Turck TBEN-S1-8DIP Data Sheet

Compact Multiprotocol I/O Module for Ethernet 8 Digital PNP Inputs, Input Diagnostics per Group TBEN-S1-8DIP
Type designation TBEN-S1-8DIP
Ident-No. 6814020
Supply
Total current max. 4 A per voltage group V1 Voltage supply connection 2 × M8, 4-pin Operating current V1: max. 150 mA mA Sensor/Actuator supply V
Electrical isolation galvanic isolation of the voltage groups V1 and V2,
AUX1
supply of ports C0-C7 from V1
short-circuit proof, 0.5 A for group C0-C3, C4-C7
voltages up to 500 VAC
Male M8, 4-pin, for power supply
Input diagnostics by group
FLC/ARGEE programmable
PROFINET® device, EtherNet/IP™ de-
vice or Modbus® TCP slave
Integrated Ethernet switch
Supports 10 Mbps/100 Mbps
2x M8, 4-pin, Ethernet fieldbus connec-
tion
Glass-fiber reinforced housing
Shock and vibration tested
Fully potted module electronics
Protection classes IP65 / IP67 / IP69K
System data
Fieldbus transmission rate 10 Mbps/100 Mbps Fieldbus connection technology 2 × M8, 4-pin Protocol detection automatic Web server default: 192.168.1.254 Service interface Ethernet via P1 or P2
Field Logic Controller (FLC)
Supported from firmware version 3.1.4.0 Released from ARGEE version 2.0.24.0
Modbus TCP
Addressing Static IP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 8 Input register start address 0 (0x0000 hex) Output register start address 2048 (0x0800 hex)
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification Quick Connect (QC) < 500 ms Device Level Ring (DLR) supported Class 3 connections 3 Class 1 connections 10 Input Assembly Instance 103 Output Assembly Instance 104 Configuration Assembly Instance 106
Edition • 2019-01-21T19:00:46+01:00
1 / 6 TURCK Inc.
Compact Multiprotocol I/O Module for Ethernet 8 Digital PNP Inputs, Input Diagnostics per Group TBEN-S1-8DIP
PROFINET
Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Fast Start-Up (FSU) < 500 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) supported
Digital inputs
Number of channels 8 Connectivity inputs M8, 3-pin Input type PNP Type of input diagnostics Group diagnostics Switching threshold EN 61131-2 Typ 3, PNP Low level signal voltage < 5 V High level signal voltage > 11 V Low level signal current < 1.5 mA High level signal current > 2 mA Input delay 0.2ms / 3 ms ms Electrical isolation galvanic isolation to P1/P2
, voltages up to 500 VDC
Standard/Directive conformity
Vibration test acceleration to 20 g
acc. to EN 60068-2-6 Shock test acc. to EN 60068-2-27 Drop and topple acc. to EN 60068-2-31/IEC 60068-2-32 Electromagnetic compatibility acc. to EN 61131-2 Approvals and certificates CE, FCC UL Certificate cULus LISTED 21 W2, Encl.Type 1 IND.CONT.EQ.
General Information
Dimensions (W x L x H) 32 x 144 x 32mm Operating temperature -40…+70 °C Storage temperature -40…+85 °C Altitude max. 5000 m Protection class IP65
IP67
IP69K MTTF 319 years acc. to SN 29500 (Ed. 99) 20 °C Housing material PA6-GF30 Housing color Black Material label Polycarbonate Halogen-free yes Mounting 2 mounting holes � 4.6 mm
Note the numbering of the IO range:
From firmware version 3.1.4.0 and higher ports C0
to C7 and channels CH0 to CH7 are counted. For
more details on the corresponding change see man-
ual.
Edition • 2019-01-21T19:00:46+01:00