of EN50170-2-2:1996 for
communications up to 12 Mbaud
Jacket
Drain Wire
Figure A
Foiled Shield
Braided Shield
Baud Rate (k baud)9.619.293.75187.550015001200
Maximum Trunk Length1200 meters1200 meters1200 meters1000 meters400 meters200 meters100 meters
TypeApprovals
455
80 °C
300 V
456
80 °C
300 V
457
80 °C
We reserve the right to make technical alterations without prior notice.
600 V
458
80 °C
300 V
4511
80 °C
300 V
4515
80 °C
600 V
590
80 °C
300 V
* Indicates length in meters.
Standard spool lengths are 30, 75, 100, 150, 200, 225, 300 meters. Consult factory for other lengths.
UL PLTC-ER DB
CSA CMX-OUTDOOR-CMG
AWM I/II A/B, FT 4
UL recognized AWM
CSA AWM I/II A/B, FT 1
UL recognized AWM
VW-1
UL recognized AWM
CSA AWM I/II A/B, FT 1
UL PLTC
CSA CMX-OUTDOOR-CMG
AWM I/II A/B, FT 4
IEC-60332-3
IEC-60754-1
EN 50267-2-2
UL recognized AWM
CSA AWM I/II A/B, FT 1
AWG
Color Code
2X22 AWG
RD/GN
2X22 AWG
RD/GN
2X22 AWG
RD/GN
Solid
2X22 AWG
RD/GN
2X22 AWG
RD/GN
2X22 AWG
RD/GN
2X22 AWG
RD/GN
Red
Figure B
Green
Data Pair2nd Data PairOuter JacketShields
Characteristic
Impedance @
1 MHz/Insulation
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
150 Ohms
HDPE
AWG
Color Code
Nonen/a
Nonen/a
Nonen/a
Nonen/a
Nonen/a
Nonen/a
2X22 AWG
BU/WT
Jacket
Characteristic
Impedance @
1 MHz/Insulation
150 Ohms
HDPE
Braided Shield
Drain Wire
Aluminum Mylar Foil Shielded
Material Color
Nominal O.D.
PVC, VIOLET,
8.5 mm (.335 in)
TPU, VIOLET,
7.9 mm (.310 in)
TPU, VIOLET,
7.8 mm (.305 in)
TPU, PLUM,
8.5 mm (.335 in)
PVC, VIOLET,
8.5 mm (.335 in)
TPU, VIOLET,
7.9 mm (.310 in)
Halogen-free
PVC, VIOLET,
8.4 mm (.330 in)
Mylar Tape
Type
Drain Wire
Foil/braid,
22 AWG
Foil/braid,
22 AWG
Foil/braid
Foil/braid,
22 AWG
Foil/braid,
22 AWG
Foil/braid,
22 AWG
Foil/braid,
22 AWG
Blue
White
Green
Red
Bulk Cable
Part Number /
Weight/300 M
RB50672-*M,
63 lbs.
RB50683-*M,
45 lbs.
RB50708-*M,
39 lbs.
RB50692-*M,
52 lbs.
Flexlife®
RB50881-*M,
58 lbs.
Flexlife
RB51225-*M,
41 lbs.
RB51057-*M,
52 lbs.
PROFIBUS®–DP Connectivity
B2007 P5 B2007 P5
Page 2
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, (M12x1) Eurofast® Cable and Cordset Selection Matrix
Eurofast (Male)Eurofast (Female)
1234
RSSWWSSWRKSWWKSW
RSSW 45x-*MWSSW 45x-*MRKSW 45x-*MWKSW 45x-*M
Bare
1
RSSW
2
Eurofast (Male)
WSSW
3
RKSW
4
Eurofast (Female)
WKSW
See page P8 for dimensional drawings.
*
Indicates length in meters.
x
Indicates cable type.
Standard cable lengths are 1, 2, 4, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths.
For stainless steel coupling nuts change part number RSSW...RSSWV.
Overmold:TPUProtection:NEMA 1, 3, 4, 6P and IEC IP 68
Coupling Nut:Nickel Plated CuZn or Stainless SteelRated Voltage:250 V
Contact Carrier:TPU or POM (Nylon)Rated Current:4 A
Contacts:Gold Plated CuZnAmbient Temperature:-40 °C to +75 °C (-22 °F to +167 °F)
12
RSSW ..Page P6WSSW ..Page P6
34
RKSW ..Page P6WKSW ..Page P6
We reserve the right to make technical alterations without prior notice.
56
FSSDWE ..Page P8FKSDWE ..Page P8
PROFIBUS®–DP Connectivity
B2007 P7
Page 4
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, (M12x1) Eurofast® Cable and Cordset Selection Matrix
Eurofast
MaleFemaleMaleFemale
123456
BareRSSWWSSWRKSWWKSWFSSDWEFKSDWE
10
D9S/T 45x-*M
RSSW D9S/T
45x-*M
WSSW D9S/T
45x-*M
RKSW D9S/T
45x-*M
Terminator
D9S/T
12
D9SM/T 45x-*M
Master
RSSW D9SM/T
45x-*M
WSSW D9SM/T
45x-*M
RKSW D9SM/T
45x-*M
D9SM/T
9-Pin Sub D Connector
11
SD9S/T 45x-*M
RSSW SD9S/T
45x-*M
WSSW SD9S/T
45x-*M
RKSW SD9S/T
45x-*M
SD9S/T
See page P8 and P11 for dimensional drawings.
*
Indicates length in meters.
x
Indicates cable type.
Standard cable lengths are 1, 2, 4, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths.
For stainless steel coupling nuts change part number RSSW...RSSWV.
Extension Example:
WKSW D9S/T
45x-*M
WKSW D9SM/T
45x-*M
WKSW SD9S/T
45x-*M
FSSDWE D9S/T
45x-*M
FSSDWE D9SM/T
45x-*M
FSSDWE SD9S/T
45x-*M
FKSDWE D9S/T
45x-*M
FKSDWE D9SM/T
45x-*M
We reserve the right to make technical alterations without prior notice.
Indicates cable type.
Standard cable lengths are 1, 2, 4, 6, 8, 10, 15, and in +5 meter increments from there. Consult factory for other lengths.
For stainless steel coupling nuts change part number RSSW...RSSWV.
B2007 P9
Page 6
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, Field Wireable D9 Connectors
y Provides connection to Master
or Node in the eld
y Maximum Cable O.D. is 8.5 mm
Housing StylePart NumberFeaturesPinout
Connector,PDP,D9S
Connector,PDP,SD9S
Connector,PDP,D9SM
-25 °C to +80 °C, right angle,
terminating switch
-25 °C to +80 °C, straight,
terminating switch
-25 °C to +80 °C, right angle,
master, terminating switch
1. N/C
2. N/C
3. RED (Bus_B)
4. N/C
5. N/C
6. N/C
7. N/C
8. Green (Bus_A)
9. N/C
Male
We reserve the right to make technical alterations without prior notice.
Page 7
PROFIBUS®–DP Physical Media Connectivity
PROFIBUS-DP, Field Wireable D9 Connectors
Specications - (D9)
Terminating Switch:YesRated Current:5 mA
Protection:IEC IP 20Temperature Rating:-25 °C to +60 °C
Rated Voltage:4.75-5.25 VDC*Max. Cable diameter: 8.5 mm