Turck FDNL-S1600-W Data Sheet

FDNL-S1600-W
This station takes in up to 16 discrete 3-wire inputs or eight discrete 4-wire input points per node. There are two inputs per connector - one on pin 4 and one on pin 2.
Inputs are monitored for short-circuits as a group. A short condition is indicated by a red MOD status LED and the IGS bit. The LED and status bit automatically reset when the fault is removed.
The node address can be set by the rotary switches located under the device cover or through software node commissioning. The unit can automatically detect the network communication rate.
The FDNL-S1600-W supports explicit messages, polled, change of state, and cyclic I/O messages.
Recommended Cordsets: Bus line: RSM RKM 579-*M Inputs: VBRS 4.4- 2RK 4T-*/* or RK 4.4T-*-RS 4.4T, BS8141-0 (male field wireable) Bus T: RSM 2RKM 57 /C1125
FDNL-S1600-W Dimensions
Advanced DeviceNet™ station•
8 x 2 discrete inputs •
Applications
For high density applications•
For use with eight 4-wire sensors or 16 • 3-wire sensors through input splitters
Features
PNP short-circuit protected inputs•
Glass filled nylon with nickel • plated brass connectors
Rotary address switches•
Automatic detection of network • communication rate
TURCK Inc. 10240192 Rev 1.08 3/08
FDNL-S1600-W
Connectors
1 = Shield 2 = V + 3 = V – 4 = CAN_H 5 = CAN_L
DeviceNet ™ minifast
I/O Data Mapping
Item Number F0125 Product Type / Code: 7/2001
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input
Data
0 I-7 I-6 I-5 I-4 I-3 I-2 I-1 I-0
1 I-15 I-14 I-13 I-12 I-11 I-10 I-09 I-08
2 IGS
Male 5-pin
®
Input Connector
Abbreviations
I = Input Data (0=OFF, 1=ON)
IGS = Input Group Status (0=Working, 1=Fault)
TURCK Inc. 10240192 Rev 1.08 3/08
FDNL-S1600-W
Module Specifications
Supply Voltage
Bus Power 11-26 VDC Internal Current Consumption <50 mA (at 24 VDC) plus sum of sensor currents (from bus power)
Input Circuits (16) PNP 3-wire sensors or dry contacts
Input Voltage (V+) 13-26 VDC (from bus power) Input Short-Circuit (V+) 700 mA - 2.0 A (total) Input Signal Current (I) OFF <2 mA ON 3.0-3.4 mA at 24 VDC Input Delay 2.5 ms
Input LED Indications
Off = Not active Green = Active
Module Status LED
Off = Power off Green = Operating Flashing Green = Autobaud Flashing Red = I/O Short
Network Status LED
Off = No connection Green = Established connection Flashing green = Ready for connection Flashing red = Connection time-out Red = Connection not possible
Connections
Bus line 5-pin minifast ® connectors Inputs eurofast
®
connectors
Address
0-63 Address from internal EEPROM (rotary switch must be in PGM position)
Housing (mm) 197 x 60 x 40 (H x W x D)
Material Glass-filled nylon, nickel plated brass connectors Mounting 4 through-holes, 4.5 diameter Enclosure NEMA 1, 3, 4, 6, 6P, 12, 14 and IEC IP 67, 68, and 69K Operating Temperature -40° to +70°C (-40° to 158° F)
TURCK Inc. 10240192 Rev 1.08 3/08