Turck RU200-CK40-LIU2N8X2TH1151 Data Sheet

Ultrasonic sensor diffuse mode sensor RU200-CK40-LIU2N8X2T-H1151
Separate transducers for transmitter
and receiver
Rectangular housing 40 x 40 mm
Connection via M12 x 1 male
Teach range adjustable via button
Blind zone: 5 cm
Range: 200 cm
Resolution: 1 mm
Sonic cone angle: 60°
1 x switching output, NPN
NO/NC programmable
1 x analog output, 4..20mA/ 0..10 V
Type designation RU200-CK40-LIU2N8X2T-H1151
Ident-No. 1610058
Repeat accuracy
Ambient temperature 0…+70 °C
Operating voltage 15…30 VDC Residual ripple DC rated operational current No-load current I Residual current Output function 5-wire, NO/NC contact, NPN Short-circuit protection yes/ Cyclic Voltage drop at I Wire breakage/Reverse polarity protection yes/ yes
Design Rectangular, CK40 Dimensions 67 x 40 x 40 mm Housing material Plastic, PBT-GF30-V0 Electrical connection Connector, M12 × 1 Protection class IP40
Switching state LED yellow
0
e
ð 10 % U
ss
ð 150 mA ð 50 mA ð 0.1 mA
ð 2.5 V
Wiring Diagram
Functional principle
Ultrasonic sensors capture a multitude of ob­jects contactless and wear-free with ultrason­ic waves. It does not matter whether the ob­ject is transparent or opaque, metallic or non­metallic, firm, liquid or powdery. Even environ­mental conditions such as spray, dust or rain hardly affect their function.
Sonic Cone
Edition • 2017-01-06T17:55:29+01:00
1 / 3 TURCK Inc.
Ultrasonic sensor diffuse mode sensor RU200-CK40-LIU2N8X2T-H1151
Setting the limits
The ultrasonic sensor has an analog and a switching
output with teachable measuring and switching range.
Teaching is possible via Easy-Teach adapter or with the
buttons at the sensor. The green and yellow LED indi-
cate whether the sensor has detected an object.
Various functions such as single switchpoint, window
mode or reflection mode to a fixed target can be taught.
Further information is described in the operating in-
structions. How to set the window mode is described
below. The limits of the window may be selected freely
within the detection range.
Easy-Teach
ñConnect teach adapter TX1-Q20L60 between sensor
and connection cable
ñFor the first limit value, place object accordingly ñ Press and hold the select button for output 1 or 2 for
2 or 8 s against Gnd ñ Press and hold the select button for 8 s against Gnd
to teach the first limit value.
ñFor the second limit value, place object accordingly ñPress and hold button for at least 2 s against Gnd
Teach-Button
ñFor the first limit value, place object accordingly ñ Press and hold button 1 to select output 1 or 2 for 2
or 8 s against Gnd
ñ Press and hold button 1 for at least 8 s ñFor the second limit value, place object accordingly ñ Press and hold button 1 for at least 2 s
LED response
Successful teaching is indicated by a fast flashing
green LED. Thereafter, the sensor automatically runs in
normal operating mode. Unsuccessful teaching is indi-
cated by the LED flashing alternately green and yellow.
In normal operating mode both LEDs signal the switch-
ing state of output 1. ñgreen: object is in the detection range but not in the
switching range
ñ yellow: object is in the switching range ñoff: object is outside the detection range or signal loss
Edition • 2017-01-06T17:55:29+01:00
2 / 3 TURCK Inc.
Loading...