BL compact™ multiprotocol fieldbus station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
Supported from firmware version3.3.2.0
Released from ARGEE version2.0.17.0
Modbus TCP
AddressingStatic IP, BOOTP, DHCP
Supported function codesFC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23
Number of TCP connections6
Input Data Sizemax. 6 register
Input register start address0 (0x0000 hex)
Output Data Sizemax. 2 register
Output register start address2048 (0x0800 hex)
EtherNet/IP™
Addressingacc. to EtherNet/IP™ specification
Device Level Ring (DLR)supported
Class 1 connections6
Input Data Size7 INT
Output Data Size2 INT
Edition • Rev. C • 2019-01-21T18:38:35+01:00
1 / 8TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
PROFINET
AddressingDCP
Conformance classB (RT)
MinCycleTime1 ms
Diagnosticsacc. to PROFINET alarm handling
Topology detectionsupported
Automatic addressingsupported
Media Redundancy Protocol (MRP)supported
Input Data Sizemax. 8 BYTE
Output Data Sizemax. 4 BYTE
Analog inputsfrom 4AI-VI
Operating modes0/4 … 20 mA or -10/0 … 10 VDC
Resolution16 bit
Repeatability< 0.05 %
Temperature coefficient< 300 ppm / ºC of full scale
Vibration testaccording to IEC 61131-2
Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz)For mounting on base plate or machinery
Shock testaccording to IEC 61131-2
Electromagnetic compatibilityaccording to IEC 61131-2
Approvals and certificatesCE, cULus, Class I Div.2
Dimensions (W x L x H)71 x 168 x 32.5mm
Operating temperature-40...+70 ºC
Storage temperature-40...+85 ºC
Relative humidity15 to 95% (non-condensing)
Protection classIP67
IP69K
MTTF98 years acc. to SN 29500 (Ed. 99) 20 °C
Housing materialGlass-filled nylon, nickel plated brass connectors
Housing colorBlack
Window materialLexan
Material screwNickel-plated brass
Material labelPolyester with polycarbonate overlay
Ground label materialNickel plated brass
Weight600 ± 20 g
Mounting2 × 5.4 mm diameter holes, 1.7 Nm torque
Edition • Rev. C • 2019-01-21T18:38:35+01:00
2 / 8TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
Pinning and wiring diagram
Ethernet
Fieldbus cable (IP67 example): RSSD RSSD 441-2M ID number
U-02482 or RSSD-RSSD-441-2M/S2174 ID number 6914218
U2187-09 or RKC4.5T-2-RSC4.5T/TEL ident-no. 6625212
Pin Assignment
2-wire Technology (Current)
2-wire connection (voltage)
3-wire connection
Edition • Rev. C • 2019-01-21T18:38:35+01:00
3 / 8TURCK Inc.
4-wire Technology
4-wire connection (external voltage supply)
BL compact™ multiprotocol fieldbus station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
BL compact™ multiprotocol fieldbus station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
Station LED status
LEDColorStatusDescription
IOsOFFNo power
REDONLow power or station error
REDFLASHING (1 Hz)I/O module configuration error
REDFLASHING (4 Hz)No I/O module bus communication
GREENONStation ok
GREENFLASHINGForce mode active
BUSOFFPower Off
GREENONConnected to Master
GREENFLASHINGReady
GREENFLASHING 3x (1Hz)ARGEE Running
REDONError
REDFLASHINGWINK
YELLOWONDHCP/BOOTP Search
LNK/ACT
GREENONLink
GREENFLASHINGTraffic
YELLOWON100 Mbit Linked
I/O LED status slot 1
LEDColorStatusDescription
D1 *OFFNo diagnostics active
REDONStation error/ module bus communication failure
REDFLASHING (0.5Hz)Diagnostics active (Slot 1)
AI channelsOFFNot active
10...1
3
* D1 LED also indicates gateway diagnostics
I/O LED status slot 2
LEDColorStatusDescription
D2 *OFFNo diagnostics active
AO channels
0 / 1
* D2 LED also indicates gateway diagnostics
GREENONActive
GREENFLASHING (0.5 Hz)Underflow in measuring range
GREENFLASHING (4 Hz)Overflow in measuring range
REDONStation error/ module bus communication failure
REDFLASHING (0.5Hz)Diagnostics active (Slot 2)
OFFNo Link
Not connected
Edition • Rev. C • 2019-01-21T18:38:35+01:00
5 / 8TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
*The scheduled diagnostic information changes every 125 ms between Slot 1 and Slot 2, if both slots send active diagnostics.
Legend:
AIAnalog InputMRMeasurement Value Range Error
AOAnalog OutputOCOpen Circuit
CFGConfiguration ErrorS1Slot 1
COMCommunication FailureVI LowVI Voltage
DIADiagnostics ActiveVO LowVO Voltage
FCEForce Mode Active
Modbus® TCP Register Mapping
Inputs (RO)
Status (RO)0x0004-FCE--CFGCOM VI low -VO low ------DIA
Diag. (RO)0x0005--------------S2 DIA S1 DIA
Outputs (RW)
I/O Diag. (RO)
PROFINET® Process Data
Inputs
Edition • Rev. C • 2019-01-21T18:38:35+01:00
6 / 8TURCK Inc.
0AI 10 LSBAI 1
1AI 10 MSB
2AI 11 LSBAI 1
3AI 11 MSB
4AI 12 LSBAI 1
5AI 12 MSB
6AI 13 LSBAI 1
7AI 13 MSB
8Module number reporting diagnostic dataDiagnostics
9Replace Sta-
tion
10------Open Circuit
11------Open Circuit
12------Open Circuit
13------Open Circuit
-Diagnostics
Active
-----
AI 1
0
AI 1
1
AI 1
2
AI 1
3
Range Error
AI 1
0
Range Error
AI 1
1
Range Error
AI 1
2
Range Error
AI 1
3
0AO 20 LSBAO 2
1AO 20 MSB
2AO 21 LSBAO 2
3AO 21 MSB
REGBit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7Bit 6 Bit 5Bit 4 Bit 3Bit 2 Bit 1Bit 0
0x0000AI 1
0x0001AI 1
0x0002AI 1
0x0003AI 1
0x0800AO 2
0x0801AO 2
0xA000------OCAI
0xA001------OCAI
0
1
2
3
0
1
MRAI
------OCAI
1
1
1
1
MRAI
------OCAI
1
1
3
3
1
0
1
2
BYTEBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0AI 10 LSB
1AI 10 MSB
2AI 11 LSB
3AI 11 MSB
4AI 12 LSB
5AI 12 MSB
6AI 13 LSB
7AI 13 MSB
0AO 20 LSBOutputs
1AO 2 MSB
MRAI
1
0
MRAI
1
2
BL compact™ multiprotocol fieldbus station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
2AO 21 LSB
3AO 21 MSB
Edition • Rev. C • 2019-01-21T18:38:35+01:00
7 / 8TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet
4 Analog Inputs for Current or Voltage and 2 Analog Outputs for Current
BLCEN-6M12LT-4AI-VI-2AO-I
Accessories
Type codeIdent-No.Description
LOCK-EURO-CA0885Locking guard for straight eurofast™ C-body connectors
(RKC, RKCV, RSC, RSCV) in a Class I, Division 2 installa-
tions
LOCK-EURO-C (10/BAG) A0886Locking guard for straight eurofast™ C-body connectors
(RKC, RKCV, RSC, RSCV) in a Class I, Division 2 installa-
tions
Edition • Rev. C • 2019-01-21T18:38:35+01:00
8 / 8TURCK Inc.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.