Differential Pressure Sensor
With current output and PNP/NPN transistor switching output
Output 2 programmable as switching output
PS001D-501L-LI2UPN8X -H1141
■ Pressure monitoring in harsh industrial
environments
■ Housing is rotatable after plugging the
process connection
■ Reading of adjusted values without tool
■ High-side switch
■ Recessed pushbutton, keylock and
password for secure programming
■ Permanent indication of pressure (bar,
psi, kPa, MPa, misc)
■ Peak pressure memory
■ Pressure range 0…1 bar difference
Type designation PS001D-501L-LI2UPN8X -H1141
Ident-No. 6834119
Pressure range
Relative pressure 0…1 bar rel.
0…14.5psi
0…0.1MPa
Admissible overpressure
Burst pressure
Response time < 3 ms
Power supply
Operating voltage 18…30 VDC
Current consumption
Voltage drop at I
Protective measure SELV; PELV according to EN 50178
Short-circuit/reverse polarity protection yes/ yes
Protection type and class IP67/IP69K/ III
Outputs
Output 1 Switching output or IO-Link mode
Output 2 analog or switching output
Switching output
Output function NO/NC, PNP/NPN
Accuracy switching output ± 1 % v. E. BSL
Rated operational current 0.2 A
Switching frequency
Switching point distance
Switch point: (min. + 0.005 × range) up to 100% of full scale
Release point(s) min. up to (SP - 0.005 x range)
Switching cycles
e
ð 5.5 bar
ï 5.5 bar
ð 50 mA
ð 2 V
ð 180 Hz
ï 0.5 %
ï 100 mil.
Wiring Diagram
Functional principle
The PSD differential pressure sensors have
two pressure connections with ceramic measuring cells to detect different pressures, from
which the difference is formed. As a result of
the pressure acting on the measuring cells,
a signal that is proportional to the pressure is
generated and electronically processed internally. Depending on the sensor variant, either
switching or analog signals are available. All
PSD variants have IO-Link.
The PSD sensors operate in various positive
pressure ranges up to a differential of 250 bar.
The connection with higher pressure can be
configured via the menu (High-Site-Switch).
Analog output
Current output 4…20 mA
Operating range 4…20/0…20 mA (3-wire)
Load
Accuracy LHR analog output ± 1 % FS BSL
Temperature behaviour
Medium temperature -40…+85 °C
Temperature coefficient zero point Tk0 ± 0.15 % of full scale/10 K
Temperature coefficient span T
Edition • 2018-03-01T18:32:25+01:00
1 / 2 TURCK Inc.
kS
ð 0.5 kò
± 0.15 % of full scale/10 K
Differential Pressure Sensor
With current output and PNP/NPN transistor switching output
Output 2 programmable as switching output
PS001D-501L-LI2UPN8X -H1141
Ambient conditions
Ambient temperature -40…+80 °C
Storage temperature -40…+80 °C
Vibration resistance 20 g (9…2000 Hz), according to IEC 68-2-6
Shock resistance 50 g (11 ms) , according to IEC 61508
EMC EN 61000-4-2 ESD:4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated: 15 V/m
EN 61000-4-4 Burst: 2 kV
EN 61000-4-5 Surge: 1000 V, 42 Ohm
EN 61000-4-6 HF cable bound: 10 V
Housing
Housing material Stainless-steel/Plastic, V2A (1.4305)
Pressure connection material Stainless steel A2 1.4305 (AISI 303)
Pressure transducer material Ceramics Al2O
Sealing material FPM spez.
Process connection G¼" female thread
Wrench size pressure connection / coupling nut 21/ 30
Electrical connection Connector, M12 × 1
Max. tightening torque housing nut 35 Nm
Reference conditions acc. to IEC 61298-1
Temperature 15…+25 °C
Atmospheric pressure 860…1060 hPa abs.
Humidity 45…75 % rel.
Auxiliary power 24 VDC
3
Display 4-digit 7-segment display, rotatable by 180°, disen-
gageable
Switching state 2 × LEDs Yellow
Programming options start/end value analog output; switch/release points;
PNP/NPN; NO/NC contact; hysteresis/window func-
tion; damping; pressure unit; peak pressure memory
Unit display 5 x LEDs green (bar, psi, kPa, MPa, misc)
Edition • 2018-03-01T18:32:25+01:00