Datasheet BLCDP-4M12MT-8XSG-PD Datasheet (Turck)

BL compact™ fieldbus station for PROFIBUS-DP 8 Configurable Digital PNP Channels BLCDP-4M12MT-8XSG-PD
Type designation BLCDP-4M12MT-8XSG-PD
Ident-No. 6811168
Electrical isolation The inputs and outputs of the 8XSG I/O cards are
On-machine Compact fieldbus I/O block
PROFIBUS-DP slave
9.6 kbps … 12 Mbps
Two 5-pole M12, reverse-keyed, connec-
tors for fieldbus connection
2 rotary switches for node address
IP67, IP69K
M12 I/O connectors
LEDs indicating status and diagnostics
Electronics galvanically separated from
the field level via optocouplers
8 Configurable digital PNP channels, 24
VDC
Max. 0.5A per channel
Channel diagnostics
Selection of filtering times (Input delay)
Invertible inputs
Fieldbus transmission rate 9.6 kbps …12 Mbps
Adjustment transmission rate Automatic detection Fieldbus connection technology 2 × M12, 5-pole, reverse keyed Fieldbus address range 0...99 Fieldbus addressing 2 decimally coded rotary switches Service interface RS232 interface
Digital inputs from 8XSG Input type PNP Type of input diagnostics Channel diagnostics Low level signal voltage < 4.5 VDC High level signal voltage 7 ... 30 VDC Low level signal current < 1.5 mA High level signal current 2.1 ... 3.7 mA Input delay (configurable) 0.25 or 2.5 ms
Digital outputs from 8XSG Output type PNP Type of output diagnostics Channel diagnostics Output voltage 24 VDC Output current per channel 0.5 A Output delay 3 ms Load type resistive, inductive, lamp load Load resistance, resistive Load resistance, inductive < 1.2 H Lamp load < 3 W Switching frequency, resistive < 200 Hz Switching frequency, inductive < 2 Hz Switching frequency, lamp load < 20 Hz Short-circuit protection yes
> 48 ò
Vibration test according to IEC 61131-2 Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility according to IEC 61131-2 Approvals and certificates CE, cULus
Edition • Rev. B • 2019-01-21T16:52:05+01:00
1 / 5 TURCK Inc.
BL compact™ fieldbus station for PROFIBUS-DP 8 Configurable Digital PNP Channels BLCDP-4M12MT-8XSG-PD
Dimensions (W x L x H) 71 x 113 x 32.5mm
Operating temperature -40...+70 ºC Storage temperature -40...+85 ºC Relative humidity 15 to 95% (non-condensing) Protection class IP67
IP69K Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Window material Lexan Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Weight 390 ± 20 g Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque
Edition • Rev. B • 2019-01-21T16:52:05+01:00
2 / 5 TURCK Inc.
BL compact™ fieldbus station for PROFIBUS-DP 8 Configurable Digital PNP Channels BLCDP-4M12MT-8XSG-PD
Pinning and wiring diagram
PROFIBUS-DP
Fieldbus cable (example): RSSW RKSW 455-2M ident-no. U0350
or RSSW-RKSW455-2M ident-no. 6602222
Pin Assignment (M12, B-Code)
Digital Inputs and Outputs
Extension cable (example): RK 4.4T-2-RS 4.4T ident-no. U2445 or
RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
Auxiliary Power
Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no.
U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208
Pin Assignment
Pin Assignment
Edition • Rev. B • 2019-01-21T16:52:05+01:00
3 / 5 TURCK Inc.
BL compact™ fieldbus station for PROFIBUS-DP 8 Configurable Digital PNP Channels BLCDP-4M12MT-8XSG-PD
Station LED status
LED Color Status Description
IOs OFF No power
RED ON Low power or station error
RED FLASHING (1 Hz) I/O module configuration error
RED FLASHING (4 Hz) No I/O module bus communication
GREEN ON Station ok
GREEN FLASHING Force mode active
BUS
GREEN ON Field bus communication active
GREEN FLASHING (1 Hz) No field bus communication active, device status OK
RED ON Bus error at the gateway; no data exchange
RED FLASHING Faulty PROFIBUS-DP address
BUS
GREEN ON Field bus communication active
GREEN FLASHING (1 Hz) No field bus communication active, device status OK
RED ON Bus error at the gateway; no data exchange
RED FLASHING Faulty PROFIBUS-DP address
I/O LED status
LED Color Status Description
D * OFF No diagnostics active
RED ON Station error/ module bus communication failure
RED FLASHING (0.5Hz) Diagnostics active
XSG channels
0...7
GREEN ON Channel status x = “1“ (ON)
RED ON Short-circuit at output
RED FLASHING (2 Hz) Short-circuit sensor supply
* D LED also indicates gateway diagnostics
OFF No field bus communication
OFF No field bus communication
OFF Channel status x = “0“ (OFF),
no diagnostics active
Edition • Rev. B • 2019-01-21T16:52:05+01:00
4 / 5 TURCK Inc.
BL compact™ fieldbus station for PROFIBUS-DP 8 Configurable Digital PNP Channels BLCDP-4M12MT-8XSG-PD
I/O Data Map
INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 DI 1
7
1 - - - - - - - -
OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 DO 1
7
1 - - - - - - - -
DI 1
DO 1
6
6
DI 1
DO 1
5
5
DI 1
DO 1
4
4
DI 1
DO 1
3
3
DI 1
DO 1
2
2
DI 1
DO 1
1
1
DI 1
DO 1
0
0
Edition • Rev. B • 2019-01-21T16:52:05+01:00