Hybrid Module for EtherNet/IP and CIP-Safety
Safe Digital Inputs and Outputs, Standard Universal Digital Channels, IO-Link
Master Ports
TBIP-L4-FDIO1-2IOL
■ EtherNet/IP™
■ Integrated Ethernet switch
■ 10 Mbps / 100 Mbps supported
■ 2 x male M12, 4-pin, D-coded, Ether-
net-Fieldbus connection
■ 7/8" connector for power supply, 4-pin
■ Two safe digital SIL3-inputs
■ 2 IO-Link Master V1.1 slots
■ Compact Ethernet/IP CIP-safe block I/O
module
■ 4-pin power supply
■ 2 safe digital inputs
■ 2 safe universal digital inputs or out-
Type designation TBIP-L4-FDIO1-2IOL
Ident-No. 100000360
Supply
Supply voltage 24 VDC
Admissible range 20.4…28.8 VDC
Voltage supply connection 4-pin male 7/8" connector X1
Electrical isolation galvanic isolation of the voltage groups V1 and V2,
voltages up to 500 VAC
puts
■ 4 universal digital inputs or outputs
■ 2 IO-Link Master Ports Class A
■ Glass-fiber reinforced housing
■ Shock and vibration tested
■ Fully potted module electronics
■ Protection classes IP65 / IP67 / IP69K
System data
Fieldbus transmission rate 10 Mbps/100 Mbps
Fieldbus connection technology 2 x M12, 4-pin, D-coded
Web server integrated
Service interface Ethernet via P1 or P2
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification
Quick Connect (QC) < 150 ms
Device Level Ring (DLR) supported
Class 1 connections 3
Safety Data
PL acc. to DIN EN 13849-1:2008 e
Category acc. to DIN EN 13849-1:2008 4
SIL according IEC 61508 3
Useful Lifetime 20 Jahre (EN ISO 13849-1)
Safety Inputs OSSD
Low level signal voltage EN 61131-2 Type 1 ( < 5 V; < 0.5 mA)
High level signal voltage EN 61131-2 Type 1 ( > 15 V; > 2 mA)
Max. OSSD supply per channel 2 A per C0, C1, C2, C3,
1.5 A at 70 °C
Please consider derating as shown in figure 1
Max. tolerance test pulse width 1 ms
Interval between 2 test pulses, minimum 20 ms at 1 ms test pulse width
15 ms at 0.5 ms test pulse width
Safety Inputs floating/antivalent
Max. loop resistance
Max. cable length
Test pulse, typical 0.6 ms
Test pulse, maximum 0.8 ms
Sensor supply Power supply V AUX1/T1 max. 2 A
Interval between 2 test pulses, minimum 900 ms
Additional information No connection to external potential allowed
< 150 ò
max. 1 μF at 150 ò
Limited by line capacity
Please consider derating as shown in figure 1
Figure 1
Figure 2
Edition • 2019-01-15T23:11:57+01:00
1 / 7 TURCK Inc.
Hybrid Module for EtherNet/IP and CIP-Safety
Safe Digital Inputs and Outputs, Standard Universal Digital Channels, IO-Link
Master Ports
TBIP-L4-FDIO1-2IOL
Safety Outputs
Output current in off state < 5 V
Output current in off state < 1 mA
suitable for inputs according to EN 61131-2 Type 1
Test pulse, typical 0.5 ms
Test pulse, maximum 1.25 ms
Interval between 2 test pulses, typical 500 ms
Interval between 2 test pulses, minimum 250 ms
Actuator power supply Power supply V AUX1/T1 max. 2 A
Please consider derating as shown in figure 1
Max. output current 2 A (resistive)
1 A (inductive)
Additional information The load must be mechanically or electrically inert to
tolerate the test pulses.
When configured as a PPM switching output the
negative pole of the load should be wired to the M-
terminal of the corresponding output (Pin 2).
Digital inputs
Connectivity inputs M12, 5-pin
Input type PNP
Switching threshold EN 61131-2 Typ 3, PNP
Low level signal voltage < 5 V
High level signal voltage > 11 V
Low level signal current < 1.5 mA
High level signal current > 2 mA
Input delay 2.5 ms
Sensor supply C4, C5: FSO 0 max. 2 A; 500 mA per input
C6: V AUX1 max. 2 A
C7: FSO1 max. 2 A
Please consider derating as shown in figure 1
Electrical isolation galvanic isolation to P1/P2
, voltages up to 500 VDC
Connectivity outputs M12, 5-pol
Output current per channel 0.5 A, short-circuit proof,
max. 2 A (resistive)/ 1 A (inductive) all std. outputs
Actuator power supply C4, C5: FSO 0 max. 2 A; 500 mA per output
C6: V AUX1 max. 2 A
C7: FSO1 max. 2 A
Please consider derating as shown in figure 1
IO-Link
Number of channels 2
IO-Link specification Version 1.1
IO-Link port type Class A and Class B
Frame type supports all specified frame types
Supported devices max. 32 byte input/32 byte output
Transmission rate 4.8 kbps (COM 1) / 38.4 kbps (COM 2) / 230 kbps
(COM 3)
Power supply Power supply V AUX1 max. 2 A
Please consider derating as shown in figure 1
Standard/Directive conformity
Vibration test acceleration to 20 g
acc. to EN 60068-2-6
Shock test acc. to EN 60068-2-27
Drop and topple acc. to EN 60068-2-31/IEC 60068-2-32
Electromagnetic compatibility acc. to EN 61131-2
Approvals and certificates CE, FCC
UL Certificate cULus LISTED 21 W2, Encl.Type 1 IND.CONT.EQ.
Edition • 2019-01-15T23:11:57+01:00
2 / 7 TURCK Inc.
Hybrid Module for EtherNet/IP and CIP-Safety
Safe Digital Inputs and Outputs, Standard Universal Digital Channels, IO-Link
Master Ports
TBIP-L4-FDIO1-2IOL
General Information
Dimensions (W x L x H) 60.4 x 230.4 x 39mm
Operating temperature -40…+70 °C
Storage temperature -40…+85 °C
Altitude max. 5000 m
Protection class IP65
IP67
IP69K
Housing material PA6-GF30
Housing color Black
Window material Lexan
Material screw 303 stainless steel
Material label Polycarbonate
Halogen-free yes
Mounting 2 mounting holes � 6.3 mm
The data sheet serves as advance information. For
definitive values see the corresponding product
manual. In this respect, no liability for completeness
and accuracy can be applied to the content of this
data sheet.
Edition • 2019-01-15T23:11:57+01:00
3 / 7 TURCK Inc.