FDNL-S1600-W
This station takes in up to 16 discrete 3-wire inputs or eight discrete 4-wire input points
per node. There are two inputs per connector - one on pin 4 and one on pin 2.
Inputs are monitored for short-circuits as a group. A short condition is indicated by a red
MOD status LED and the IGS bit. The LED and status bit automatically reset when the
fault is removed.
The node address can be set by the rotary switches located under the device cover or
through software node commissioning. The unit can automatically detect the network
communication rate.
The FDNL-S1600-W supports explicit messages, polled, change of state, and cyclic I/O messages.
Recommended Cordsets:
Bus line: RSM RKM 579-*M
Inputs: VBRS 4.4- 2RK 4T-*/* or RK 4.4T-*-RS 4.4T,
BS8141-0 (male field wireable)
Bus T: RSM 2RKM 57 /C1125
FDNL-S1600-W Dimensions
Advanced DeviceNet™ station•
8 x 2 discrete inputs •
Applications
For high density applications•
For use with eight 4-wire sensors or 16 •
3-wire sensors through input splitters
Features
PNP short-circuit protected inputs•
Glass filled nylon with nickel •
plated brass connectors
Rotary address switches•
Automatic detection of network •
communication rate
TURCK Inc. 10240192 Rev 1.08 3/08
FDNL-S1600-W
Connectors
1 = Shield
2 = V +
3 = V –
4 = CAN_H
5 = CAN_L
DeviceNet ™ minifast
I/O Data Mapping
Item Number F0125
Product Type / Code: 7/2001
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input
Data
0 I-7 I-6 I-5 I-4 I-3 I-2 I-1 I-0
1 I-15 I-14 I-13 I-12 I-11 I-10 I-09 I-08
2 IGS
Male 5-pin
®
Input Connector
Abbreviations
I = Input Data (0=OFF, 1=ON)
IGS = Input Group Status (0=Working, 1=Fault)