Turck PROFIBUS Catalog Page

Page 1
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, Cable Specications
y Cable that meets the requirements
of EN50170-2-2:1996 for communications up to 12 Mbaud
Jacket
Drain Wire
Figure A
Foiled Shield
Braided Shield
Baud Rate (k baud) 9.6 19.2 93.75 187.5 500 1500 1200
Maximum Trunk Length 1200 meters 1200 meters 1200 meters 1000 meters 400 meters 200 meters 100 meters
Type Approvals
455 80 °C 300 V
456 80 °C 300 V
457 80 °C
We reserve the right to make technical alterations without prior notice.
600 V
458 80 °C 300 V
4511 80 °C 300 V
4515 80 °C 600 V
590 80 °C 300 V
* Indicates length in meters.
Standard spool lengths are 30, 75, 100, 150, 200, 225, 300 meters. Consult factory for other lengths.
UL PLTC-ER DB CSA CMX-OUTDOOR-CMG AWM I/II A/B, FT 4
UL recognized AWM CSA AWM I/II A/B, FT 1
UL recognized AWM VW-1
UL recognized AWM CSA AWM I/II A/B, FT 1
UL PLTC CSA CMX-OUTDOOR-CMG AWM I/II A/B, FT 4
IEC-60332-3 IEC-60754-1 EN 50267-2-2
UL recognized AWM CSA AWM I/II A/B, FT 1
AWG
Color Code
2X22 AWG
RD/GN
2X22 AWG
RD/GN
2X22 AWG
RD/GN
Solid
2X22 AWG
RD/GN
2X22 AWG
RD/GN
2X22 AWG
RD/GN
2X22 AWG
RD/GN
Red
Figure B
Green
Data Pair 2nd Data Pair Outer Jacket Shields
Characteristic Impedance @
1 MHz/Insulation
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
AWG
Color Code
None n/a
None n/a
None n/a
None n/a
None n/a
None n/a
2X22 AWG
BU/WT
Jacket
Characteristic Impedance @
1 MHz/Insulation
150 Ohms
HDPE
Braided Shield
Drain Wire
Aluminum Mylar Foil Shielded
Material Color
Nominal O.D.
PVC, VIOLET,
8.5 mm (.335 in)
TPU, VIOLET,
7.9 mm (.310 in)
TPU, VIOLET,
7.8 mm (.305 in)
TPU, PLUM,
8.5 mm (.335 in)
PVC, VIOLET,
8.5 mm (.335 in)
TPU, VIOLET,
7.9 mm (.310 in) Halogen-free
PVC, VIOLET,
8.4 mm (.330 in)
Mylar Tape
Type
Drain Wire
Foil/braid,
22 AWG
Foil/braid,
22 AWG
Foil/braid
Foil/braid,
22 AWG
Foil/braid,
22 AWG
Foil/braid,
22 AWG
Foil/braid,
22 AWG
Blue White
Green Red
Bulk Cable Part Number / Weight/300 M
RB50672-*M,
63 lbs.
RB50683-*M,
45 lbs.
RB50708-*M,
39 lbs.
RB50692-*M,
52 lbs.
Flexlife®
RB50881-*M,
58 lbs.
Flexlife
RB51225-*M,
41 lbs.
RB51057-*M,
52 lbs.
PROFIBUS®–DP Connectivity
B2007 P5 B2007 P5
Page 2
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, (M12x1) Eurofast® Cable and Cordset Selection Matrix
Eurofast (Male) Eurofast (Female)
1 2 3 4
RSSW WSSW RKSW WKSW
RSSW 45x-*M WSSW 45x-*M RKSW 45x-*M WKSW 45x-*M
Bare
1
RSSW
2
Eurofast (Male)
WSSW
3
RKSW
4
Eurofast (Female)
WKSW
See page P8 for dimensional drawings.
*
Indicates length in meters.
x
Indicates cable type. Standard cable lengths are 1, 2, 4, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths. For stainless steel coupling nuts change part number RSSW...RSSWV.
RSSW RSSW 45x-*M RSSW WSSW 45x-*M RSSW RKSW 45x-*M RSSW WKSW 45x-*M
WSSW WSSW 45x-*M WSSW RKSW 45x-*M WSSW WKSW 45x-*M
RKSW RKSW 45x-*M RKSW WKSW 45x-*M
WKSW WKSW 45x-*M
We reserve the right to make technical alterations without prior notice.
Pinouts
Eurofast 45 series pinout 59 series pinout Eurofast
Male
1. N/C
2. Green (TxD)
3. N/C
4. Red (RxD)
5. Bare (Shield Drain Wire)
1. Blue (TxD_1)
2. Green (TxD)
3. White (RxD_1)
4. Red (RxD)
5. Bare (Shield Drain Wire)
P6 B2007 www.turck.com 1-800-544-7769 Fax: (763) 553-0708 Turck Minneapolis, MN 55441 B2007 P7
Female
Page 3
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, (M12x1) Eurofast® Cable and Cordsets
Specications
Overmold: TPU Protection: NEMA 1, 3, 4, 6P and IEC IP 68
Coupling Nut: Nickel Plated CuZn or Stainless Steel Rated Voltage: 250 V
Contact Carrier: TPU or POM (Nylon) Rated Current: 4 A
Contacts: Gold Plated CuZn Ambient Temperature: -40 °C to +75 °C (-22 °F to +167 °F)
1 2
RSSW .. Page P6 WSSW .. Page P6
3 4
RKSW .. Page P6 WKSW .. Page P6
We reserve the right to make technical alterations without prior notice.
5 6
FSSDWE .. Page P8 FKSDWE .. Page P8
PROFIBUS®–DP Connectivity
B2007 P7
Page 4
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, (M12x1) Eurofast® Cable and Cordset Selection Matrix
Eurofast
Male Female Male Female
1 2 3 4 5 6
Bare RSSW WSSW RKSW WKSW FSSDWE FKSDWE
10
D9S/T 45x-*M
RSSW D9S/T 45x-*M
WSSW D9S/T 45x-*M
RKSW D9S/T 45x-*M
Terminator
D9S/T
12
D9SM/T 45x-*M
Master
RSSW D9SM/T 45x-*M
WSSW D9SM/T 45x-*M
RKSW D9SM/T 45x-*M
D9SM/T
9-Pin Sub D Connector
11
SD9S/T 45x-*M
RSSW SD9S/T 45x-*M
WSSW SD9S/T 45x-*M
RKSW SD9S/T 45x-*M
SD9S/T
See page P8 and P11 for dimensional drawings.
*
Indicates length in meters.
x
Indicates cable type. Standard cable lengths are 1, 2, 4, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths. For stainless steel coupling nuts change part number RSSW...RSSWV.
Extension Example:
WKSW D9S/T 45x-*M
WKSW D9SM/T 45x-*M
WKSW SD9S/T 45x-*M
FSSDWE D9S/T 45x-*M
FSSDWE D9SM/T 45x-*M
FSSDWE SD9S/T 45x-*M
FKSDWE D9S/T 45x-*M
FKSDWE D9SM/T 45x-*M
We reserve the right to make technical alterations without prior notice.
FKSDWE SD9S/T 45x-*M
RSSW D9S/T 455-0.3M
Pinouts
Eurofast 45 series pinout Eurofast D9 D9 pinout
Male
1. N/C
2. Green (TxD)
3. N/C
4. Red (RxD)
5. Bare (Shield Drain Wire)
P8 B2007 www.turck.com 1-800-544-7769 Fax: (763) 553-0708 Turck Minneapolis, MN 55441 B2007 P9
Female Male
1 = N/C 2 = N/C 3 = RD (RXD) 4 = N/C 5 = N/C 6 = N/C 7 = N/C 8 = GN (TXD) 9 = N/C
Page 5
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, (M12x1) Eurofast® Cable and Cordset Selection Matrix
Eurofast
Male Female Male Female
1 2 3 4 5 6
Bare RSSW WSSW RKSW WKSW FSSDWE FKSDWE
We reserve the right to make technical alterations without prior notice.
10
Node
11
Straight
12
10
Node
D9S
SD9S
D9SM
D9S 45x-*M
SD9S 45x-*M
D9SM 45x-*M
RSSW D9S RSSW 45x-*M-*M
RSSW SD9S RSSW 45x-*M-*M
RSSW D9SM RSSW 45x-*M
WSSW D9S WSSW 45x-*M-*M
WSSW SD9S WSSW 45x-*M-*M
WSSW D9SM WSSW 45x-*M-*M
RKSW D9S RKSW 45x-*M-*M
RKSW SD9S RKSW 45x-*M-*M
RKSW D9SM RKSW 45x-*M-*M
WKSW D9S WKSW 45x-*M-*M
WKSW SD9S WKSW 45x-*M-*M
WKSW D9SM WKSW 45x-*M-*M
FSSDWE D9S FSSDWE 45x-*M-*M
FSSDWE SD9S FSSDWE 45x-*M-*M
FSSDWE D9SM FSSDWE 45x-*M-*M
FKSDWE D9S FKSDWE 45x-*M-*M
FKSDWE SD9S FKSDWE 45x-*M-*M
FKSDWE D9S FKSDWE 45x-*M-*M
Eurofast
Male Female Male Female Male Female
1 3 2 4 5 6
Bare RSSW RKSW WSSW WKSW FSSDWE FKSDWE
D9S 45x-*M RSSW D9S RKSW 45x-*M-*M WSSW D9S WKSW 45x-*M-*M FSSDWE D9S FKSDWE 45x-*M-*M
PROFIBUS®–DP Connectivity
D9S
11
SD9S 45x-*M RSSW SD9S RKSW 45x-*M-*M WSSW SD9S WKSW 45x-*M-*M FSSDWE SD9S FKSDWE 45x-*M-*M
Straight
SD9S
12
D9SM 45x-*M RSSW D9SM RKSW 45x-*M-*M WSSW D9SM WKSW 45x-*M-*M FSSDWE D9SM FKSDWE 45x-*M-*M
D9SM
See page P8 and P11-P12 for dimensional drawings.
*
Indicates length in meters.
x
Indicates cable type. Standard cable lengths are 1, 2, 4, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths. For stainless steel coupling nuts change part number RSSW...RSSWV.
B2007 P9
Page 6
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, Field Wireable D9 Connectors
y Provides connection to Master
or Node in the eld
y Maximum Cable O.D. is 8.5 mm
Housing Style Part Number Features Pinout
Connector,PDP,D9S
Connector,PDP,SD9S
Connector,PDP,D9SM
-25 °C to +80 °C, right angle, terminating switch
-25 °C to +80 °C, straight, terminating switch
-25 °C to +80 °C, right angle, master, terminating switch
1. N/C
2. N/C
3. RED (Bus_B)
4. N/C
5. N/C
6. N/C
7. N/C
8. Green (Bus_A)
9. N/C
Male
We reserve the right to make technical alterations without prior notice.
Page 7
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, Field Wireable D9 Connectors
Specications - (D9)
Terminating Switch: Yes Rated Current: 5 mA
Protection: IEC IP 20 Temperature Rating: -25 °C to +60 °C
Rated Voltage: 4.75-5.25 VDC *Max. Cable diameter: 8.5 mm
10 11
Connector, PDP, D9S Page P8 Connector, PDP, SD9S Page P8
12
We reserve the right to make technical alterations without prior notice.
Connector, PDP, D9SM Page P8
PROFIBUS®–DP Connectivity