Turck FAS20-4S-4G-E-A Data Sheet

FAS20-4S-4G-E-A
This module provides one connector with
AUX+
four PNP inputs and four PNP outputs each for connection to AS-interface
®
. The wiring is simple screw terminals to support multiple I/O congurations.
A short-circuit on any I/O point is indicated by a fault signal per the AS-i v3.0 specication. All inputs are powered from the auxillary power supply.
All outputs are powered from the auxillary power.
The node address can be set using an AS-i handheld addressing tool or via software through the AS-i master.
This station supports extended address mode (1-31 A/B).
Integrated Design:
• AS-interface® station
• Four inputs and four outputs
• For dry environments
• For use with four 3-wire discrete sensors
Features:
• PNP short-circuit protected inputs
• Short-circuit protected outputs
• Glass lled nylon with nickel plated brass connectors
Connector:
Type “Bus”
4-pin eurofast
®
Pinouts
1 = AS-i (V+) 2 = V­3 = AS-i (V-) 4 = V+
Bus
Dimensions:
Terminal Wiring:
ASi+
ASi­N/C
AUX-
V+
I I
I
I
o
o o
o
V-
3
2
1
0
3
2
1
0
Turck Inc. 10240516 Rev 1.2 1/19 1
FAS20-4S-4G-E-A
Module Specications:
Electrical
Operating Voltage 18-31 Volts (from AS-i Network) Internal Current Consumption 30 mA Auxiliary Power Consumption ≤ 1 A (total)
Input Circuits (4) PNP 3-wire sensors or dry contacts
Input Short-Circuit (I
out
I
(max) 700 mA (shared by sensors) Input Signal State O < 2mA On = 3.0 – 3.4 mA Input Delay 2.5 ms
Output Circuits
Output Current ≤ 1 A (from auxiliary power, shared with inputs and outputs)
LED Indications
Aux LED O = O Green = On AS-i Network LED O = O Green = Ok Red/Green = Fault
max
) 700 mA (from auxiliary power)
Connections
AS-interface® eurofast® or 5-pin screw terminals Auxillary Power eurofast or 5-pin screw terminals Screw terminal torque = 0.5 Nm max.
Device Address
Address Adjustment 1A – 31A / 1B – 31B (V3.0)
Mechanical
Material Nylon Operating Temperature -13° to +158°F (-25° to +70°C ) Protection IP20 Pollution degree 2 environment
Data and Parameter Bit:
I/O Data
Parameter Group
D
3
O
3
I
3
P
3
Not Used Not Used OGS Enable IGS Enable
D
2
O
2
I
2
P
2
D
1
O
1
I
1
P
1
D
0
O
0
I
0
P
0
IO Code 7 ID Code A ID2 Code 7
Current parameter P0 represents IGS and OGS simultaneously. I/O faults are reported via the AS-i peripheral fault bit.
Turck Inc. 10240516 Rev 1.2 1/19 2