Integrated Design:
• AS-interface
®
station
• Four input and three outputs
Applications:
• For dry environments
• For use with four 2-wire or
3-wire discrete sensors
This module provides one connector with
four PNP inputs and three PNP outputs for
connection to AS-interface
®
. The wiring is
simple screw terminals to support multiple I/O
congurations.
A short-circuit on any I/O point is indicated by
a fault signal per the AS-i v3.0 specication.
All inputs and outputs are powered from the
AS-i line.
Dimensions:
The node address can be set using an AS-i
handheld addressing tool or via software
through the AS-i master.
This station supports extended address mode
1–31 A/B (V2.1, 3.0).
Features:
• PNP short-circuit protected inputs
• Short-circuit protected outputs
• Glass lled nylon with nickel
plated brass connectors
Terminal Wiring:
ASi+
ASiN/C
N/C
N/C
AUX-
V+
I
I
I
I
o
o
o
o
V-
3
2
1
0
3
2
1
0
Turck Inc. 10240522 Rev 1.2 1/19 1
Module Specications:
Electrical
Operating Voltage 18–31 Volts (from AS-i Network)
Internal Current Consumption 30 mA
Input Circuits (4) PNP 3-wire sensors or dry contacts
Input/Output Short-Circuit (I
Input Signal State Off < 2mA
On = 3.0–3.4 mA
Input Delay 2.5 ms
Output Circuits
Output Current Up to 130 mA shared (from AS-i power line)
LED Indications
AS-i Network LED Off = Off
Green = Ok
Red/Green = Fault
Connections
AS-interface® 5-pin screw terminals
Screw terminal torque = 0.5 Nm max.
max
) 130 mA (from AS-i power line)
Device Address
Address Adjustment 1–31 A/B extended address mode (V2.1, 3.0)
Mechanical
Material Nylon
Operating Temperature -13° to +158°F (-25° to +70°C )
Protection IP20
Pollution degree 2 environment
Data and Parameter Bit:
I/O Data
Parameter
Group
D
3
O
3
I
3
P
3
Not Used Not Used Not Used IGS/OGS Enable
D
2
O
2
I
2
P
2
D
1
O
1
I
1
P
1
D
0
O
0
I
0
P
0
IO Code 7
ID Code A
ID2 Code E
Current parameter P0 represents IGS and OGS simultaneously.
I/O faults are reported via the AS-i peripheral fault bit.
Turck Inc. 10240522 Rev 1.2 1/19 2