Turck BLCEN-4M12MT-4IOL Data Sheet

BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 IO-Link Channels BLCEN-4M12MT-4IOL
Type designation BLCEN-4M12MT-4IOL
Ident-No. 6811499
Fieldbus transmission rate 10/100 Mbps Adjustment transmission rate Automatic detection Fieldbus connection technology 2 × M12, 4-pole, D-coded Fieldbus address range 1…92
0 (192.168.1.254) 93 (BootP) 94 (DHCP) 95 (PGM) 96 (PGM-DHCP) *Recommended for PROFINET
97…98 (manufacturer specific) Fieldbus addressing 2 decimally coded rotary switches Protocol detection automatic Web server Integrated Service interface Ethernet Vendor ID 48 Product type 12 Product code 11499
On-machine Compact fieldbus I/O block
EtherNet/IP™, Modbus® TCP, or
PROFINET slave
Integrated Ethernet Switch
10 Mbps / 100 Mbps supported
Two 4-pole M12, D-coded, connectors
for fieldbus connection
2 rotary switches for node address
IP67, IP69K
M12 I/O connectors
LEDs indicating status and diagnostics
Electronics galvanically separated from
the field level via optocouplers
FLC/ARGEE programmable
Field Logic Controller (FLC)
Supported from firmware version 3.3.2.0 Released from ARGEE version 2.0.17.0
Modbus TCP
Addressing Static IP, BOOTP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 6 Input Data Size max. 10 register Input register start address 0 (0x0000 hex) Output Data Size max. 8 register Output register start address 2048 (0x0800 hex)
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification Device Level Ring (DLR) supported Class 1 connections 6 Input Data Size 13 INT Output Data Size 8 INT
Edition • Rev. C • 2019-01-21T18:46:27+01:00
1 / 7 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 IO-Link Channels BLCEN-4M12MT-4IOL
PROFINET
Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) supported Input Data Size max. 16 BYTE Output Data Size max. 16 BYTE
Digital inputs from 4IOL Input type PNP Low level signal voltage < 5 V High level signal voltage > 11 V Low level signal current < 1.5 mA DI / < 5mA SIO High level signal current 2.1 ... 3.7 mA DI / 5 ... 11 mA SIO
Digital outputs from 4IOL Output type PNP Output voltage 24 VDC Output current per channel 0.5 A Output delay 3 ms Load type resistive, inductive, lamp load Load resistance, resistive Load resistance, inductive < 1.2 H Lamp load < 3 W Switching frequency, resistive < 200 Hz Switching frequency, inductive < 2 Hz Switching frequency, lamp load < 20 Hz Short-circuit protection yes
> 48 ò
IO-Link Pin 4 in IOL mode IO-Link specification version 1.1 IO-Link port type Class A Frame type supports all specified frame types Supported devices max. 14 byte inpute / 14 byte output Transmission rate 4.8 kbps (COM 1) / 38.4 kbps (COM 2) / 230 kbps
(COM 3)
Vibration test according to IEC 61131-2 Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility according to IEC 61131-2 Approvals and certificates CE, cULus, Class I Div.2
Dimensions (W x L x H) 71 x 113 x 32.5mm Operating temperature -40...+70 ºC Storage temperature -40...+85 ºC Relative humidity 15 to 95% (non-condensing) Protection class IP67
IP69K MTTF 136 years acc. to SN 29500 (Ed. 99) 20 °C Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Window material Lexan Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Weight 390 ± 20 g Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque
Edition • Rev. C • 2019-01-21T18:46:27+01:00
2 / 7 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 IO-Link Channels BLCEN-4M12MT-4IOL
Pinning and wiring diagram
Ethernet
Fieldbus cable (IP67 example): RSSD RSSD 441-2M ID number
U-02482 or RSSD-RSSD-441-2M/S2174 ID number 6914218
Pin assignment (M12, D-coded)
I/O Channels
Extension cable (example): RK 4.4T-2-RS 4.4T ident-no. U2445 or
RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
Auxiliary Power
Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no.
U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
Pin Assignment
Pin Assignment
Edition • Rev. C • 2019-01-21T18:46:27+01:00
3 / 7 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 IO-Link Channels BLCEN-4M12MT-4IOL
Station LED status
LED Color Status Description
IOs OFF No power
RED ON Low power or station error
RED FLASHING (1 Hz) I/O module configuration error
RED FLASHING (4 Hz) No I/O module bus communication
GREEN ON Station ok
GREEN FLASHING Force mode active
BUS OFF Power Off
GREEN ON Connected to Master
GREEN FLASHING Ready
GREEN FLASHING 3x (1Hz) ARGEE Running
RED ON Error
RED FLASHING WINK
YELLOW ON DHCP/BOOTP Search
LNK/ACT
GREEN ON Link
GREEN FLASHING Traffic
YELLOW ON 100 Mbit Linked
I/O LED status
LED Color Status Description
D * OFF No diagnostics active
RED ON Station error/ module bus communication failure
RED FLASHING (0.5Hz) Diagnostics active
IO-Link Mode channels
10...1
3
GREEN Flashing IO-Link communication, Process data valid
RED ON No IO-Link communication
OFF No Link
OFF Channel Status x = “0“ (OFF),
no diagnostics active
3
GREEN ON Channel Status x = “1” (ON)
7
GREEN ON Channel Status x = “1” (ON)
* D LED also indicates gateway diagnostics
Flashing Process Data Invalid
OFF Channel Status x = “0” (OFF)DI Mode 10...1
OFF Channel Status x = “0” (OFF)XSG 14...1
Edition • Rev. C • 2019-01-21T18:46:27+01:00
4 / 7 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 IO-Link Channels BLCEN-4M12MT-4IOL
Process Data Mapping of Each Protocol
EtherNet/IP™ I/O & Diagnostics Data Mapping
INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Digital
0 DI 1
7
1 OCDO 17OCDO 16OCDO 15OCDO 14DVS 1
IOL Data 2…15 IO-Link Read Data (depends on parameter settings)
16 Module number reporting diagnostic dataDiagnostics
17 Replace Sta-
tion
Slot 1 (ref. Byte
18 IOL 10 EVT2 IOL 10 EVT1 IOL 10 PDINV IOL 10 HWER IOL 10 DSER IOL 1
16)
19 IOL 10 GEN-ERIOL 10 OVL IOL 10 VHIGH IOL 10 VLOW IOL 10 ULVE IOL 10 LLVU IOL 10 OTMP IOL 1
20 IOL 11 EVT2 IOL 11 EVT1 IOL 11 PDINV IOL 11 HWER IOL 11 DSER IOL 1
21 IOL 11 GEN-ERIOL 11 OVL IOL 11 VHIGH IOL 11 VLOW IOL 11 ULVE IOL 11 LLVU IOL 11 OTMP IOL 1
22 IOL 12 EVT2 IOL 12 EVT1 IOL 12 PDINV IOL 12 HWER IOL 12 DSER IOL 1
23 IOL 12 GEN-ERIOL 12 OVL IOL 12 VHIGH IOL 12 VLOW IOL 12 ULVE IOL 12 LLVU IOL 12 OTMP IOL 1
24 IOL 13 EVT2 IOL 13 EVT1 IOL 13 PDINV IOL 13 HWER IOL 13 DSER IOL 1
25 IOL 13 GEN-ERIOL 13 OVL IOL 13 VHIGH IOL 13 VLOW IOL 13 ULVE IOL 13 LLVU IOL 13 OTMP IOL 1
OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 DO 1
7
1 - - - - - - - -
IOL Data 2…15 IO-Link Write Data (depends on parameter settings)
Legend
GENER Common error EVT1 Maintenance events
VHIGH Overvoltage HWER Hardware error
ULVE Upper limit value exceeded CFGER Wrong or missing device
OTMP Overtemperature DVS Data Valid Signal
EVT2 Out of specification error OC Over Current
PDINV Process input data invalid DIAG Diagnostics
DSER Data storage error DO Digital Output
OVL Overload DI Digital Input
VLOW Undervoltage COM Communication Lost Bit
LLVU Lower limit value underrun CFG Connfiguration Error
PRMER Parameterization error
Modbus® TCP Register Mapping
REG Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Inputs (RO)
0x0000 OCDO
OCDO
1
7
0x0001…
0x0007
Status (RO) 0x000C - FCE - - CFG COM VI low VI high VO low VO
Diag. (RO) 0x000D - - - - - - - - - - - - - - - S1
0x0800 - - - - - - - - DO 17DO 16DO 15DO 1
0x0801…
0x0807
I/O Diag. (RO)
0xA000 IOL 1
GEN-
0
IOL 1
OVL
ER
01A001 IOL 1
Edition • Rev. C • 2019-01-21T18:46:27+01:00
5 / 7 TURCK Inc.
GEN-
ER
1
IOL 1
OVL
DI 1
6
- Diagnostics
DO 1
6
OCDO
OCDO
1
1
6
0
1
IOL 1
VHIGH
IOL 1
VHIGH
1
5
IOL 1
0
VLOW
IOL 1
1
VLOW
DI 1
5
DI 1
4
DI 1
3
DI 1
2
DVS 1
3
DI 1
1
DVS 1
2
DI 1
0
DVS 1
1
0
- - - - -
Active
- OCDO 1
0
CFGER
0
PRMER
- OCDO 1
1
CFGER
1
PRMER
- OCDO 1
2
CFGER
2
PRMER
- OCDO 1
3
CFGER
3
PRMER
DO 1
5
DO 1
4
- - - -Digital
DVS 13DVS 12DVS 11DVS 10DI 17DI 16DI 15DI 14DI 13DI 12DI 11DI 1
4
IO-Link Read Data (depends on parameter settings)
OCVI - - - - DIAG
high
4
- -Outputs (RW)
IO-Link Write Data (depends on parameter settings)
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
DSER
IOL 1
DSER
IOL 1
0
CFGER
IOL 1
1
CFGER
0
1
0
1
ULVE
IOL 1
ULVE
0
1
LLVU
IOL 1
LLVU
0
1
OTMP
IOL 1
OTMP
0
PRMER
IOL 1
1
PRMER
0
1
EVT2
IOL 1
EVT2
0
1
EVT1
IOL 1
EVT1
0
1
PDINV
IOL 1
PDINV
0
1
HWER
IOL 1
HWER
0
1
4
5
6
7
DIAG
- OC
DO 1
- OC
DO 1
0
4
5
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 IO-Link Channels BLCEN-4M12MT-4IOL
01A002 IOL 1
01A003 IOL 1
PROFINET® Process Data
Inputs
0 DI 1
1 OCDO 17OCDO 16OCDO 15OCDO 14DVS 1
2…15 IO-Link Read Data (depends on parameter settings)
Outputs
0 DO 1
1 - - - - - - - -
2…15 IO-Link Write Data (depends on parameter settings)
GEN-
ER
GEN-
ER
2
3
IOL 1
OVL
IOL 1
OVL
7
7
2
3
IOL 1
VHIGH
IOL 1
VHIGH
DI 1
DO 1
2
3
6
IOL 1
VLOW
IOL 1
VLOW
6
2
3
IOL 1
ULVE
IOL 1
ULVE
DI 1
DO 1
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
DSER
IOL 1
DSER
1
1
IOL 1
2
CFGER
IOL 1
3
CFGER
2
2
2
2
2
2
2
2
LLVU
OTMP
PRMER
EVT2
EVT1
PDINV
HWER
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
IOL 1
PDINV
2
2
3
IOL 1
HWER
DI 1
DVS 1
3
3
3
3
3
3
3
LLVU
OTMP
PRMER
EVT2
EVT1
5
5
DI 1
DO 1
4
4
DI 1
3
DI 1
DVS 1
3
- - - -
2
3
DI 1
DVS 1
0
0
- OC
DO 1
- OC
DO 1
6
7
Edition • Rev. C • 2019-01-21T18:46:27+01:00
6 / 7 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 IO-Link Channels BLCEN-4M12MT-4IOL
Accessories
Type code Ident-No. Description
LOCK-EURO-C A0885 Locking guard for straight eurofast™ C-body connectors
(RKC, RKCV, RSC, RSCV) in a Class I, Division 2 installa-
tions
LOCK-EURO-C (10/BAG) A0886 Locking guard for straight eurofast™ C-body connectors
(RKC, RKCV, RSC, RSCV) in a Class I, Division 2 installa-
tions
Edition • Rev. C • 2019-01-21T18:46:27+01:00