turck TBPN-L1-FDIO1-2IOL Safety Manual

Page 1
Your Global Automation Partner
TBPN-L1-FDIO1-2IOL
Safety Block I/O Module
Safety manual - Translation
Page 2
2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 3
1 About this document 5
2 Scope 5
3 Safety Integrity Level/Performance Level/Category 5
4 Product description 6
4.1 Intended use 6
4.1.1 Foreseeable misuse 6
4.2 Device overview 6
4.3 Type plate 7
4.4 Switches and connectors 7
4.5 Block diagram 7
5 Safety function 8
5.1 Safe status 8
5.2 Fatal Error 8
6 Safety planning 8
6.1 Prerequisites 8
6.2 Reaction time 8
6.3 Safety characteristic data 9
7 Operating instructions 9
7.1 General 9
7.2 Before operation 10
7.2.1 Mounting 10
7.2.2 Connection 11
7.2.3 Address assignment 12
7.2.4 Conguring 12
7.3 Operation 13
7.3.1 Indication elements 13
7.3.2 Output error behavior 14
7.3.3 Decommissioning 14
8 Appendix: Wiring diagram 14
8.1 Ethernet 14
8.2 Power supply 14
8.3 Safety inputs 14
8.4 Safety in-/outputs 15
8.5 DXP 15
8.6 IO-Link 15
9 Appendix: Connection examples 16
9.1 Inputs 16
9.2 Outputs 16
V2.0 | 2018/01
3
Page 4
10 Appendix: Designations and abbreviations 17
11 Appendix: Function tests 17
12 Appendix: Document history 17
13 Appendix: Technical data 18
14 Appendix: Declaration of Conformity 20
4
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 5

1 About this document

This safety manual contains all information that is required by users to operate the device in functional safety systems. Read this manual carefully before using the device.
This document addresses only functional safety according EN ISO 13849-1 and EN/IEC 61508. Other issues are not considered.
All instructions must be followed in order to assure functional safety.
Always make sure that this is the latest version of the safety manual at www.turck.com. TheGerman versionis considered the definitive document. Every care was taken in the produc­tion of the translations of this document. If there is any uncertainty in its interpretation, refer to theGerman version of the safety manual or contact TURCK directly.

2 Scope

This safety manual is valid for the Turck PROFIsafe device TBPN-L1-FDIO1-2IOL.

3 Safety Integrity Level/Performance Level/Category

The devices are rated for applications up to:
SIL3 according to EN/IEC 61508 and EN/IEC 62061
Category 4/PLe according to EN ISO 13849-1
V2.0 | 2018/01
5
Page 6

Product description

4 Product description
The TBPN-L1-FDIO1-2IOL is a safety block I/O module for safety applications with PROFIsafe over PROFINET.
The device provides two safety SIL3-inputs (FDI) to connect 2-channel mechanical safety switches and electronic safety sensors (OSSD). Two further SIL3-channels (FDX) can be freely used as inputs (FDI) or outputs (FDO). The safety outputs serve for the safe shutdown of loads (resistive up to 2 A). For non-safety functions, the device provides four universal in-/outputs (DXP) at C4 as well as two IO-Link master channels (IOL) at C6 and C7 for connecting IO-Link sensors and IO-Link hubs. Additionally, the IO-Link slots each provide one digital in-/output at pin 2. The non-safety ports C4, C5 and C7 can be switched-o safe via the internal outputs FSO0 and FSO1 (see „4.5 Block diagram“ on p.7). This allows a safety shutdown of the connected sensors and actuators.

4.1 Intended use

The TBPN-L1-FDIO1-2IOL is a decentralized PROFIsafe safety module. It collects field signals and transfers the signals safe to a PROFINET master. Thanks to an extended temperature range from -40 to +70 °C and the protection class IP65/ IP67/IP69K, it can be used in harsh environments directly on the machine. The device is specified for the operation in industrial environment. If it is used in residential or mixing areas, radio interference may occur.

4.1.1 Foreseeable misuse

The device is not suitable for:
The use in explosive areas
Outdoor use
The permanent use in liquids

4.2 Device overview

30,2
60,4
24
P1
P2
230,5
218
38,8
C0C1C2C3
X1
6,3
C4C5C6C7
X2
6
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 7

4.3 Type plate

TBPN-L1-FDIO1-2IOL
FE
V1
Ident-No.: 6814053 Charge code: YoC:
Hans Turck GmbH & Co. KG Witzlebenstr.7 D-45472 Mülheim a. d. Ruhr www.turck.com

4.4 Switches and connectors

Meaning
Meaning Power IN
X2 Power OUT
C0 FDI0/1, safety input
C1 FDI2/3, safety input
C2 FDX4/5, safety in-/output
C3 FDX6/7, safety in-/output
C4
C5
C6 IOL, IO-Link port1
C7 IOL, IO-Link port2 (safe shutdown via FSO1 possible)
F-Address
P1 Ethernet 1
P2 Ethernet 2
FE Functional earth
C0
C1
C2
C3
X2X1
C4
C5
C6
C7
F-Address
P2P1
DXP8/9, standard in-/outputs (safe shutdown via FSO0)
DXP10/11, standard in-/outputs (safe shutdown via FSO0 possible)
Rotary coding switch for address setting for PROFIsafe (F-address setting)

4.5 Block diagram

1
C0
5
1
C1
5
1
C2
5
C3
4
FDI0/1 FSO0
2
4
FDI2/3
2
4
FDX4/5
2
4
FDX6/7
2
(intern)
FSO1
(intern)
DXP8
DXP9
DXP10
DXP11
IO-Link Port1
DI12 (C/Q)
DXP13
IO-Link Port2
DI14 (C/Q)
DXP15
4
C4
2
4
C5
2
4
C6
2
4
C7
2
V2.0 | 2018/01
7
Page 8

Safety function

5 Safety function
The device provides two safe digital SIL3 inputs (FDI) and two SIL3-connectors (FDX), configu­rable as in- or outputs.
The following devices can be connected to the safety inputs:
Max. four 2-channel safety switches and sensors
Contact switches, e.g. Emergency stop buttons, protective door switches
Sensors with OSSD switching outputs with test signals
Sensors with OSSD switching outputs without test signals
The two safety SIL3 outputs can be used PP- or PM-switching
Additionally, the DXP channels (C4 and C5) as well as the second IO-Link port (C7) can be switched-o safe via the internal outputs FSO0 and FSO1 (see „4.5 Block diagram“ on p.7).

5.1 Safe status

In the safe state the device outputs are in LOW-state (0). The inputs report a LOW-state (0) to the logic.

5.2 Fatal Error

The following errors lead to Fatal Error and thus to the safe state:
Incorrect wiring at the output (e.g. capacitive load, energetic recovery)
Incorrect power supply
Strong EMC disturbances
Internal device error

6 Safety planning

The operator is responsible for the safety planning.

6.1 Prerequisites

Perform a hazard and risk analysis.Develop a safety concept for the machine or plant.Calculate the safety integrity for the complete machine or plant.Validate the complete system.

6.2 Reaction time

If the system is operated with higher availability, the max. reaction time is extended (see „6.3
Safety characteristic data“ on p.9).
In addition to the reaction time in the device, reaction times of the further PROFIsafe compo­nents have to be considered eventually. Please find the respective information in the technical data of the respective devices.
Further information about the reaction time can be found in the online help for the software „Turck Safety Configurator” (see also „7.2.4 Configuring“ on p.12).
8
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 9

6.3 Safety characteristic data

Characteristic data Value Standard
Performance Level (PL) e EN/ISO 13849-1
Safety category 4 EN/ISO 13849-1
Safety Integrity Level (SIL ) 3 IEC/EN 61508
SIL CL 3 EN/IEC 62061
PFH
D
PFD 5 × 10
MTTF
D
DC 99 %
Permissible duration of use (TM) 20 years EN ISO 13849-1
Maximum on-time 12 months IEC/EN 61508
Max. reaction time in case of shutdown
PROFIsafe > local output 25 ms IEC/EN 61508
Local input > PROFIsafe 20 ms
Local input <> local output 35 ms

7 Operating instructions

7.1 General

4 × 10 -9 1/h IEC/EN 61508; EN/ISO 13849-1
-6
> 2500 years EN/ISO 13849-1: 2016
IEC/EN 61508
In case of a safety application, the device has to be registered under www.turck.de/SIL.The device must only be mounted, installed, operated and maintained by trained and quali-
fied personnel.
The device is not specified for a certain application. Make sure that application-specific
aspects are considered.
Before expiration of the permissible duration of use the device must be replaced (see „6.3
Safety characteristic data“ on p.9).
Execute a functional test every twelve months. The device must not be repaired. If problems occur with regard to functional safety, TURCK
must be notified immediately and the device must be returned immediately to:
Hans Turck GmbH & Co. KG Witzlebenstraße 7 45472 Mülheim an der Ruhr Germany
In case of device errors which lead to the safe state, measures have to be taken which guaran-
tee the safe state for the further operation of the complete control system.
Dangerous failures have to be reported immediately to Turck.
V2.0 | 2018/01
9
Page 10
Operating instructions

7.2 Before operation

The operator of the machine or the plant in which the safety related system is used, is responsi­ble for the correct and safe overall function of every single safety component.
Carry out a validation of the safety category for the complete system depending on the selec-
tion of the used safety components.

7.2.1 Mounting

ATTENTION
Mounting on uneven surfaces
Damage to the device due to mechanical tensions
Mount the device onto an even mounting surface. Use two M6 screws to mount the device.Mount the device onto a pre-drilled and grounded mounting surface. The maximum
tightening torque for the screws is 1.5 Nm.
M6 (2x) max. 1.5 Nm
218 [5.58]
10
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 11

7.2.2 Connection

Connect the Ethernet
The maximum tightening torque for the Ethernet connectors is 0.6 Nm.
Connect power supply
The externally connectable circuits have to be securely disconnected from the mains supply.
ATTENTION
Loss of protection class IP65/IP67/IP69K
Damage to the device due to invasive foreign material or liquids
Seal unused sockets, connectors and covers carefully. Use appropriate 7/8" sealing caps, e.g. type RKMV-CCC (not included in the scope of
delivery).
Use appropriate M12-sealing caps (included in the scope of delivery).
Connect the device to the field bus according to the pin assignment (see „1 About this docu-
ment“ on p.5).
WARNING
Wrong 24 V power supply unit
Dangerous voltage and loss of functional safety
Exclusively use power supply units with PELV voltage according to EN50178 (PELV).Assure that the maximum output voltage of 60 V is not exceeded, even in case of an
error.
Connect the device to the power supply according to the pin assignment (see „8 Appen-
dix: Wiring diagram“ on p.14). The female connectors at the device have the following
function:
X1: Voltage IN
ū
X2: Conduct voltage to next node
ū
Connect sensors and actuators
DANGER
Wrong supply of sensors and actuators
Danger to life due to external supply
Guarantee that no external supply is used.Guarantee that the inputs are only supplied through the same 24 V source as the
device itself.
DANGER
Connection of fast reacting loads
Danger to life due to connection failures
Use loads with mechanical or electrical inertia.
Positive and negative test pulses have to be tolerated.
The maximum tightening torque for the M12 connectors is 0.8 Nm.
Connect the sensors and actuators to the in- and outputs according to the pin assignment
(see „8 Appendix: Wiring diagram“ on p.14).
V2.0 | 2018/01
11
Page 12
Operating instructions
BUS
ERR

7.2.3 Address assignment

Set the F-address (PROFIsafe address) for the TBPN-L1-FDIO1-2IOL using the three rotary
coding switches under the cover at the device.
The module is delivered with the switch position 0. The address 0 and the addresses ≥ 900 are no valid F-addresses.
7.2.4 Conguring
The safety function of the safe channels can only be configured via the software Turck Safety Configurator. After the configuration, the device generates a CRC and a configuration protocol. This protocol has to be checked and validated by the user. The CRC is stored as reference in the configuration of the PROFIsafe control and guarantees the correct safety function. Further information about the software can be found in the online help.
Memory
F-Address
32
1
0
9876
x 100 x 10 x1
32
4
1
5
0
9
8 7
1
4
5
0
6
9
8 7
32
4
5
6
PROFINETETH1 ETH2
Switch position Meaning
0 State of delivery, no valid address
1…899 F-address, the setting is accepted after a device restart
900 Factory Reset: reset of the device to factory settings
901 Erase Memory Stick: deletes the content of the configuration memory
The configuration of the safe I/O channels set via the Turck Safety Configuratior is automatically stored to a pluggable memory stick which is part of the scope of delivery. In case of a device ex­change, the device configuration can be transferred to another device using the memory stick.
12
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 13

7.3 Operation

7.3.1 Indication elements

During operation, the LEDs have the following functions:
LED Color Meaning
ETH1
green Link established, 100 Mbps
green blinking Ethernet Traffic, 100 Mbps
yellow Link established, 10 Mbps
yellow blinking Ethernet Traffic, 10 Mbps
ETH2
PWR
ERR
BUS
green Link established, 100 Mbps
green blinking Ethernet Traffic, 100 Mbps
yellow Link established, 10 Mbps
yellow blinking Ethernet Traffic, 10 Mbps
green Voltage OK
red Power supply faulty
green No diagnostics
red Diagnostics pending
green Active connection to a master
green blinking Device ready for operation
red IP address conflict or restore mode or timeout
red blinking Blink-/wink-command active
0…3
V2.0 | 2018/01
green/red blinking Autonegotiation and/or waiting for DHCP-/BootP-address assignment.
green Channel active
green blinking Self-test
red Discrepancy
red blinking Cross-connection
13
Page 14

Appendix: Wiring diagram

P1
LED Color Meaning
4…7
green Channel active
green blinking Self-test (input only)
red Discrepancy, overload (output only)
red blinking Cross-connection
8…11
green Channel active
red Overload (output only)
red blinking Channel inactive (input only), overload of supply
green permanent,
Channel active and overload of supply (input only)
red blinking
12…15 green IO-Link communication or DI active
red Error
0…7
red all blinking
Fatal Error
alternating
WINK
white flashing Helps to localize the module if the Blink/Wink command is active.

7.3.2 Output error behavior

In case of an error a switched-off output can be switched on for ≤ 1 ms.

7.3.3 Decommissioning

The decommissioning is described in the user manual (D301379).
8 Appendix: Wiring diagram
The pin assignments can be found on the side of the device.

8.1 Ethernet

v
2
1
4
v
2
1
4
P2
3
flange = FE
3
flange = FE
1 = TX + 2 = RX + 3 = TX – 4 = RX –
1 = RX + 2 = TX + 3 = RX – 4 = TX –
14
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 15
8.2 Power supply
wv
1 BK = GND V2
3
2 BU = GND V1
452
3 GNYE = FE 4 BN = 24 VDC V1
1
5 WH = 24 VDC V2
X1 X2
8.3 Safety inputs
v
1 = V
2
2 = FDI (T2)
4
3 = GND (V1) 4 = FDI (T1) 5 = T2
13
5

8.4 Safety in-/outputs

v
1 = V
2
2 = FDO-/FDI (T2)
4
3 = GND (V1) 4 = FDO+/FDI (T1) 5 = T2
13
5
aux
aux
1/T1
1/T1
3
4
2
5
1
8.5 DXP

8.6 IO-Link

NOTE
For PM-switching outputs, connect the negative pole of the load to the M-connector of the respective output (pin 2).
v
1 = FSO0
2
2 = DI/DO
4
v
2
4
3 = GND (V1) 4 = DI/DO 5 = FE
1 = V 2 = DI/DO 3 = GND (V1) 4 = C/Q 5 = GND (V1)
13
5
13
5
aux
1/FSO1
V2.0 | 2018/01
15
Page 16

Appendix: Connection examples

9 Appendix: Connection examples

9.1 Inputs

Safe equivalent inputs for potential free contacts (NC/NC)
1 T1
2 FDI (T2)
3 n.c.
4 FDI (T1)
5 T2
TBPN-L1…
Safe antivalent input for potential free contacts (NC/NO)
1 T1
2 FDI (T2)
3 n.c.
4 FDI (T1)
5 T2
TBPN-L1…
Safe electronic input (OSSD)
OSSD
+
1 VAUX1
2 FDI (T2)
3 GND
4 FDI (T1)
5 n.c.
TBPN-L1…
1 T1
2 FDI (T2)
3 n.c.
4 FDI (T1)
5 T2
TBPN-L1…

9.2 Outputs

Safe output PP-switching
TBPN-L1…
1 n.c.
2 n.c.
3 GND (V1)
4 FDO +
5 n.c.
Safe output PM-switching
TBPN-L1…
1 n.c.
2 FDO –
3 n.c.
4 FDO +
5 n.c.
For PP-switching outputs, connect the negative pole of the load to the GND of the respective output (pin 3). Another connection to the GND of the power supply unit is not permitted! The wiring has to allow an exclusion of faults regard­ing cross connection.
For PM-switching outputs, connect the negative pole of the load to the M-connector of the respective output (pin 2).
16
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 17

10 Appendix: Designations and abbreviations

Abbreviation Meaning
DC Diagnostic Coverage
E/E/PE-system Electrical/electronic/programmable electronic system
HFT Hardware failure tolerance
MTTF
d
PFD Probability of dangerous failure on demand
PFH Average frequency of dangerous failure per hour
PL Performance Level
SIL Safety Integrity Level
Mean Time To Failure Dangerous

11 Appendix: Function tests

Ensure that the function test is only carried out by qualified personnel. A suggested function test consists of the following steps:
Step Action
1 Switch every safety related input at least once a year.
2 Control the switching behavior by monitoring the output circuits.
3 Observe the maximum duty cycle and the total operation time depending on the select-
ed PFD value.
4 If the maximum duty cycle is reached: request the shutdown function in order to check
the function of the safety system
Once the test has been completed, document and archive the results.

12 Appendix: Document history

Version Date Modications
1.0 2016-06-30 First version
2.0 2018-01-17 – Safety characteristic data updated –Connection examples extended
V2.0 | 2018/01
17
Page 18

Appendix: Technical data

13 Appendix: Technical data
Device
Technical data TBPN-L1-FDIO1-2IOL
Ident no. 6814053
YoC 2016
Interfaces
PROFINET 2 x M12, 4-pin, D coded
Service interface Ethernet
Power supply
V1 (incl. electronics supply) 24 VDC
V2 24 VDC, only through connected
Permissible range 20.4...28.8 VDC
Isolation voltages ≥ 500 VAC
Times
Internal delay time (for calculating the Watchdog time)
Reaction times see „6.3 Safety characteristic data“ on p.9
Safety inputs for potential free contacts
Loop resistance <150 Ω
Max. cable length max. 1 μF at 150 Ω
Test pulse typ. 0.6 ms
Test pulse max. 0.8 ms
Interval between 2 test pulses 900 ms (for static inputs)
Safety inputs for OSSD
Signal voltage, low level EN 61131-2, type 1 (< 5 V; < 0,5 mA)
Signal voltage, high level EN 61131-2, type 1 (> 15 V; > 2 mA)
Max. OSSD supply per channel 2 A
Max. tolerated test pulse width 1 ms
Min. interval between 2 test pulses 12 ms at 1 ms test pulse width
Safety outputs
Suitable for inputs according to EN 61131-2, type 1
Output level in OFF-state < 5 V
Output current in OFF-state < 1 mA
Test pulse resistive load, max. 0.5 ms
Test pulse, max. 1.25 ms
Interval between 2 test pulses, typical 500 ms
Interval between 2 test pulses, min. 250 ms
Max. output current 2 A (resistive)
10 ms
limited by line capacity
8.5 ms at 0.5 ms test pulse width
7.5 ms at 0.2 ms test pulse width
18
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 19
Max. total current for device 9 A, derating curve:
[A]
I
9
7
0
0-404070
[°C]
Max. output current 2 A, (DC-load) derating curve:
I [A]
2
1.5
0
0-404070
[°C]
The user has to provide an additional overcurrent protection on site.
General Information
Max. cable length
–Ethernet 100 m (per segment)
–Sensor/actuator 30 m
Operating/storage temperature -40 °C to +70 °C (-40 to + 158 °F)
Protection class IP65/IP67/IP69K
Housing material Fiber-glass reinforced Polyamide (PA6-GF30)
Window material Lexan
Tests
Vibration test according to EN 60068-2-6, IEC 68-2-47,
acceleration up to 20 g
Drop and topple according to IEC 60068-2-31/IEC 60068-2-32 1
Shock test according to EN 60068-2-27
Electro-magnetic compatibility according to EN 61131-2/EN 61326-3-1
V2.0 | 2018/01
19
Page 20

Appendix: Declaration of Conformity

EG Konformitätserklärung Nr.
EC Declaration of Conformity No.: / Déclaration CE de conformité n° / Declaración CE de conformidad n.° / Dichiarazione CE di conformità N. / deklaracji zgodności WE nr:
5126M
Wir/
We/Nous/Nosotros/Noi/My
HANS TURCK GMBH & CO KG WITZLEBENSTR. 7 D – 45472 MÜLHEIM A.D. RUHR
erklären in alleiniger Verantwortung, dass die Produkte
declare under our sole responsibility that the products / déclarons sous notre seule responsabilité que les produits / declaramos bajo nuestra propia responsabilidad que los productos / dichiariamo sotto la nostra esclusiva responsabilità, che I / deklaruje z pełną odpowiedzialnością, że produkty
Safety Block I/O Modul
Safty block I/O Module / Modules de sécurité E/S / Módulos de E/S de bloque de seguridad / Moduli I/O di sicurezza / Kompaktowe moduły
bezpieczeństwa I/O
TBPN-L1-FDIO1-2IOL
auf die sich die Erklärung bezieht, den Anforderungen der folgenden EU-Richtlinien durch Einhaltung der folgenden Normen genügen:
to which this declaration relates are in conformity with the requirements of the following EU directives by compliance with the following standards: / concernés par la présente déclaration répondent aux exigences des directives européennes suivantes conformément aux normes suivantes: / a los que hace referencia esta declaración cumplen los requisitos de las siguientes directivas de la UE ya que s on conformes a las siguientes normas: / cui la presente dichiarazione fa riferimento, soddisfano i requisiti delle seguenti dire ttive UE in conformità alle seguenti norme: / do których odnosi się ta deklarcja, spełniają wymagania następujących dyrektyw UE poprzez zgodność z następującymi normami
EMV-Richtlinie /
EMC Directive / Directive EMC / Directiva CEM / Direttiva EMC (compatibilità elettromagnetica) / Dyrektywa EMC
2014 / 30 / EU
26/2/2014
EN 61000-6-2:2005
EN 61000-6-4:2007 + A1:2011
EN 61131-2:2007
Maschinenrichtlinie /
Machinery directive / Directive machines / Directiva sobre máquinas / Direttiva macchine / Dyrektywa Maszynowa
2006 / 42 / EC
17/5/2006
EN ISO 13849-1:2015
EN ISO 13849-2:2012
EN 62061:2005/A1:2013/A2:2015
Weitere Normen, Bemerkungen
Additional standards, remarks / Autres normes, remarques / Otras normas, observaciones / Norme aggiuntive, osservazioni / Inne standardy, komentarze
EN 61326-3-1:2008 EN 61508-1…7:2010
Dokumentationsbevollmächtigter:
Authorized representative for documentation: / Représentant pour la documentation: / Rappresentante per la documentazione: / Representante para la documentación: / upoważnionego reprezentatywne dla dokumentacji:
Dr. M. Linde Witzlebenstr. 7 45472 Mülheim a. d. Ruhr
Nummer der EG-Baumusterprüfbescheinigung /
Number of EC Type Examination Certificate / Nom du certificat d'examen de type CE / Número del certificado de examen CE de tipo / Numero del certificato di esame CE del tipo / numer świadectwa badania typu WE
44 205 16 045401
Benannte Stelle /
Notified body / Organisme notifié / Organismo notificado / Organismo notificato / Jednostka notyfikowana
0044 TÜV NORD CERT GmbH Langemarckstraße 20 45151 Essen, Germany
Mülheim, 29.06.2016
i.V. Dr. M. Linde,
Leiter Zulassungen / Manager Approvals / Responsable des
autorisations / Director de aprobaciones / Direttore Omologazioni / Kierownik
Ort und Datum der Ausstellung /
Place and date of issue / Lieu et date d'émission / Lugar y fecha de expedición / Luogo e data del rilascio / Miejsce i data wydania
Name, Funktion und Unterschrift des Befugten / Name, function and signature of authorized person / Nom, fonction et signature de la personne autorisée / Nombre, cargo y firma del autorizado / Nome e funzione della persona autorizzata /
Nazwisko, stanowisko i podpis osoby upoważnionej
14 Appendix: Declaration of Conformity
20
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Page 21
D301391 | 2018/01
*D301391ßß1801*
28 subsidiaries and over
60 representations worldwide!
www.turck.com
Loading...