Turck FDN20-4S-4XSG-E/C1261 Data Sheet

FDN20-4S-4XSG-E/C1261
V
+
I
7
I
6
I
5
I
4
V
-
I
3
I
2
I
1
I
0
FDN20-4S-4XSG-E/C1261
Integrated Design
Extremely flexible DeviceNet station
The station provides a connection for 8 I/O points. The first 4 points can be either inputs or outputs. The other 4 points are inputs only. All inputs and outputs are powered by DeviceNet™. This is ideal for small systems that don’t require auxiliary power.
To use an I/O point as an input, simply leave the corresponding output OFF. To use an I/O point as an output, simply turn on the corresponding output bit. The output will switch on high. Note that this will in turn cause the corresponding input bit to turn on. If the corresponding input does not turn on, the output is shorted.
The FDN20-4S-4XSG-E/C1261 supports explicit messaging, poll, change of state, and cyclic I/O messages. These connections are established through UCMM or predefined master/slave connection set.
Dimensions
Four inputs and four inputs/outputs
Application
For operator stations
For use with PNP Sensors or 0.5 Amp outputs
Features
PNP short-circuit protected inputs
0.5 Amp short-circuit protected outputs]
All of the I/O is powered by DeviceNet
Nickel plated brass connector
Removable terminal blocks
Terminal Wiring
To connect as inputs To connect as outputs
TURCK Inc. 10240451 Rev 1.1 10/07
(I/O points 0-3 shown as outputs)
FDN20-4S-4XSG-E/C1261
DeviceNet™
Style: 5-Pin eurofast ®
1 = Shield 2 = V + 3 = V – 4 = CAN_H 5 = CAN_L
Cordset: Bus Line use RSC RKC 579-*M Tee: Bus Line use RSC 2RKC 57
Male
Through Bus Mounting Hole
Module Specifications
Supply Voltage
Bus Power 11-26 VDC Internal Current Consumption 75 mA plus sum of sensor and output currents (from bus power)
Input Circuits (4-8) PNP 3-wire sensors or dry contacts
Input Voltage (V+) 18-26 VDC (from bus power) Input Short-Circuit (V+) <700 mA (total, short-circuit protected) Input Signal Current (Input) OFF 0-4 V, 0-0.5 mA ON 8-24 VDC, 1-3.4 mA Input Delay 2.5 ms
Output Circuits (4) DC Actuators
Output Voltage 18-26 VDC (from bus power) Output Load Current 0.5 Amps each (from bus power) Maximum Switching Frequency 100 Hz
Rotary Switch
0-63: Address from switch 64-79: Address from EEPROM 80-99: Reserved
Network Status LED
Green: Established Connection Flashing Green: Ready for Connection Flashing Red: Connecton Time-Out Red: Connection Not Possible
Housing
Material Nylon Enclosure IP 20 Operating Temperature -40° to +70°C (-40° to +158°F)
TURCK Inc. 10240451 Rev 1.1 10/07
Loading...