Turck FGEN-IOM88-5001 Data Sheet

Compact multiprotocol I/O module for Ethernet 8 digital PNP inputs 8 digital outputs 2 A FGEN-IOM88-5001
Type designation FGEN-IOM88-5001
Ident-No. 6825424
System data
Fieldbus connection technology 2 × M12 Protocol detection automatic Web server from FW 3.1.0.0 Service interface Ethernet
Multiprotocol I/O Module for the Eth-
ernet protocols Modbus TCP®, Ether­Net/IP™ and PROFINET®
PROFINET® supports Fast Start-Up
(FSU)
EtherNet/IP™ supports QuickConnect
(QC)
Integrated Ethernet Switch
FDT/DTM supported
Input diagnostics per port
Output diagnostics per channel
Two inputs or outputs per port
7/8", 5-pin, for power supply
Power supply, galvanically separated
Fibre-glass reinforced PA6 housing
Vibration and shock-resistant
Encapsulated module electronics
Metal connectors
Degree of protection IP67
Modbus TCP
Addressing Static IP, BOOTP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 8
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification Quick Connect (QC) < 150 ms Device Level Ring (DLR) supported Class 3 connections 3 Class 1 connections 10
PROFINET
Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Fast Start-Up (FSU) < 150 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported
Number of channels (8) 3-wire pnp sensors Switching threshold EN 61131-3
low max.: 1.5 mA / high min.: 2 mA Input delay 2.5 ms Electrical isolation galvanically separated against the bus and outputs Input voltage 18…30 VDC from operating voltage UB
Number of channels (8) DC actuators Output voltage 18…30 VDC from load voltage Output current per channel 2.0 A, short-circuit proof Simultaneity factor 0.25 for entire module
1* 2A or 2* 1A per port
total current max. 9 A per module Load type resistive, inductive, lamp load Electrical isolation galvanically separated against bus and inputs
Edition • 2019-01-21T22:42:37+01:00
1 / 5 TURCK Inc.
Compact multiprotocol I/O module for Ethernet 8 digital PNP inputs 8 digital outputs 2 A FGEN-IOM88-5001
Vibration test acc. to EN 60068-2-6
Shock test acc. to EN 60068-2-27 Electromagnetic compatibility acc. to EN 61131-2 UL Certificate pol. deg.2, env. temp. max. 40 °C, cl.2 ps req.
Dimensions (W x L x H) 60 x 220.5 x 27mm Operating temperature 0…+55 °C Storage temperature -25 …+70 °C Altitude max.5000 m Protection class IP67 MTTF 197 years acc. to SN 29500 (Ed. 99) 20 °C Housing material fibre-glass reinforced Polyamide (PA6-GF30) Halogen-free yes Mounting 4 mounting holes Ø 5,4 mm
Edition • 2019-01-21T22:42:37+01:00
2 / 5 TURCK Inc.
Compact multiprotocol I/O module for Ethernet 8 digital PNP inputs 8 digital outputs 2 A FGEN-IOM88-5001
Accessories
Ethernet cable (example):
RSSD RSSD 441 2M
Ident-No. U-02482
Accessories
Connection cable for dual channels (example):
RK 4.4T-2-RS 4.4T
Ident-No. U2445
Splitter for single channels (example):
YB2-FSM 4.5-2FKM 4.5
Ident-No. U0875-78
M12 x 1 Ethernet
M12 x 1 Input
M12 x 1 Output
Accessories
Power supply cable (example):
RSM RKM 50-2M
Ident-No. U2282-0
7/8'' Power Supply
Edition • 2019-01-21T22:42:37+01:00
3 / 5 TURCK Inc.
Compact multiprotocol I/O module for Ethernet 8 digital PNP inputs 8 digital outputs 2 A FGEN-IOM88-5001
LED status module
LED Color Status Description
ETH1 / ETH2 green on Ethernet Link (100 Mbps)
flashing Ethernet communication (100 Mbps)
yellow on Ethernet Link (10 Mbps)
flashing Ethernet communication (10 Mbps)
off no Ethernet link
Bus green on Active connection to a master
flashing ready
red on IP address conflict or Restore Mode
flashing Blink/Wink command active
off No power supply
Power green on Operating voltage UB and load voltage UL within the defined tolerances
red on Load voltage UL below the defined tolerances
off Operating voltage UB below the defined tolerances
LED status IOs
LED Color Status Description
C0.I1 … C3.I8 green on Input active
red on Overload of sensor supply at the corresponding connector
off Input inactive
C4.O9 … C7.O16 green on Output active
red on Output active with overload / short circuit
off Output inactive
Edition • 2019-01-21T22:42:37+01:00
4 / 5 TURCK Inc.
Compact multiprotocol I/O module for Ethernet 8 digital PNP inputs 8 digital outputs 2 A FGEN-IOM88-5001
Process data mapping of single protocols
Modbus TCP Register Mapping
Reg Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Inputs (RO) 0x0000 - - - - - - - - DI7
Status (RO) 0x0001 - FCE - - CFG COM UB - UL - - - - - - Diag
Diag (RO) 0x0002 - - - - - - - - - - - - - - - I/O
Outputs (RW) 0x0800 - - - - - - - - DO7
I/O Diag (RO) 0xA000 SCO7 SCO6 SCO5 SCO4 SCO3 SCO2 SCO1 SCO0 - - - - SCS3 SCS2 SCS1 SCS0
EtherNet/IP™ data mapping with activated Scheduled Diagnostics
Word Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input data (Station -> Scanner)
GW Status 1 - FCE - - CFG COM UB - UL - - - - - - Diag
Inputs 2 - - - - - - - - DI7
Diag 1 3 - - Sched
Diag
Diag 2 4 SCO7 SCO6 SCO5 SCO4 SCO3 SCO2 SCO1 SCO0 - - - - SCS3 SCS2 SCS1 SCS0
Output (Scanner -> Station)
Control 1 reserved
Outputs
EtherNet/IP™ data mapping with activated Summarized Diagnostics
Input data (Station -> Scanner)
GW Status 1 - FCE - - CFG COM UB - UL - - - - - - Diag
Inputs 2 - - - - - - - - DI7
Diag 1 3 - I/O
Output (Scanner -> Station)
Control 1 reserved
Outputs
PROFINET Process Data
Inputs 0 DI7
Outputs 0 DO15
Legend:
DI Digital input COM Communication error on internal module bus
DO Digital output CFG I/O configuration error
Cx female FCE I/O-ASSISTANT Force Mode active
Px Pin I/ODiag I/O diagnostics available
DiagWarn Diagnostic at least on 1 channel SchedDiag Manufacturer-specific diagnostics configured and active
UL Undervoltage UL SCSx Short-circuit on sensor supply at female x
UB Undervoltage UB SCOx Short-circuit output x
2 - - - - - - - - DO7
Word Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
2 - - - - - - - - DO7
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
C3P2
C7P2
- - - - - - - - - - - - I/O
DI6
C3P4
DO14
C7P4
DI5
C2P2
DO13
C6P2
DI4
C2P4
DO12
C6P4
C3P2
C3P2
C3P2
C3P2
C3P2
C3P2
DI3
C1P2
DO11
C5P2
DI6
C3P4
DO6
C3P4
DI6
C3P4
DO6
C3P4
DI6
C3P4
DO6
C3P4
DI5
C2P2
DO5
C2P2
DI5
C2P2
DO5
C2P2
DI5
C2P2
DO5
C2P2
DI2
C1P4
DO10
C5P4
DI4
C2P4
DO4
C2P4
DI4
C2P4
DO4
C2P4
DI4
C2P4
DO4
C2P4
DI3
C1P2
DO3
C1P2
DI3
C1P2
DO3
C1P2
DI3
C1P2
DO3
C1P2
DI1
C0P2
DO9
C4P2
DI2
C1P4
DO2
C1P4
DI2
C1P4
DO2
C1P4
DI2
C1P4
DO2
C1P4
DI1
C0P2
DO1
C0P2
DI1
C0P2
DO1
C0P2
DI0
C0P2
DO0
C0P2
DI0
C0P4
Warn
Diag
DO0
C0P4
Warn
DI0
C0P4
Diag
DO0
C0P4
Warn
DI0
C0P4
Diag
DO0
C0P4
DI0
C0P4
DO8
C4P4
Edition • 2019-01-21T22:42:37+01:00