Compact Multiprotocol I/O Module for Ethernet
4 Analog Outputs, Configurable as Voltage or Current
TBEN-S2-4AO
Type designation TBEN-S2-4AO
Ident-No. 6814028
Supply
Supply voltage 24 VDC
Admissible range 18…30 VDC
Total current max. 4 A per voltage group
Total current V1 + V2 max. 5.5 A at 70 °C per mod-
ule
Voltage supply connection 2 × M8, 4-pin
Operating current V1: min. 50 mA, max. 110 mA
V2: min.30 mA, max. 70 mA
Sensor/Actuator supply V
Electrical isolation galvanic isolation of the voltage groups V1 and V2,
AUX2
supply of ports C0-C3 from V2
not short-circuit proof, max. 4 A per group C0-C3
voltages up to 500 VAC
■ Each channel can be selected for volt-
age
■ Output ranges:
■ Voltage: 0/1…5 V, +/-10 V, 0/2…10 V
■ Current: 0/4…20 mA
■ FLC/ARGEE programmable
■ PROFINET® device, EtherNet/IP™ de-
vice or Modbus® TCP slave
■ Integrated Ethernet switch
■ Supports 10 Mbps/100 Mbps
■ 2x M8, 4-pin, Ethernet fieldbus connec-
tion
■ Male M8, 4-pin, for power supply
■ Separated power groups for safety
shutdown
■ Glass-fiber reinforced housing
■ Shock and vibration tested
■ Fully potted module electronics
■ Protection classes IP65 / IP67 / IP69K
System data
Fieldbus transmission rate 10 Mbps/100 Mbps
Fieldbus connection technology 2 × M8, 4-pin
Protocol detection automatic
Web server default: 192.168.1.254
Service interface Ethernet via P1 or P2
Field Logic Controller (FLC)
Supported from firmware version 3.0.2.0
Released from ARGEE version 2.0.25.0
Modbus TCP
Addressing Static IP, DHCP
Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23
Number of TCP connections 8
Input register start address 0 (0x0000 hex)
Output register start address 2048 (0x0800 hex)
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification
Quick Connect (QC) < 500 ms
Device Level Ring (DLR) supported
Class 3 connections 3
Class 1 connections 10
Input Assembly Instance 103
Output Assembly Instance 104
Configuration Assembly Instance 106
Edition • 2019-01-21T19:11:01+01:00
1 / 5 TURCK Inc.
Compact Multiprotocol I/O Module for Ethernet
4 Analog Outputs, Configurable as Voltage or Current
TBEN-S2-4AO
PROFINET
Addressing DCP
Conformance class B (RT)
MinCycleTime 1 ms
Fast Start-Up (FSU) < 500 ms
Diagnostics acc. to PROFINET alarm handling
Topology detection supported
Automatic addressing supported
Media Redundancy Protocol (MRP) supported
Analog outputs
Number of channels 4
Operating modes Voltage, current
Resolution 16 bit
Operating mode voltage
Load resistor
Output signal type Common ground
Output signal range 0...10V, +/- 10V, 2...10V, 0...5V, 1...5V
Cycle time 4 ms
Basic error at 25 °C 0.1 %
Repeat accuracy 0.05 %
Temperature coefficient < 20 ppm/°C
Error total (FSR)
1 kò
ð 0.23%
Operating mode current
Load resistor
Output signal type Common ground
Output signal range 0…20 mA, 4…20 mA
Cycle time 4 ms
Basic error at 25 °C 0.15 %
Repeat accuracy 0.05 %
Temperature coefficient < 20 ppm/°C
Error total (FSR)
Standard/Directive conformity
Vibration test acceleration to 20 g
Shock test acc. to EN 60068-2-27
Drop and topple acc. to EN 60068-2-31/IEC 60068-2-32
Electromagnetic compatibility acc. to EN 61131-2
Approvals and certificates CE, FCC
UL Certificate cULus LISTED 21 W2, Encl.Type 1 IND.CONT.EQ.
General Information
Dimensions (W x L x H) 32 x 144 x 32mm
Operating temperature -40…+70 °C
Storage temperature -40…+85 °C
Altitude max. 5000 m
Protection class IP65
MTTF 244 years acc. to SN 29500 (Ed. 99) 20 °C
Housing material PA6-GF30
Housing color Black
Material label Polycarbonate
Halogen-free yes
Mounting 2 mounting holes Ø 4.6 mm
600 ò
ð 0.28 %
acc. to EN 60068-2-6
IP67
IP69K
Note the numbering of the IO range:
From firmware version 3.0.2.0 and higher ports C0
to C3 and channels CH0 to CH3 are counted. For
more details on the corresponding change see manual.
Edition • 2019-01-21T19:11:01+01:00