FM-IM-3UP63X
Flow Monitoring – For the Connection of Flow Sensors
IO-Link Device with Transistor Outputs
Features
Transistor outputs for flow, temperature and
■
faults
Adjustment of switchpoint, no teaching of
■
flow boundaries (QuickTeach)
LED band for indication of flow speed and
■
media temperature
Monitoring of operating and display range
■
Detection of wire-break and short-circuit on
■
the sensor side
Standard IO or IO-Link operating mode
■
Parametrized via pushbutton or soft-
■
ware-supported via IO-Link
Functional principle
Technical data
Type FM-IM-3UP63X
ID no. 7525100
Electrical data
Operating voltage 20…30VDC
Power consumption <4.5W
No-load current I
0
Teach modes QuickTeach; min/max adjustment. Teach
Flow speed [%] after min/max adjustment (perma-
Flow speed % after Quick-Teach (permanent)
Medium temperature [°C] with the SET button temporarily
Repeatability flow rate typical ±1% (of full scale)
Repeatability media temperature typical ±1K
Measuring accuracy media temperature typical ±7K
Switchpoint hysteresis media temperature
Input function Connection of flow sensors
Sensor voltage ≤15VDC
Sensor current ≤35mA
Sensor current limitation approx.110mA
Measuring frequency 5 Hz (every 200 ms with software filter)
Output functions
Flow monitoring transistor output
≤63mA
modes incl. DeltaFlow monitoring (teach
modes are automatically released with
the change of flow speed).
nent)
pressed
2K
All non-Ex flow sensors from the FCS series
(immersion sensors) and FCI series (inline
series) can be operated with the FM-IM
external processing unit.
The flow module features four status LEDs
as well as a 10-segment LED band for local
monitoring. Software-based diagnostic options
are also available to the user, such as wirebreak and short-circuit on the sensor side.
Furthermore, monitoring of flow rates and
media temperatures within a predefined
operating and display range.
The upper and lower limits of the flow range
are taught in using the max./min. teach
mode implemented. The flow switchpoint is
easily adjusted by means of the Quick-Teach
function, without having to program a lower
and upper limit of the flow range. Working
on the calorimetric principle, the connectible
sensors not only detect the flow rate but also
the media temperature.
The flow module can be operated either in
IO-Link (IOL) or in standard IO (SIO) mode
via the integrated IO-Link interface. In SIO
mode, the switching outputs are operated in
the standard way. In IOL mode the current
process signal is transmitted cyclically as a 10
bit-serial value.
Parametrization is initiated either via
pushbutton or software-supported via IOLink interface. The actual parametrization is
then implemented via the tool-based DTM or
IODD within the FDT frame PACTware™ or
acyclically near the control via On-Request
Data Objects (ORDO).
FM-IM-3UP63X | 04-05-2021 11-33 | Technical modifications reserved
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com 1|3
Technical data
Temperature monitoring transistor output
Error monitoring transistor output
Switching characteristic PNP
Switching state active high / active low parametrizable
(transistor output error monitoring only
active low)
Switching voltage 20…30VDC
Switching current 100mA
Electrical connections 5-pole removable reverse polarity protect-
ed terminal blocks
Connection mode screw connection
Terminal cross-section 1.5…2.5mm²
IO-Link
Communication IO-Link spec. 1.0
Transmission rate 38.4 kbps (COM 2)
Transmission physics Transmission physics 3-wire physics
Communication channel Clamp 12 and via front panel jack COM
Communication modes Tool based engineering via FDT / DTM,
Included in the SIDI GSDML Yes
Tests/approvals
Approvals CE, C-UL U.S. submitted
Electromagnetic compatibility (EMC) acc. to NE21
Relative humidity EN 60068-2-38
Mechanical data
Design Signal processor
Dimensions 89x110x27mm
Housing material Polycarbonate/ABS
Ambient temperature (min.) -25
Ambient temperature (max.) 70
Mounting type DIN rail mounting and mounting panel
Protection class IP20
MTBF 109Years
(PHY 2)
(PC)
IODD. Acyclic communication via On-Request Data Objects
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com 2|3