![](/html/16/16d3/16d398f0ea0d4ff40db437d2cb6a762573d108d52bdcd5a67658b4535bd94c3e/bg1.png)
Compact I/O station for DeviceNet
16 Universal Digital Channels
FDN20-16XSG
Type designation FDN20-16XSG
Ident no. F0175
Number of channels 16
Electrical isolation I/Os to DeviceNet
internal power consumption <75 mA plus I/O supply
Voltage supply via DeviceNet 24 VDC
Supply voltage 24 VDC
Admissible range field supply 11…26 VDC
Power dissipation, typical
ð 1.2 W
■ DeviceNet slave
■ Removable 5-pin screw-clamp terminal
block, for DeviceNet fieldbus connection
■ Rotary coding switch for setting the De-
viceNet™ address
■ 3 I/O supply groups galvanically isolat-
ed from each other
■ 16 universal digital channels, DI / DO
■ 24 VDC, PNP
■ Output current: 0.5A
■ Protection class IP20
Inputs
Number of channels 16
Input voltage 11…26 VDC
Low level signal voltage < 4 V
High level signal voltage 8…24 V
Low level signal current < 0.5 mA
High level signal current 1…3.4 mA
Max. input current Total: 700 mA
Number of channels 16
Output voltage 18…26 VDC
Output current per channel 0.5A (from Aux)
Switching frequency
Short-circuit protection yes
Fieldbus transmission rate 125/250/500 kbps
Fieldbus address range 0...63
Fieldbus addressing 2 decimally coded rotary switches
UL Certificate pol. deg.2; surr. air temp. max. 40°C; cl.2 ps req.;
Dimensions (W x L x H) 57.1 x 152.2 x 44.1mm
Housing material Nylon
Operating temperature -40…70°C
Protection class IP20
UL Certificate pol. deg.2; surr. air temp. max. 40°C; cl.2 ps req.;
ð 100 Hz
tight. torque max. 0.56-0.79 Nm
tight. torque max. 0.56-0.79 Nm
Edition • 2021-04-09T11:50:59+02:00
1 / 2 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
![](/html/16/16d3/16d398f0ea0d4ff40db437d2cb6a762573d108d52bdcd5a67658b4535bd94c3e/bg2.png)
Compact I/O station for DeviceNet
16 Universal Digital Channels
FDN20-16XSG
Terminal assignment
DeviceNet and Power Supply
Fieldbus cable (example):
CBC5-572-2M (ident no. 6606065) or
RKC5701-5M (ident no. 6931035)
Power Supply and I/O Channels
AUX1: Supply of the I/O channels 0 to 7
AUX2: Supply of the I/O channels 8 to 13
AUX3: Supply of the I/O channels 14 to 15
Via terminals V+ and V- more devices can be fed from the De-
viceNet™ supply with 24 VDC or with up to 0.7A.
Edition • 2021-04-09T11:50:59+02:00