Datasheet BLCEN-4M12MT-8DO-0.5A-P Datasheet (Turck)

BL compact™ multiprotocol fieldbus station for Industrial Ethernet 8 Digital PNP Outputs BLCEN-4M12MT-8DO-0.5A-P
Type designation BLCEN-4M12MT-8DO-0.5A-P
Ident-No. 6811470
Fieldbus transmission rate 10/100 Mbps Adjustment transmission rate Automatic detection Fieldbus connection technology 2 × M12, 4-pole, D-coded Fieldbus address range 1…92
0 (192.168.1.254) 93 (BootP) 94 (DHCP) 95 (PGM) 96 (PGM-DHCP) *Recommended for PROFINET
97…98 (manufacturer specific) Fieldbus addressing 2 decimally coded rotary switches Protocol detection automatic Web server Integrated Service interface Ethernet Vendor ID 48 Product type 12 Product code 11470
On-machine Compact fieldbus I/O block
EtherNet/IP™, Modbus® TCP, or
PROFINET slave
Integrated Ethernet Switch
10 Mbps / 100 Mbps supported
Two 4-pole M12, D-coded, connectors
for fieldbus connection
2 rotary switches for node address
IP67, IP69K
M12 I/O connectors
LEDs indicating status and diagnostics
Electronics galvanically separated from
the field level via optocouplers
8 digital PNP outputs, 24 VDC
Max. 0.5A per output
FLC/ARGEE programmable
Field Logic Controller (FLC)
Supported from firmware version 3.3.2.0 Released from ARGEE version 2.0.17.0
Modbus TCP
Addressing Static IP, BOOTP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 6 Input Data Size max. 2 register Input register start address 0 (0x0000 hex) Output Data Size max. 1 register Output register start address 2048 (0x0800 hex)
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification Device Level Ring (DLR) supported Class 1 connections 6 Input Data Size 2 INT Output Data Size 1 INT
PROFINET
Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) supported Output Data Size max. 2 BYTE
Edition • Rev. B • 2019-01-21T18:32:27+01:00
1 / 5 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 8 Digital PNP Outputs BLCEN-4M12MT-8DO-0.5A-P
Digital outputs
Output type PNP Type of output diagnostics Channel diagnostics Output voltage 24 VDC Output current per channel 0.5 A Output delay 3 ms Load type resistive, inductive, lamp load Load resistance, resistive Load resistance, inductive < 1.2 H Lamp load < 3 W Switching frequency, resistive < 200 Hz Switching frequency, inductive < 2 Hz Switching frequency, lamp load < 20 Hz Short-circuit protection yes
Vibration test according to IEC 61131-2 Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility according to IEC 61131-2 Approvals and certificates CE, cULus
Dimensions (W x L x H) 71 x 113 x 32.5mm Operating temperature -40...+70 ºC Storage temperature -40...+85 ºC Relative humidity 15 to 95% (non-condensing) Protection class IP67
MTTF 147 years acc. to SN 29500 (Ed. 99) 20 °C Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Window material Lexan Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Weight 390 ± 20 g Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque
> 48 ò
IP69K
Edition • Rev. B • 2019-01-21T18:32:27+01:00
2 / 5 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 8 Digital PNP Outputs BLCEN-4M12MT-8DO-0.5A-P
Pinning and wiring diagram
Ethernet
Fieldbus cable (IP67 example): RSSD RSSD 441-2M ID number
U-02482 or RSSD-RSSD-441-2M/S2174 ID number 6914218
Pin Assignment (M12, D-code)
Digital Outputs
Extension cable (example): RK 4.4T-2-RS 4.4T ident-no. U2445 or
RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
Auxiliary Power
Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no.
U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
Pin Assignment
Wiring Diagram
Pin Assignment
Edition • Rev. B • 2019-01-21T18:32:27+01:00
3 / 5 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 8 Digital PNP Outputs BLCEN-4M12MT-8DO-0.5A-P
Station LED status
LED Color Status Description
IOs OFF No power
RED ON Low power or station error
RED FLASHING (1 Hz) I/O module configuration error
RED FLASHING (4 Hz) No I/O module bus communication
GREEN ON Station ok
GREEN FLASHING Force mode active
BUS OFF Power Off
GREEN ON Connected to Master
GREEN FLASHING Ready
GREEN FLASHING 3x (1Hz) ARGEE Running
RED ON Error
RED FLASHING WINK
YELLOW ON DHCP/BOOTP Search
LNK/ACT
GREEN ON Link
GREEN FLASHING Traffic
YELLOW ON 100 Mbit Linked
I/O LED status
LED Color Status Description
D * OFF No diagnostics active
RED ON Station error/ module bus communication failure
RED FLASHING (0.5Hz) Diagnostics active
DO channel OFF Status of channel x = „0“ (OFF),
0...7
* D LED also indicates gateway diagnostics
GREEN ON Status of channel x = „1“ (ON)
RED ON Short circuit / overload on channel x
OFF No Link
no diagnostics active
Edition • Rev. B • 2019-01-21T18:32:27+01:00
4 / 5 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 8 Digital PNP Outputs BLCEN-4M12MT-8DO-0.5A-P
Process Data Mapping of Each Protocol
EtherNet/IP™ I/O & Diagnostics Data Mapping
INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Module number reporting diagnostic dataDiagnostics
1 Replace Sta-
tion
Slot 1 (ref. Byte
0)
2 Over Current
DO 1
7
3 - - - - - - - -
OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 DO 1
7
1 - - - - - - - -
Legend:
CFG Configuration Error FCE Force Mode Active
COM Communication Failure SC Short Circuit / Overcurrent
DIA Diagnostics Active VI VI Voltage
DO Digital Output VO VO Voltage
Modbus® TCP Register Mapping
REG Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Status (RO) 0x0000 - FCE - - CFG COM VI low - VO low - - - - - - DIA
Diag. (RO) 0x0001 - - - - - - - - - - - - - - - S1 DIA
Outputs (RW) 0x0800 - - - - - - - - DO 17DO 16DO 15DO 14DO 13DO 12DO 11DO 1
I/O Diag. (RO) 0xA000 - - - - - - - - SCDO
PROFINET® Process Data
BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Outputs
0 DO 1
7
1 - - - - - - - -
- Diagnostics
Active
Over Current
DO 1
6
DO 1
6
DO 1
6
Over Current
DO 1
5
DO 1
5
DO 1
5
- - - - -
Over Current
DO 1
4
DO 1
4
DO 1
4
Over Current
DO 1
3
DO 1
3
SCDO
1
1
7
DO 1
3
Over Current
DO 1
DO 1
6
DO 1
2
2
SCDO
1
5
2
Over Current
DO 1
DO 1
SCDO
1
4
DO 1
1
1
SCDO
1
3
1
SCDO
1
Over Current
DO 1
0
DO 1
0
SCDO
1
2
1
DO 1
0
SCDO
1
0
0
Edition • Rev. B • 2019-01-21T18:32:27+01:00
5 / 5 TURCK Inc.
Loading...