turck TBIP-L-FDIO1-2IOL Series, TBIP-L4-FDIO1-2IOL, TBIP-L5-FDIO1-2IOL Safety Manual

Your Global Automation Partner
TBIP-L…-FDIO1-2IOL
Safety Block I/O Module
Safety manual – Translation
2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Table of Contents
V01.0 | 2017/10
3
4
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

1 About this Document

This safety manual contains all information that is required by users to operate the device in functional safety systems. Read this manual carefully before using the device.
This document addresses only functional safety according EN ISO 13849-1 and EN/IEC 61508. Other issues are not considered.
All instructions must be followed in order to assure functional safety.
Always make sure that this is the latest version of the safety manual at www.turck.com. TheGerman versionis considered the definitive document. Every care was taken in the produc­tion of the translations of this document. If there is any uncertainty in its interpretation, refer to theEnglish version of the safety manual or contact TURCK directly.

2 Scope

This safety manual is valid for the Turck CIP Safety devices TBIP-L4-FDIO1-2IOL and TBIP-L5-FDIO1-2IOL.

3 Safety Integrity Level/Performance Level/Category

The devices are rated for applications rated to:
SIL3 according to EN/IEC 61508 and EN/IEC 62061
Category 4/PLe according to EN ISO 13849-1
V01.0 | 2017/10
5

Product Description

4 Product Description
The TBIP-L4-FDIO1-2IOL and TBIP-L5-FDIO1-2IOL are safety block I/O modules for safety applica­tions with CIP Safety over EtherNet/IP™.
The devices provide two safety SIL3-inputs (FDI) to connect 2-channel mechanical safety switches and electronic safety sensors (OSSD). Two further SIL3-channels (FDX) can be freely used as inputs (FDI) or outputs (FDO). The safety outputs serve for the safety shutdown of loads (ohmic up to 2 A). For non-safety functions, the devices provide four universal In-/outputs (DXP) at ports C4 and C5 as well as two IO-Link master channels (IOL) at ports C6 and C7 for connecting IO-Link sensors and IO-Link hubs. Additionally, the IO-Link slots each provide one digital in-/output at pin2. The non-safety ports C4, C5 and C7 can be switched-o safe via the internal outputs FSO0 and FSO1 (see”4.5 Block Diagram” on p.7). This allows a safety shutdown of the connected sensors and actuators.

4.1 Intended Use

TBIP-L4-FDIO1-2IOL and TBIP-L5-FDIO1-2IOL are decentralized CIP Safety safety modules. The modules collect field signals and transfer the signals safe to a CIP Safety master. Thanks to an extended temperature range from -40 to +70 °C and the protection class IP65/ IP67/IP69K, the device can be used in harsh environments directly on the machine. The device is specified for the operation in industrial environment. If it is used in residential or mixing areas, radio interference may occur.

4.1.1 Foreseeable Misuse

The devices are not suitable for:
The use in explosive areas
Outdoor use
The permanent use in liquids

4.2 Device Overview

30.2
60.4
24
P1
P2
230.5
218
38.8
C0C1C2C3
X1
6.3
C4C5C6C7
X2
6
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

4.3 Type Labels

TBIP-L5-FDIO1-2IOL
TBIP-L4-FDIO1-2IOL
V1
TBIP-L5-FDIO1-2IOL TBIP-L4-FDIO1-2IOL
Ident-No.: 6814056 Charge code: YoC:
Hans Turck GmbH & Co. KG Witzlebenstr.7 D-45472 Mülheim a. d. Ruhr www.turck.com

4.4 Switches and Connectors

Meaning
X1 Power IN
X2 Power OUT
C0 FDI0/1, safety-related input
C1 FDI2/3, safety-related input
C2 FDX4/5, safety-related in-/output
C3 FDX6/7, safety-related in-/output
C4 DXP8/9, standard in-/outputs
C5 DXP10/11, standard in-/outputs
C6 IOL, IO-Link port1
C7 IOL, IO-Link port2 (safe shutdown via FSO 1 possible)
IP address Rotary coding switch for address setting (last byte of the IP address for
P1 Ethernet 1
P2 Ethernet 2
FE Functional earth
C0
C1
C2
C3
FE
X2X1
C4
C5
C6
C7
IP Address
P2P1
Ident-No.: 100000360 Charge code: YoC:
(safe shutdown via FSO0 possible)
(safe shutdown via FSO0 possible)
the safe device side – C3 to C7))
Hans Turck GmbH & Co. KG Witzlebenstr.7 D-45472 Mülheim a. d. Ruhr www.turck.com

4.5 Block Diagram

V01.0 | 2017/10
C0
C1
C2
C3
4
FDI0/1 FSO0
2
4
FDI2/3
2
4
FDX4/5
2
4
FDX6/7
2
(intern)
FSO1
(intern)
1
5
1
5
1
5
DXP8
DXP9
DXP10
DXP11
IO-Link Port1
DI12 (C/Q)
DXP13
IO-Link Port2
DI14 (C/Q)
DXP15
4
C4
2
4
C5
2
4
C6
2
4
C7
2
7