turck TBIL-M1-16DXP-B Instructions For Use Manual

Your Global Automation Partner
TBIL-M1-16DXP-B
I/O Hub with IO-Link
Instructions for Use
2
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Table of Contents
1.1 Target groups................................................................................................................ 5
1.2 Explanation of Symbols Used .................................................................................... 5
1.3 Additional Documents ................................................................................................5
1.4 Feedback About These Instructions .........................................................................5
2.1 Product Identification ................................................................................................. 6
2.2 Scope of Delivery.......................................................................................................... 6
2.3 Legal Requirements ..................................................................................................... 6
2.4 Manufacturer and Service........................................................................................... 6
3.1 Intended Use .................................................................................................................7
3.2 General Safety Instructions ........................................................................................7
3.3 Notes on the Use in Safety-Related Applications................................................... 7
4.1 Device Overview...........................................................................................................8
4.1.1 Display Elements...........................................................................................................................8
4.2 Properties and Features.............................................................................................. 8
4.3 Functions and Operating Modes...............................................................................8
6.1 Connecting the Supply Voltage and IO-Link.........................................................10
6.1.1 Supply Concept ..........................................................................................................................11
6.2 Connecting Digital Sensors and Actuators ...........................................................12
7.1 Safety Function...........................................................................................................13
7.1.1 Safety Characteristic Data for the Galvanic Isolation.................................................... 13
7.1.2 Cited Standards .......................................................................................................................... 13
7.2 Safety Planning........................................................................................................... 14
7.3 Safe Commissioning ..................................................................................................14
7.3.1 Installing Connecting Cables Safely.................................................................................... 14
7.3.2 Switch-off Supply Voltage Safely .........................................................................................14
7.3.3 Connecting Sensors and Actuators..................................................................................... 14
7.4 Function Tests.............................................................................................................14
8.1 Parameters...................................................................................................................15
9.1 Process Input Data .....................................................................................................21
9.2 Process Output Data..................................................................................................22
9.3 LED Displays ................................................................................................................23
9.3.1 IO-Link............................................................................................................................................ 23
9.3.2 Channel-LEDs ..............................................................................................................................23
9.4 Evaluating Diagnostic Data......................................................................................24
V01.01 | 2018/11
3
Table of Contents
9.5 IO-Link Events .............................................................................................................26
9.6 IO-Link Error Codes ....................................................................................................26
12.1 Returning Devices ......................................................................................................28
4
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

1 About These Instructions

These operating instructions describe the structure, functions and the use of the product and will help you to operate the product as intended. Read these instructions carefully before using the product. This is to avoid possible damage to persons, property or the device. Retain the in­structions for future use during the service life of the product. If the product is passed on, pass on these instructions as well.

1.1 Target groups

This document is written for specially trained personnel, and must be read carefully by anyone who is responsible for the mounting, commissioning, operation, maintenance, disassembly or disposal of the device.

1.2 Explanation of Symbols Used

The following symbols are used in these instructions:
DANGER
DANGER indicates a dangerous situation with high risk of death or severe injury if not avoided.
WARNING
WARNING indicates a dangerous situation with medium risk of death or severe in­jury if not avoided.
CAUTION
CAUTION indicates a dangerous situation of medium risk which may result in minor or moderate injury if not avoided.
NOTICE
NOTICE indicates a situation which may lead to property damage if not avoided.
NOTE
NOTE indicates tips, recommendations and useful information on specific actions and facts. The notes simplify your work and help you to avoid additional work.
u
a
CALL TO ACTION
This symbol denotes actions that the user must carry out.
RESULTS OF ACTION
This symbol denotes relevant results of actions.

1.3 Additional Documents

The following additional documents are available online at www.turck.com:
n Data sheet n Declaration of Conformity n IO-Link devices commissioning manual

1.4 Feedback About These Instructions

We make every effort to ensure that these instructions are as informative and as clear as pos­sible. If you have any suggestions for improving the design or if some information is missing in the document, please send your suggestions to techdoc@turck.com.
V01.01 | 2018/11
5
Notes on the Product
Manufacturer and Service

2 Notes on the Product

2.1 Product Identification

These instructions are valid for the following devices:
n TBIL-M1-16DXP-B

2.2 Scope of Delivery

The scope of delivery includes:
n I/O hub n Dummy plugs for M12-connectors n Label clips n Quick Start Guide

2.3 Legal Requirements

The device is subject to the following EC directives:
n 2014/30/EU (electromagnetic compatibility) n 2011/65/EU (RoHS II Directive)

2.4 Manufacturer and Service

Hans Turck GmbH & Co. KG Witzlebenstraße 7 45472 Muelheim an der Ruhr Germany
Turck supports you with your projects, from initial analysis to the commissioning of your applic­ation. The Turck product database contains software tools for programming, configuration or commissioning, data sheets and CAD files in numerous export formats. You can access the product database at the following address: www.turck.de/products For further inquiries in Germany contact the Sales and Service Team on:
n Sales: +49 208 4952-380 n Technology: +49 208 4952-390
Outside Germany, please contact your local Turck representative.
6
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

3 For Your Safety

The product is designed according to state-of-the-art technology. However, residual risks still exist. Observe the following warnings and safety notices to prevent damage to persons and property. Turck accepts no liability for damage caused by failure to observe these warning and safety notices.

3.1 Intended Use

These devices are designed solely for use in industrial areas. The block module TBIL-M1-16DXP-B is an IO-Link device (Class B) and serves as I/O hub between field devices (sensors/actuators) and the IO-Link master. The hub has 16 I/O channels. Each I/O channel can be used as digital in- or output without additional configuration. The device is designed in IP67/IP69K and can be mounted directly in the field. The devices can be used in safety functions up to Performance Level d (acc. to IEC 13849) and SIL 2 (acc. to ISO 61508). For the outputs at the connectors C4…C7, the supply voltage V2 can be safely switched off by an external safety relay or a safety PLC. The devices may only be used as described in these instructions. Any other use is not in accord­ance with the intended use. Turck accepts no liability for any resulting damage.

3.2 General Safety Instructions

n The device may only be assembled, installed, operated, parameterized and maintained by
professionally-trained personnel.
n The device may only be used in accordance with applicable national and international
regulations, standards and laws.
n The device only meets the EMC requirements for industrial areas and is not suitable for use
in residential areas.

3.3 Notes on the Use in Safety-Related Applications

n For the use in safety-related applications: Observe chapter “Using the device in safety applic-
ations”.
n The device is part of a safety-related overall system. The overall system must always be
evaluated as a whole with regard to the requirements of EN ISO 13849-1 and EN IEC 61508.
n The device is not specified for a certain application. Make sure that application-specific
aspects are considered.
n Replace the device before the end of its service life (see "Safety characteristic data for the
galvanic isolation").
n If there is a fault, e.g. a defective housing, do not use the device. n During operation, surface temperatures may occur that could cause burns if touched. n Perform a function test every 12 months n The devices must not be repaired. If problems occur with regard to functional safety, notify
Turck immediately and return the devices immediately to:
Hans Turck GmbH & Co. KG Witzlebenstraße 7 45472 Muelheim an der Ruhr Germany
V01.01 | 2018/11
7
Product Description
0 8
1 9
2 10
3 11
4 12
5 13
6 14
7 15
C3 C2
C7 C6
C1
C5C0C4
73
107
44.7
32.
150
16
25.2
ø 4.3
54
M12 x 1
27.4
Functions and Operating Modes

4 Product Description

The I/O hub TBIL-M1-16DXP-B connects up to 16 digital sensors or actuators with one IO-Link master port. For the connection of field devices, eight M12 connectors are available. Each I/O channel of the TBIL-M1-16DXP-B can be used as digital in- or output without additional configuration. The I/O hub is connected to the IO-Link master via an M12 female connector. The devices are designed in a fully encapsulated housing with degree of protection IP67/IP69K.

4.1 Device Overview

Fig.1: Dimensions

4.1.1 Display Elements

The device has the following LED indicators:
n IO-Link communication n I/O status

4.2 Properties and Features

n Fibre-glass reinforced housing n Shock and vibration tested n Fully potted module electronics n Protection class IP67/IP69K n IO-Link Class B device with 2 galvanically isolated supply voltages (V1/V2) n IO-Link diagnostics for short-circuit and supply over- and undervoltage n 2 universal digital channels per connector n Metal connectors

4.3 Functions and Operating Modes

The I/O hub TBIL-M1-16DXP-B is an IO-Link Class B device with 2 galvanically isolated supply voltages V1 and V2. The connectors C0…C3 are supplied from V1, the connectors C4…C7 from V2. The two supply voltages are galvanically isolated. This allows that the V2 voltage supply for the outputs at connectors C4...C7 can be safely switched off or not safely for the purpose of en­ergy management. The device provides diagnostics for power supply and short circuit of the sensors and actuators on the IO-Link master.
8
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

5 Mounting

The device is mounted via four M4 screws on a flat and pre-drilled mounting surface.
Fasten the module to the mounting surface with 4 M4 screws. The maximum tightening
Fig.2: Mounting the device to a mounting plate.
torque for the screws is 0.5 Nm
V01.01 | 2018/11
9
Connecting
1 = 24 VDC (V1) 2 = 24 VDC (V2) 3 = GND (V1) 4 = C/Q (IO-Link) 5 = GND (V2)
4
13
2
5
Connecting the Supply Voltage and IO-Link

6 Connecting

WARNING
Penetration of liquids or foreign objects through leaking connections
Danger to life due to failure of the safety function
Tighten the M12 connectors with a tightening torque of 0.8 Nm.Always seal unused connectors with respective protection caps.

6.1 Connecting the Supply Voltage and IO-Link

WARNING
Defective power supply unit
Danger to life due to dangerous voltages on touchable parts
Only use SELV or PELV power supplies in accordance with EN ISO 13849-2, which
allow a maximum of 60 VDC or 25 VAC in the event of a fault.
A 5-pole M12 connector is available for the connection to IO-Link and the supply voltage.
Fig.3: M12 connector for the connection to IO-Link
Connect the device to the supply voltage and IO-Link according to the pin assignment.
Fig.4: Pin assignment IO-Link
10
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

6.1.1 Supply Concept

V1
V2
The I/O hub TBIL-M1-16DXP-B is supplied via the IO-Link connector with two galvanically isol­ated voltages V1 and V2 through the IO-Link connector. The IO-Link channels are separated into the different potential groups "detachable I/O" (supplied through V2) and "non-detach­able" I/O (supplied through V1). This allows a safety shutdown of parts of an installation via emergency stop circuits.
Fig.5: Supply concept TBIL-M1-16DXP-B
V1 = supply of the module eclectronics and the connectors C0…C3 V2 = supply of the connectors C4…C7 with Class B supply
V01.01 | 2018/11
11
Connecting
0
1
2
3
4
5
6
7
C0…C3
4
1
3
2
5
v
1 = V
SENS
(V1) 2 = In/Out 3 = GND (V1) 4 = In/Out 5 = n.c.
8
9
10
11
12
13
14
15
C4…C7
4
1
3
2
5
v
1 = V
SENS
(V2) 2 = In/Out 3 = GND (V2) 4 = In/Out 5 = n.c.
Connecting Digital Sensors and Actuators

6.2 Connecting Digital Sensors and Actuators

For connecting digital sensors and actuators, 5-pin M12 connectors are available.
Fig.6: M12 connector for connecting digital sensors and actuators (C0…C3)
Connect the sensors and actuators to the device according to the pin assignment.
Fig.7: Pin assignment TBIL-M1-16DXP-B (C0…C3)
Fig.8: M12 connector for connecting digital sensors and actuators (C4…C7)
Connect the sensors and actuators to the device according to the pin assignment.
Fig.9: Pin assignment TBIL-M1-16DXP-B (C4…C7)
External Supply of Sensors and Actuators
The TBIL-I/O hub can also be used to connect externally powered sensors and actuators. For the external supply of sensors and actuators, observe the following safety measures:
Supply sensors and actuators from SELV or PELV power supplies. Decouple external circuits that are not designed as SELV/PELV systems by optocouplers,
relays or other measures.
12
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

7 Using the Device in Safety Applications

The device is designed in accordance with EN ISO 13849-1 “Safety of machinery - Safety-related parts of control systems”.

7.1 Safety Function

The safety function is executed by the higher-level system. The supply voltage (V2) of the outputs at C4…C7 can be safely switched off by an external safety relay or a safety PLC.
Safe Status
In the safe state, the outputs at C4…C7 are switched off (0). The disconnection is done extern­ally in the higher-level system.
Performance Level (PL)/SIL Level
In safety functions based only on fault exclusions, a maximum of PL d EN ISO 13849) and SIL 2 (EN IEC 61508) can be reached. The device is part of a safety-related overall system. The overall system must always be evaluated as a whole with regard to the requirements of EN ISO 13849-1 and EN IEC 61508.

7.1.1 Safety Characteristic Data for the Galvanic Isolation

Characteristic data Value Standard
PFH
D
Average frequency of dangerous failure per hour
MTTF
D
Mean Time To Failure Dangerous
PL (Performance Level) d EN/ISO 13849-1: 2016
SIL (Safety Integrity Level) 2 IEC/EN 61508
Diagnostic Coverage 0…99 % EN/ISO 13849-1: 2016
5 × 10-9 1/h IEC/EN 61508;
EN/IEC 62061; EN/ISO 13849-1
> 100 a EN/ISO 13849-1: 2016

7.1.2 Cited Standards

Standard Title
DIN EN ISO 13849-1:2016 Safety of machinery – Safety-related parts of control systems
DIN EN 62061:2005 + A1:2013 IEC 62061:2005
DIN EN 61508:2011 IEC 61508:2010
DIN EN 61131-2:2008 IEC 61131-2:2007
EN ISO/ISO 12100 Safety of machinery – General principles for design – Risk as-
Safety of machinery – Functional safety of safety-related elec­trical, electronic and programmable electronic control systems
Functional safety of electrical/electronic/programmable elec­tronic safety-related systems
Programmable controllers
sessment and risk reduction
V01.01 | 2018/11
13
Commissioning
Function Tests

7.2 Safety Planning

The operator is responsible for the safety planning.
Prerequisites
Perform a hazard and risk analysis. Develop a safety concept for the machine or plant. Calculate the safety integrity for the complete machine or plant. Validate the complete system.

7.3 Safe Commissioning

7.3.1 Installing Connecting Cables Safely

NOTICE
Incorrect connection of connecting cables
Danger of cross connections
Install and connect the cables safely and separately in accordance with
EN60204-1.
Install cables with cross-circuit protection if the safe installation of the cables is
not possible.

7.3.2 Switch-off Supply Voltage Safely

WARNING
1-pole switch-off the supply voltage
Safe separation not guaranteed
Always switch-off the supply voltage on both poles.

7.3.3 Connecting Sensors and Actuators

WARNING
External feed
Deactivation of the galvanic isolation
If the galvanic isolation is used, ensure on the application side that no external
feed can occur.
Do not supply DXP inputs externally that operate with potential that can be
safely switched off.

7.4 Function Tests

Function test should only be carried out by qualified personnel. Before commissioning the system, check and document the switch-off of the V2 voltage
group by an upstream safety relay.
Control the switching behavior of he output circuits. If the maximum duty cycle is reached: Execute switch-off of the V2 voltage group by the
safety relay to check the function of the safety system.
14
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

8 Parameterizing and Configuring

8.1 Parameters

IO-Link object directory – ISDU device parameters: Direct Parameter Page
ISDU Index
Hex. (Dec.)
0x00 (0)
Sub index Object name Access Length
[Byte]
Direct Parameter Page 1 read
only
0x07 Vendor ID read
0x08
0x09 Device ID read
0x0A
0x0B
only
only
16
2 0x013D
3 TBIL-M1-16DXP-B:
IO-Link object directory – ISDU device parameters: Identification
ISDU Index
Hex. (Dec.)
0x10 (16)
0x11 (17)
0x12 (18)
0x13 (19)
0x14 (20)
0x15 (21)
0x16 (22)
0x17 (23)
0x18 (24)
0x19 (25)
Object name Access Length
[Byte]
Vendor Name
Vendor Text read
Product Name
Product ID read
Product Text read
Serial Number
Hardware ID r/w 8 Hardware ID of the
Firmware Revision
Application Specific Tag
Function Tag read/
read only
only
read only
only
only
read only
read only
read/ write
write
16 Turck
32 www.turck.com
32 TBIL-M1-16DXP-B
16 Ident no. of the device:
32 I/O hub
16 Sequential
16 Firmware version of
32 Default "***" Customer-specific or
32 Default "***" The application-spe-
Meaning/ default value
100000881
serial number
device, e.g. V1.0
the device, e.g. V1.0.7.0
Meaning/default value
(ID for Turck)
0x1EB303
Comment
application-specific data can be stored in this field.
cific device function can be stored in this field.
V01.01 | 2018/11
15
Parameterizing and Configuring
Parameters
ISDU Index
Object name Access Length
[Byte]
Meaning/ default value
Comment
Hex. (Dec.)
0x1A (26)
Location Tag read/
write
32 Default "***" The application-spe-
cific installation loca­tion of the device can be stored in this field.
IO-Link object directory – ISDU device parameters: Preferred Index (parameters and diagnostics of the digital in- and outputs)
ISDU Index
Hex. (dec.)
0x40 (64)
0x41 (65)
0x42 (66)
0x43 (67)
0x44 (68)
0x45 (69)
0x46 (70)
Diagnostics
0x50 (80)
0x51 (81)
Object name Access Length
[Byte]
Parameter ID read/
4 Customer-specific ID, for free use
write
Inverting Input
Activate Output
Impulse Stretching
read/ write
read/ write
read/ write
2 Invert digital input
2 Activate output
16 Pulse stretching input
Input
Short Circuit Recovery
Failsafe read/
read/ write
2 Manual output reset after overcurrent
4 Output After Error
write
Under Voltage
read/ write
2 Enable undervoltage diagnosis V2/Under-
Diagnostics
Supply Error read
2 n Undervoltage supply V1/V2
only
Output Short Circuit
read only
2 Overcurrent output 0…15
Meaning
voltage value for V1 and V2
n Overcurrent Vsens Connector C0…C7
16
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Invert Digital Input – 0x41 (65), Sub Index 0
This parameter inverts the state of the digital input in the process image.
Format Length
Byte 1 byte 1 bit per channel
Default values are shown in bold.
Value Meaning
0 No
1 Yes Input signal inverted
Byte 0 Byte 1
Bit offset Bit offset
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.
Activate Output – 0x42 (66), Sub Index 0
this parameeter activates or deactivates the output function of the digital channel.
Format Length
Byte 1 byte 1 bit per channel
Default values are shown in bold.
Value Meaning
0 No Output function deactivated, channel can only be used as in-
put
1 Yes
Output function activated, channel can be used as in- or out­put
Byte 0 Byte 1
Bit offset Bit offset
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.
V01.01 | 2018/11
17
Parameterizing and Configuring
Parameters
Pulse Stretching Input – 0×43 (67)
This parameter defines the duration of the pulse stretching for digital input edges in multiples of 10 ms. This allows that even short signals with longer PLC cycle times can be detected.
Format Length
Array of Bytes 8 byte 1 byte per channel
Default values are shown in bold.
Value Meaning
0 disabled
1 1…255 Pulse stretching input [*10 ms]
Bit offset Bit offset
0 8 16 24 32 40 48 56 64 72 80 88 96 104 112 120
Sub index Sub index
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
Pulse stretching deactivated
NOTE
This parameter can also be set for all connectors of the module via the IODD.
Manual Output Reset after Overcurrent – 0x44 (68), Sub Index 0
This parameter defines if a manual reset is necessary after an overcurrent occurred at the digital channel.
Format Length
Byte 1 byte 1 bit per channel
Default values are shown in bold.
Value Meaning
0 No
Automatic recovery mode
1 Yes Controlled recovery mode (output has to be reset manually)
Byte 0 Byte 1
Bit offset Bit offset
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.
18
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Output After Error – 0x45 (69), Sub Index 0
This parameter defines the behavior of the output in case of an interruption of the IO-Link com­munication.
Format Length
Array of Bytes 2 byte 2 bit per channel
Default values are shown in bold.
Value Meaning
00 0
Set output to 0
01 1 Set output to 1
10 Current value Hold current value
11 reserved
Byte 3 Byte 2 Byte 1 Byte 0
Bit offset Bit offset Bit offset Bit offset
6 4 2 0 6 4 2 0 6 4 2 0 6 4 2 0
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
NOTE
This parameter can also be set for all connectors of the module via the IODD.
V01.01 | 2018/11
19
Parameterizing and Configuring
Parameters
Enable Undervoltage Diagnosis V2/Undervoltage Value for V1 and V2 – 0×46 (70), Sub Index 0
This parameter defines whether undervoltage diagnostics are sent to in case of an V2 under­voltage. Additionally it defines the threshold values for undervoltage diagnostics for V1 and V2.
Format Length
Array of Bytes 2 byte 2 bit per module
The default values are written in bold.
Value Meaning
Activate V2 diagnostics
0 No
1 Yes
Threshold value for undervoltage diagnostics V1 and V2
0 Standard
(IEC 61131-2)
1 Extended lower threshold: 17.5 V
V2 diagnostics activated
lower threshold: 19.2 V upper threshold: 20.4 V
Byte 0
Bit offset
7 6 5 4 3 2 1 0
- - - - - - Activate diagnostics Threshold
Byte 1
Bit offset
7 6 5 4 3 2 1 0
- - - - - - - -
20
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

9 Operating

CAUTION
Operating the device outside the specification
Slight injuries and equipment damage possible.
Operate the unit only within the operating temperature specified in the tech-
Use only thermally suitable connection cables.

9.1 Process Input Data

nical data.
Byte no.
Inputs
0
1
Module diagnostics
2
Connector diagnostics – overcurrent sensor supply
3
Channel diagnostics – overcurrent output
4
5
Bit offset
7 6 5 4 3 2 1 0
C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4
Group diagnos­tics
Overcur­rent C7
Overcur­rent C3P2
Overcur­rent C7P2
- - - Under-
Overcur­rent C6
Overcur­rent C3P4
Overcur­rent C7P4
Overcur­rent C5
Overcur­rent C2P2
Overcur­rent C6P2
Overcur­rent C4
Overcur­rent C2P4
Overcur­rent C6P4
NOTE
The diagnoses can also be accessed via IO-Link indices.
voltage V2
Overcur­rent C3
Overcur­rent C1P2
Overcur­rent C6P2
Under­voltage V1
Overcur­rent C2
Overcur­rent C1P4
Overcur­rent C5P4
- -
Overcur­rent C1
Overcur­rent C0P2
Overcur­rent C4P2
Overcur­rent C0
Overcur­rent C0P4
Overcur­rent C4P4
V01.01 | 2018/11
21
Operating
Process Output Data
Designation Meaning
Inputs
CxPy 0 Input inactive
1 Input active
Module diagnostics
Group diagnostics 0 No diagnostic mes-
sage
1 Module diagnostics
active
Undervoltage Vx 0 No diagnostic message
1 Undervoltage of supply voltage V1 and V2
Connector diagnostics – overcurrent sensor supply
Overcurrent Cx 0 No diagnostic mes-
sage
1 Overload at the sensor/actuator supply at the connector. At mod-
ules with group diagnostics all connector-LEDs of the supply group flash simultaneously in case of an error.
Channel diagnostics – overcurrent output
Overcurrent CxPy 0 No diagnostic mes-
sage
1 Overlaod at the output/short-circuit
Evaluate the bit to monitor the dia-
gnostics cyclically.
ð Bit = 0: no diagnostics active
ð Bit = 1: Module diagnostics
Bit = 1: Evaluate further diagnostic
bits to determine the origin of the diagnosctic message.

9.2 Process Output Data

Byte no.
Outputs
0
1
Designation Meaning
CxPy 0 Output inactive
Bit offset
7 6 5 4 3 2 1 0
C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4
C7P2 C7P4 C6P2 C6P4 C5P2 C5P4 C4P2 C4P4
1 Output active
22
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

9.3 LED Displays

The device has the following LED indicators:
n IO-Link communication n I/O status

9.3.1 IO-Link

IO-Link LED Meaning
Green flashing IO-Link communication error-free, valid process data are sent
Red IO-Link communication error or module error
Red flashing (1 Hz)
Off no voltage supply

9.3.2 Channel-LEDs

LED 0…15 Meaning (input) Meaning (output)
Green Input active Output active
Red flashing (0.5 Hz)
Red Output active, overload/overcurrent
Off Input inactive Output inactive
IO-Link communication error-free, invalid process data or diagnostic message
Overload of the sensor supply In devices with group diagnostics, all connector-LEDs of the supply group flash simultaneously in case of an error.
at output
V01.01 | 2018/11
23
Operating
Evaluating Diagnostic Data

9.4 Evaluating Diagnostic Data

Group Diagnostics: Undervoltage V1/V2 and Overcurrent Sensor Supply – 0x50 (80), Sub Index 0
Indicates errors in the module and sensor supply:
n Group diagnostics: Diagnostics pending at the module n Undervoltage V1 (per module) n Undervoltage V2 (per module) n Overcurrent sensor supply (per connector)
Format Length
Array of Bytes 2 byte
0 = no diagnostics 1 = diagnostic message
Byte 0
Bit offset
15 14 13 12 11 10 9 8
Group diagnostics - - - Undervoltage
supply V2
Byte 1
Bit offset
7 6 5 4 3 2 1 0
Overcur­rent Vsens C7
Overcur­rent Vsens C6
Overcur­rent Vsens C5
Overcur­rent Vsens C4
Overcur­rent Vsens C3
Undervoltage supply V1
Overcur­rent Vsens C2
Overcur­rent Vsens C1
- -
Overcur­rent Vsens C0
24
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Overcurrent Output – 0x51 (81), Sub Index 0
Indicates an overcurrent at the corresponding digital output.
Format Length
Array of Bytes 2 byte 1 bit per output
0 = no diagnostics 1 = diagnostic message
Byte 0
Bit offset
7 6 5 4 3 2 1 0
Overcur­rent C3P2
Byte 1
Bit offset
7 6 5 4 3 2 1 0
Overcur­rent C7P2
Overcur­rent C3P4
Overcur­rent C7P4
Overcur­rent C2P2
Overcur­rent C6P2
Overcur­rent C2P4
Overcur­rent C6P4
Overcur­rent C1P2
Overcur­rent C6P2
Overcur­rent C1P4
Overcur­rent C5P4
Overcur­rent C0P2
Overcur­rent C4P2
Overcur­rent C0P4
Overcur­rent C4P4
V01.01 | 2018/11
25
Operating
IO-Link Error Codes

9.5 IO-Link Events

Event Code
0x5111 Undervoltage
0x5112 Undervoltage
0x7710 Overcurrent Vsens
Description Event Mode
supply V1
supply V2
connector x or overcurrent output x

9.6 IO-Link Error Codes

Error code Description
0x8011 Index not available
0x8012 Sub Index not available
0x8023 Accesss denied Index cannot be written
0x8030 Parameter value out of range Parameter value out of range
0x8033 Parameter length overrun Length of data to be written does not
0x8034 Parameter length underrun
0x8035 Function not available Function not available in the device
0x8041 Inconsistent parameter set Inconsistent parameters
0xF4 (appears) Undervoltage at the
0xB4 (disappears)
0xF4 (appears) Undervoltage at the
0xB4 (disappears)
0xF4 (appears) Group event for overcurrent:
0xB4 (disappears)
supply group V1 (C0…C3)
supply group V2 (C4…C7, Class B supply)
Overcurrent of the sensor supply at one of the connectors (C0…C7) or overcurrent at one of the outputs (DO0…DO15) The mapped diagnostics in the process image of the inputs show which slot or output detects an overcurrent.
match the length defined for this para­meter.
26
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

10 Troubleshooting

If the device does not function as expected, first check whether ambient interference is present. If there is no ambient interference present, check the connections of the device for faults. If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type.
V01.01 | 2018/11
27
Maintenance
Returning Devices

11 Maintenance

Ensure that the plug connections and cables are always in good condition. The devices are maintenance-free, clean dry if required.

12 Repair

The device must not be repaired by the user. The device must be decommissioned if it is faulty. Observe our return acceptance conditions when returning the device to Turck.

12.1 Returning Devices

Returns can only be accepted if a declaration of decontamination is enclosed with the device. The declaration can be downloaded from
https://www.turck.de/en/retoure-service-6079.php
and must be completely filled in, and affixed securely and weather-proof to the outside of the packaging.

13 Disposal

The devices must be disposed of correctly and must not be included in normal household garbage.
28
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

14 Technical Data

Technical Data
Power supply
Operating/load voltage 24 VDC
Permissible range 18…30 VDC
Operating current From V1: < 100 mA
Total current Max. 4 A per voltage group,
Sensor/actuator supply VAUX1 Supply connector C0…C3 from V1 short-circuit proof,
Sensor/actuator supply VAUX2 Supply connector C4…C7 from V2 short-circuit proof,
Potential isolation Galvanic isolation from V1 and V2 voltage group, voltages
Inputs
Number of channels 16 digital pnp inputs (EN 61131-2)
Type of input diagnostics Type of input diagnostics
Signal voltage, low level -3…5 VDC (EN 61131-2, type 1 and 3)
Signal voltage, high level 11…30 VDC (EN 61131-2, type 1 and 3)
Input delay 2.5 ms
Max. input current 15 mA
Outputs
Number of channels 16 digital pnp outputs
Type of output diagnostics Channel diagnostics
Output voltage 24 VDC from supply voltage
Output current per channel 1.8 A, short-circuit-proof
Output delay 1.3 ms
Load type Ohmic, inductive lamp load
IO-Link
IO-Link specification Specified according to version 1.1
Parameterization FDT/DTM, IODD
Transmission rate COM 2: 38,4 kbit/s
Transmission physics 3-wire physics (PHY2)
Minimum cycle time 4.2 ms
Connectors
IO-Link M12 × 1, 5-pole
Input/output M12 × 1, 5-pole
Permissible torques
n IO-Link n I/O channels n Mounting (M4 screws)
From V2: < 85 mA
V1 + V2: max. 5.4 A
120mA per connector, with diagnostics
120mA per connector, with diagnostics
up to 500 VDC
0.8 Nm
0.8 Nm
0.5 Nm
V01.01 | 2018/11
29
Technical Data
Technical Data
Standard/Directive conformity
Vibration test According to EN 60068-2-6
Shock test According to EN 60068-2-27
Drop and topple According to IEC 60068-2-31/IEC 60068-2-32
Electro-magnetic compatibility According to EN 61131-2/-6-4
Approvals CE, cULus
General Information
Dimensions (B × L × H) 54 × 150 × 27.4 mm
Operating temperature -40...+55 °C (at total current up to 5.4 A)
-40...+70 °C (at total current up to 4 A)
Storage temperature -40…+85 °C
Protection class IP67/IP69K
MTTF 79 years
Housing material PA6-GF30
Housing color Black
Halogen-free Yes
Mounting 4 mounting holes, Ø 4,3 mm
30
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com

15 Appendix: Declaration of Conformity

EU-Konformitätserklärung Nr.: 5035-2M
EU Declaration of Conformity No.:
Wir/ We: HANS TURCK GMBH & CO KG
WITZLEBENSTR. 7, 45472LHEIM A.D. RUHR
erklären in alleiniger Verantwortung, dass die Produkte
declare under our sole responsibility that the products
Kompakte I/O Module in IP20/IP67:
Compact I/O modules in IP20/IP67:
Typen / types: FDN20-*, FDNL-*, FDNP-*, FDP20-*, FGDP-*, FGEN-*, FLDP-*, FLIB-*, FXEN-*, SDPX-*, TBDP-*, TBEN-*, TBIL-*, TBPN-*
auf die sich die Erklärung bezieht, den Anforderungen der folgenden EU-Richtlinien durch Einhaltung der folgenden Normen gegen:
to which this declaration relates are in conformity with the requirements of the following EU-directives by compliance with the following standards:
EMV - Richtlinie /EMC Directive 2014 / 30 / EU 26.02.2014 EN 61131-2:2007 (Abschnitte / section 8, 9, 10)
RoHS Richtlinie /RoHS Directive 2011 / 65 / EU 08.06.2011
Weitere Normen, Bemerkungen:
additional standards, remarks:
Zusätzliche Informationen:
Supplementary infomation: