TURCK TBEN-LL-8IOL User Manual

Compact multiprotocol I/O module for Ethernet 8 IO-Link Master Channels 4 Universal Digital PNP Channels, 2 A, Channel Diagnostics TBEN-LL-8IOL
Type designation TBEN-LL-8IOL
Ident-No. 100003910
Supply voltage 24 VDC Admissible range 18…30 VDC
Total current max. 9 A per voltage group
Total current V1 + V2 max. 11 A Voltage supply connection M12 L-coded connector Sensor/Actuator supply V
Sensor/Actuator supply V
Electrical isolation galvanic isolation of the voltage groups V1 and V2,
AUX1
AUX2
Supply from V1
Short-circuit proof, max. 4 A per X0 & X4, max. 2 A
per slot X1-X3, X5-X7
Class B supply from V2
Short-circuit proof, max. 4 A per X4 & X5, max. 2 A
per X6 & X7
voltages up to 500 VAC
PROFINET Device, Ethernet/IP Device
or Modbus TCP Slave
Integrated Ethernet switch
10 Mbps/100 Mbps supported
2 × M12, 4-pin, D-coded Ethernet field-
bus connection
Glass fiber reinforced housing
Shock and vibration tested
Fully potted module electronics
Protection classes IP65, IP67, IP69K
M12, L-coded connector for power sup-
ply
M12 ports for IO-Link master, 5-pin
IO-Link master port class A and port
class B
IO-Link Protocol 1.1
System data
Fieldbus transmission rate 10 Mbps/100 Mbps Fieldbus connection technology 2 x M12, 4-pin, D-coded Protocol detection automatic Service interface Ethernet via XF1 or XF2
Modbus TCP
Addressing Static IP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 8 Input register start address 0 (0x0000 hex) Output register start address 2048 (0x0800 hex)
Ethernet/IP
Addressing acc. to EtherNet/IP specification Quick Connect (QC) < 150 ms Device Level Ring (DLR) supported Class 3 connections (TCP) 3 Class 1 connections (CIP) 10 Input Assembly Instance 101 Output Assembly Instance 102 Configuration Assembly Instance 106
Edition • 2020-10-14T22:39:34+02:00
1 / 6 TURCK Inc. ñ 3000 Campus Drive Minneapolis, MN 55441-2656 ñ Phone: 763-553-7300 ñ Application Support: 1-800-544-7769 ñ Fax 763-553-0708 ñ www.turck.com
Compact multiprotocol I/O module for Ethernet 8 IO-Link Master Channels 4 Universal Digital PNP Channels, 2 A, Channel Diagnostics TBEN-LL-8IOL
PROFINET
Version 2.35 Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Fast Start-Up (FSU) < 150 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) supported Netload class 3
Digital inputs
Number of channels 4 DXP + 8 SIO Connectivity inputs M12, 5-pin Input type PNP Type of input diagnostics Channel diagnostics Switching threshold EN 61131-2 type 3, pnp Low level signal voltage < 5 V High level signal voltage > 11 V Low level signal current < 1.5 mA High level signal current > 2 mA Input delay 0.05 ms Electrical isolation Galvanically isolated to the fieldbus
voltages up to 500 VAC
Digital outputs
Number of channels 4 DXP Connectivity outputs M12, 5-pin Output type PNP Type of output diagnostics Channel diagnostics Output voltage 24 VDC from potential group Output current per channel 2 A, short-circuit proof
IO-Link
Number of channels 8 IO-Link Pin 4 in IOL mode IO-Link specification Version 1.1 IO-Link port type Class A and Class B Frame type Supports all specified frame types Supported devices Max. 32 byte input / 32 byte output Transmission rate 4.8 kbps (COM 1) / 38.4 kbps (COM 2) / 230 kbps
(COM 3)
Standard/Directive conformity
Vibration test acceleration to 20 g
acc. to EN 60068-2-6 Shock test acc. to EN 60068-2-27 Drop and topple acc. to EN 60068-2-31/IEC 60068-2-32 Electromagnetic compatibility acc. to EN 61131-2 Approvals and certificates CE,
FCC,
FM Class I, Zone 2,
UV-resistant in accordance with DIN EN ISO
4892-2A (2013) UL Certificate cULus LISTED 21 W2, Encl.type 1 IND.CONT.EQ.
Edition • 2020-10-14T22:39:34+02:00
2 / 6 TURCK Inc. ñ 3000 Campus Drive Minneapolis, MN 55441-2656 ñ Phone: 763-553-7300 ñ Application Support: 1-800-544-7769 ñ Fax 763-553-0708 ñ www.turck.com