Compact multiprotocol I/O module for Ethernet
8 IO-Link Master Channels
4 Universal Digital PNP Channels, 2 A, Channel Diagnostics
TBEN-LL-8IOL
Type designation TBEN-LL-8IOL
Ident-No. 100003910
Supply
Supply voltage 24 VDC
Admissible range 18…30 VDC
Total current max. 9 A per voltage group
Total current V1 + V2 max. 11 A
Voltage supply connection M12 L-coded connector
Sensor/Actuator supply V
Sensor/Actuator supply V
Electrical isolation galvanic isolation of the voltage groups V1 and V2,
AUX1
AUX2
Supply from V1
Short-circuit proof, max. 4 A per X0 & X4, max. 2 A
per slot X1-X3, X5-X7
Class B supply from V2
Short-circuit proof, max. 4 A per X4 & X5, max. 2 A
per X6 & X7
voltages up to 500 VAC
■ PROFINET Device, Ethernet/IP Device
or Modbus TCP Slave
■ Integrated Ethernet switch
■ 10 Mbps/100 Mbps supported
■ 2 × M12, 4-pin, D-coded Ethernet field-
bus connection
■ Glass fiber reinforced housing
■ Shock and vibration tested
■ Fully potted module electronics
■ Protection classes IP65, IP67, IP69K
■ M12, L-coded connector for power sup-
ply
■ M12 ports for IO-Link master, 5-pin
■ IO-Link master port class A and port
class B
■ IO-Link Protocol 1.1
System data
Fieldbus transmission rate 10 Mbps/100 Mbps
Fieldbus connection technology 2 x M12, 4-pin, D-coded
Protocol detection automatic
Service interface Ethernet via XF1 or XF2
Modbus TCP
Addressing Static IP, DHCP
Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23
Number of TCP connections 8
Input register start address 0 (0x0000 hex)
Output register start address 2048 (0x0800 hex)
Ethernet/IP
Addressing acc. to EtherNet/IP specification
Quick Connect (QC) < 150 ms
Device Level Ring (DLR) supported
Class 3 connections (TCP) 3
Class 1 connections (CIP) 10
Input Assembly Instance 101
Output Assembly Instance 102
Configuration Assembly Instance 106
Edition • 2020-10-14T22:39:34+02:00
1 / 6 TURCK Inc. ñ 3000 Campus Drive Minneapolis, MN 55441-2656 ñ Phone: 763-553-7300 ñ Application Support: 1-800-544-7769 ñ Fax 763-553-0708 ñ www.turck.com

Compact multiprotocol I/O module for Ethernet
8 IO-Link Master Channels
4 Universal Digital PNP Channels, 2 A, Channel Diagnostics
TBEN-LL-8IOL
PROFINET
Version 2.35
Addressing DCP
Conformance class B (RT)
MinCycleTime 1 ms
Fast Start-Up (FSU) < 150 ms
Diagnostics acc. to PROFINET alarm handling
Topology detection supported
Automatic addressing supported
Media Redundancy Protocol (MRP) supported
Netload class 3
Digital inputs
Number of channels 4 DXP + 8 SIO
Connectivity inputs M12, 5-pin
Input type PNP
Type of input diagnostics Channel diagnostics
Switching threshold EN 61131-2 type 3, pnp
Low level signal voltage < 5 V
High level signal voltage > 11 V
Low level signal current < 1.5 mA
High level signal current > 2 mA
Input delay 0.05 ms
Electrical isolation Galvanically isolated to the fieldbus
voltages up to 500 VAC
Digital outputs
Number of channels 4 DXP
Connectivity outputs M12, 5-pin
Output type PNP
Type of output diagnostics Channel diagnostics
Output voltage 24 VDC from potential group
Output current per channel 2 A, short-circuit proof
IO-Link
Number of channels 8
IO-Link Pin 4 in IOL mode
IO-Link specification Version 1.1
IO-Link port type Class A and Class B
Frame type Supports all specified frame types
Supported devices Max. 32 byte input / 32 byte output
Transmission rate 4.8 kbps (COM 1) / 38.4 kbps (COM 2) / 230 kbps
(COM 3)
Standard/Directive conformity
Vibration test acceleration to 20 g
acc. to EN 60068-2-6
Shock test acc. to EN 60068-2-27
Drop and topple acc. to EN 60068-2-31/IEC 60068-2-32
Electromagnetic compatibility acc. to EN 61131-2
Approvals and certificates CE,
FCC,
FM Class I, Zone 2,
UV-resistant in accordance with DIN EN ISO
4892-2A (2013)
UL Certificate cULus LISTED 21 W2, Encl.type 1 IND.CONT.EQ.
Edition • 2020-10-14T22:39:34+02:00