I/O Hub for Connection of Digital Signals to IO-Link Master
16 Universal Digital Channels, PNP
TBIL-M1-16DXP
Type designation TBIL-M1-16DXP
Ident-No. 6814102
■ Rugged, fully potted I/O hub in IP67
■ IO-Link diagnostics for short-circuit and
supply voltage
■ 2 universal digital channels per port
■ Metal connector
Power dissipation, typical
Fieldbus connection technology 1 × M12
Number of channels 16 digital PNP inputs (EN 61131-2)
Type of input diagnostics Group diagnostics
Low level signal voltage -3…5 VDC (EN 61131-2, type 1 and 3)
High level signal voltage 11…30 VDC (EN 61131-2, type 1 and 3)
Input delay 0.010 ms
Electrical isolation inputs to FE 500VDC
Number of channels 16 digital PNP outputs
Type of output diagnostics Group diagnostics
Output voltage 24 VDC
Output current per channel 0.5 A, short-circuit proof
Simultaneity factor 0.35
Output delay 0.15 ms
Load type resistive, inductive, lamp load
Electrical isolation outputs to FE 500 VDC
IO-Link
Frame type 2.6
Transmission rate COM 2 / 38.4 kbps
Programming FDT/DTM
Transmission physics corresponds to 3-wire physics (PHY2)
Vibration test acc. to EN 60068-2-6
Shock test acc. to EN 60068-2-27
Electromagnetic compatibility acc. to EN 61131-2:2007
ð 3.2 W
Dimensions (W x L x H) 54 x 150 x 27.4mm
Operating temperature -40 … 70 °C
Storage temperature -40 …85 °C
Protection class IP67
IP69K
MTTF 96 years
Housing material PA6-GF30
Mounting 4 mounting holes Ø 4.3 mm
Edition • 2019-01-21T19:37:33+01:00
1 / 4 TURCK Inc.
I/O Hub for Connection of Digital Signals to IO-Link Master
16 Universal Digital Channels, PNP
TBIL-M1-16DXP
Pinning and wiring diagram
Accessories
Suitable IO-Link cables (Example):
2 m: RK 4T-2-RS 4T (Ident. no. U2151-3)
5 m: RK 4T-5-RS 4T (Ident. no. U2158-15)
Further lengths and variants in the product catalog or on request
Suitable IO-Link masters (Example):
BL20-E-4IOL (Ident. no. 6827385)
BL67-4IOL (Ident. no. 6827386)
SDPX-IOL4-0001 (Ident. no. 6825480)
Further types in the product catalog or on request
M12 x 1 IO-Link
Accessories
Suitable Sensor supply cables (Example):
2 m: RK 4.4T-2-RS 4.4T Ident. no. (U2445)
5 m: RK 4.4T-5-RS 4.4T Ident. no. (U2167-3)
Further lengths and variants in the product catalog or on request
Optional Accessories
Closure cap VZ3 M12 Ident. no. (01202601)
Labels KS9/20 Ident. no. (10267953)
M12 x 1 I/O Port
Edition • 2019-01-21T19:37:33+01:00
2 / 4 TURCK Inc.
I/O Hub for Connection of Digital Signals to IO-Link Master
16 Universal Digital Channels, PNP
TBIL-M1-16DXP
Module LED status
LED Color Status Description
IO-Link
Red
I/O LED Status
LED Color Status Description
C1 A / B … C8 A / B Green ON Input or output active
C … = slot number, A / B = Signal LED (signal A = pin 4, B = signal pin 2)
OFF Power off Green
Flashing IO-Link communication OK,
valid process data is sent or received
ON IO-Link communication or module error
Flashing IO-Link communication OK,
invalid process data or diagnosis enabled
ON Output active with overload / short circuit Red
Flashing Power overload at the corresponding port. Both port LEDs are flashing.
OFF Input or output inactive
Edition • 2019-01-21T19:37:33+01:00
3 / 4 TURCK Inc.
I/O Hub for Connection of Digital Signals to IO-Link Master
16 Universal Digital Channels, PNP
TBIL-M1-16DXP
Process Data
Byte Bit 7
MSB
Inputs 0 DI8
C4P2 (B)
1 DI16
C8P2 (B)
Outputs 0 DO8
C4P2 (B)
1 DO16
C8P2 (B)
C… = slot no., P… = pin no.
Diagnostics / Events
Class/Qualifier
Mode Type Instance
0xC0 0x30 0x04 0xF4 appears 0x5110
0x80 0x30 0x04 0xB4 disappears 0x5110
0xC0 0x30 0x04 0xF4 appears 0x5111
0x80 0x30 0x04 0xB4 disappears 0x5111
0xC0 0x30 0x04 0xF4 appears 0x7710
0x80 0x30 0x04 0xB4 disappears 0x7710
0xC0 0x30 0x04 0xF4 appears 0x5000
0x80 0x30 0x04 0xB4 disappears 0x5000
Device Parameters
ISDU
Index Sub-
0x0C 0x02 Data Storage Lock R/W 1Bit Boolean Lock Parameter Upload
0x10 0x00 Vendor Name R 16 Bytes String TURCK
0x11 0x00 Vendor Text R 32 Bytes String www.turck.com
0x12 0x00 Product Name R 32 Bytes String TBIL-M1-16DXP
0x13 0x00 Product ID R 16 Bytes String 6814102
0x14 0x00 Product Text R 32 Bytes String I/O HUB
0x15 0x00 Serial Number R 16 Bytes String
0x17 0x00 FW Revision R 16 Bytes String
0x18 0x00 Application Specific Tag R/W 32 Bytes String Free text e.g for application name
0x40 0x00 Parameter ID R/W 4 Bytes Unsigned 32 ID no. e.g. for module identification
0x41 0x00 Inverting Input R/W 2 bytes Unsigned 16 Inverting the input logic
0x42 0x00 Activate Output R/W 2 Bytes Unsigned 16 Activate Output
0x43 0x00 Impulse Stretching R/W 16 Bytes Unsigned 8 Expansion of input pulse
0x44 0x00 Short Circuit Recovery R/W 2 Bytes Unsigned 16 Behaviour after short circuit output
0x45 0x00 Failsafe R/W 2 Bytes Unsigned 32 Behavior on communication loss
Parameter Name Access
Index
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
DI7
C4P4 (A)
DI15
C8P4 (A)
DO7
C4P4 (A)
DO15
C8P4 (A)
R: Read
W: Write
DI6
C3P2 (B)
DI14
C7P2 (B)
DO6
C3P2 (B)
DO14
C7P2 (B)
Code Description
Data Length Data Type
DI5
C3P4 (A)
DI13
C7P4 (A)
DO5
C3P4 (A)
DO13
C7P4 (A)
Supply voltage too high
Supply voltage too low
Short circuit to GND
Hardware error
DI4
C2P2 (B)
DI12
C6P2 (B)
DO4
C2P2 (B)
DO12
C6P2 (B)
0: Unlocked; 1: Locked
Default: 0
Default: ***
Default: 0x0000
0: Normal; 1: Inverted
Default: 0x00
0: Inactive; 1: Active
Default: 0xFFFF
0: Off, 1-255; Basis: 10 ms
Default: 0x00
0: Automatic
1: Controlled (output newly set)
Default: 0x0000
00: Output on 0
01: Output on 1
10: Last value
11: Reserved
Default: 0x0000
DI3
C2P4 (A)
DI11
C6P4 (A)
DO3
C2P4 (A)
DO11
C6P4 (A)
DI2
C1P2 (B)
DI10
C5P2 (B)
DO2
C1P2 (B)
DO10
C5P2 (B)
LSB
DI1
C1P4 (A)
DI9
C5P4 (A)
DO1
C1P4 (A)
DO9
C5P4 (A)
Edition • 2019-01-21T19:37:33+01:00