from the approval are listed.
Edition • 2019-02-15T19:14:46+01:00
4 / 4 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com