Turck BLCEN-4M12MT-4AI4AO-VI Data Sheet

BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Current or Voltage and 4 Analog Outputs for Voltage BLCEN-4M12MT-4AI4AO-VI
On-machine Compact fieldbus I/O block
EtherNet/IP™, Modbus® TCP, or
PROFINET slave
Integrated Ethernet Switch
10 Mbps / 100 Mbps supported
Two 4-pole M12, D-coded, connectors
for fieldbus connection
2 rotary switches for node address
IP67, IP69K
M12 I/O connectors
LEDs indicating status and diagnostics
Electronics galvanically separated from
the field level via optocouplers
Type designation BLCEN-4M12MT-4AI4AO-VI
Ident-No. 6811451
Fieldbus transmission rate 10/100 Mbps Adjustment transmission rate Automatic detection Fieldbus connection technology 2 × M12, 4-pole, D-coded Fieldbus address range 1…92
0 (192.168.1.254) 93 (BootP) 94 (DHCP) 95 (PGM) 96 (PGM-DHCP) *Recommended for PROFINET
97…98 (manufacturer specific) Fieldbus addressing 2 decimally coded rotary switches Protocol detection automatic Web server Integrated Service interface Ethernet Vendor ID 48 Product type 12 Product code 11451
4 analog inputs for current or voltage
0/4…20 mA or -10/0…+10 VDC (se-
lectable per channel)
4 analog voltage outputs
-10/0…+10 VDC
FLC/ARGEE programmable
Field Logic Controller (FLC)
Supported from firmware version 3.3.2.0 Released from ARGEE version 2.0.17.0
Modbus TCP
Addressing Static IP, BOOTP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 6 Input Data Size max. 6 register Input register start address 0 (0x0000 hex) Output Data Size max. 4 register Output register start address 2048 (0x0800 hex)
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification Device Level Ring (DLR) supported Class 1 connections 6 Input Data Size 9 INT Output Data Size 4 INT
Edition • Rev. C • 2019-01-21T18:17:41+01:00
1 / 8 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Current or Voltage and 4 Analog Outputs for Voltage BLCEN-4M12MT-4AI4AO-VI
PROFINET
Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) supported Input Data Size max. 8 BYTE Output Data Size max. 8 BYTE
Analog inputs from 4AI4AO-VI Operating modes 0/4 … 20 mA or -10/0 … 10 VDC Resolution 16 bit Repeatability < 0.05 % Temperature coefficient < 300 ppm / ºC of full scale
Analog outputs from 4AI4AO-VI Operating modes -10/0 … 10 V Resolution 16 bit Repeat accuracy < 0.05 % Temperature coefficient < 300 ppm/ºC of full scale
Vibration test according to IEC 61131-2 Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility according to IEC 61131-2 Approvals and certificates CE, cULus, Class I Div.2
Dimensions (W x L x H) 71 x 113 x 32.5mm Operating temperature -40...+70 ºC Storage temperature -40...+85 ºC Relative humidity 15 to 95% (non-condensing) Protection class IP67
IP69K MTTF 110 years acc. to SN 29500 (Ed. 99) 20 °C Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Window material Lexan Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Weight 390 ± 20 g Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque
Edition • Rev. C • 2019-01-21T18:17:41+01:00
2 / 8 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Current or Voltage and 4 Analog Outputs for Voltage BLCEN-4M12MT-4AI4AO-VI
Pinning and wiring diagram
Ethernet
Fieldbus cable (IP67 example): RSSD RSSD 441-2M ID number
U-02482 or RSSD-RSSD-441-2M/S2174 ID number 6914218
Pin assignment (M12, D-coded)
Analog Inputs and outputs
Extension cable (example): RK 4.5T-2-RS 4.5T/S653 ident-no.
U2187-09 or RKC4.5T-2-RSC4.5T/TEL ident-no. 6625212
Pin Assignment
2-wire Technology (Current)
2-wire connection (voltage)
3-wire connection
Edition • Rev. C • 2019-01-21T18:17:41+01:00
3 / 8 TURCK Inc.
4-wire Technology
4-wire connection (external voltage supply)
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Current or Voltage and 4 Analog Outputs for Voltage BLCEN-4M12MT-4AI4AO-VI
Auxiliary Power
Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no.
U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
Pin Assignment
Edition • Rev. C • 2019-01-21T18:17:41+01:00
4 / 8 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Current or Voltage and 4 Analog Outputs for Voltage BLCEN-4M12MT-4AI4AO-VI
Station LED status
LED Color Status Description
IOs OFF No power
RED ON Low power or station error
RED FLASHING (1 Hz) I/O module configuration error
RED FLASHING (4 Hz) No I/O module bus communication
GREEN ON Station ok
GREEN FLASHING Force mode active
BUS OFF Power Off
GREEN ON Connected to Master
GREEN FLASHING Ready
GREEN FLASHING 3x (1Hz) ARGEE Running
RED ON Error
RED FLASHING WINK
YELLOW ON DHCP/BOOTP Search
LNK/ACT
GREEN ON Link
GREEN FLASHING Traffic
YELLOW ON 100 Mbit Linked
I/O LED status
LED Color Status Description
D * OFF No diagnostics active
RED ON Station error/ module bus communication failure
RED FLASHING (0.5Hz) Diagnostics active
AI channels OFF Channel inactive
0...3
AO channels Not connected
4...7 (The analog outputs do not have a LED)
* D LED also indicates gateway diagnostics
GREEN ON Channel active
GREEN FLASHING (0.5 Hz) Underflow diagnostics
GREEN FLASHING (4 Hz) Overflow diagnostics
OFF No Link
Edition • Rev. C • 2019-01-21T18:17:41+01:00
5 / 8 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Current or Voltage and 4 Analog Outputs for Voltage BLCEN-4M12MT-4AI4AO-VI
Process Data Mapping of Each Protocol
EtherNet/IP™ I/O & Diagnostics Data Mapping
INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
2
3
Slot 1 (ref. Byte
8)
OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
2
3
Legend:
MR Measured Value out of range FCE Force Mode Enabled
WB Wire break (4-20 mA only) CFG Configuration Error
OFU Overflow/Underflow COM Modulebus Configuration Error
HW Hardware Error VI LOW Voltage Field Supply Usys
OVR Output value out of range VO LOW Voltage Field Supply Ui
OFU Overflow/Underflow DIA Module Diagnostics Available
Modbus® TCP Register Mapping
Inputs (RO)
Edition • Rev. C • 2019-01-21T18:17:41+01:00
Status (RO) 0x0004 - FCE - - CFG COM VI low - VO low - - - - - - DIA
6 / 8 TURCK Inc.
0 AI 10 LSBAI 1
1 AI 10 MSB
2 AI 11 LSBAI 1
3 AI 11 MSB
4 AI 12 LSBAI 1
5 AI 12 MSB
6 AI 13 LSBAI 1
7 AI 13 MSB
8 Module number reporting diagnostic dataDiagnostics
9 Replace Sta-
tion
10 Hardware
Failure
11 Hardware
Failure
- Diagnostics
- - - - -
Active
- - - AI 10 Over-
flow/Under-
flow
- - - AO 10 Over-
flow/Under-
- Wire Break AI
10 (4…20 mA
Range Error
AI 1
0
range only)
- - Range Error
AO 1
0
flow
12 Hardware
Failure
13 Hardware
Failure
- - - AI 11 Over-
flow/Under-
flow
- - - AO 11 Over-
flow/Under-
- Wire Break AI
11 (4…20 mA
Range Error
AI 1
1
range only)
- - Range Error
AO 1
1
flow
14 Hardware
Failure
15 Hardware
Failure
- - - AI 12 Over-
flow/Under-
flow
- - - AO 12 Over-
flow/Under-
- Wire Break AI
12 (4…20 mA
Range Error
AI 1
2
range only)
- - Range Error
AO 1
2
flow
16 Hardware
Failure
- - - AI 13 Over-
flow/Under-
- Wire Break AI
1
3
Range Error
AI 1
3
flow
17 Hardware
Failure
- - - AO 13 Over-
flow/Under-
- - Range Error
AO 1
3
flow
0 AO 10 LSBAO 1
1 AO 10 MSB
2 AO 11 LSBAO 1
3 AO 11 MSB
4 AO 12 LSBAO 1
5 AO 12 MSB
6 AO 13 LSBAO 1
7 AO 13 MSB
REG Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0x0000 AI 1
0x0001 AI 1
0x0002 AI 1
0x0003 AI 1
0
1
2
3
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Current or Voltage and 4 Analog Outputs for Voltage BLCEN-4M12MT-4AI4AO-VI
Diag. (RO) 0x0005 - - - - - - - - - - - - - - - S1 DIA
Outputs (RW)
I/O Diag. (RO)
PROFINET® Process Data
Inputs
Outputs
0x0800 AO 1
0x0801 AO 1
0x0802 AO 1
0x0803 AO 1
0xA000 HWAO
0xA001 HWAO
0xA002 HWAO
0xA003 HWAO
0
1
2
3
- - - OFUAO
1
4
- - - OFUAO
1
5
- - - OFUAO
1
6
- - - OFUAO
1
7
- - OVRAO
1
4
- - OVRAO
1
5
- - OVRAO
1
6
- - OVRAO
1
7
HWAI
- - - OFUAI
1
1
1
0
HWAI
- - - OFUAI
1
1
5
1
HWAI
- - - OFUAI
1
1
6
2
HWAI
- - - OFUAI
1
1
7
3
1
0
1
1
1
2
1
3
- WBAI
- WBAI
- WBAI
- WBAI
BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 AI 10 LSB
1 AI 10 MSB
2 AI 11 LSB
3 AI 11 MSB
4 AI 12 LSB
5 AI 12 MSB
6 AI 13 LSB
7 AI 13 MSB
0 AO 10 LSB
1 AO 10 MSB
2 AO 11 LSB
3 AO 11 MSB
4 AO 12 LSB
5 AO 12 MSB
6 AO 13 LSB
7 AO 13 MSB
MRAI
1
1
0
0
MRAI
1
1
1
1
MRAI
1
1
2
2
MRAI
1
1
3
3
Edition • Rev. C • 2019-01-21T18:17:41+01:00
7 / 8 TURCK Inc.
BL compact™ multiprotocol fieldbus station for Industrial Ethernet 4 Analog Inputs for Current or Voltage and 4 Analog Outputs for Voltage BLCEN-4M12MT-4AI4AO-VI
Accessories
Type code Ident-No. Description
LOCK-EURO-C A0885 Locking guard for straight eurofast™ C-body connectors
(RKC, RKCV, RSC, RSCV) in a Class I, Division 2 installa-
tions
LOCK-EURO-C (10/BAG) A0886 Locking guard for straight eurofast™ C-body connectors
(RKC, RKCV, RSC, RSCV) in a Class I, Division 2 installa-
tions
Edition • Rev. C • 2019-01-21T18:17:41+01:00
8 / 8 TURCK Inc.
Loading...