Turck BLCDN-16M8L-8XSG-P-8XSG-P Data Sheet

BL compact™ fieldbus station for DeviceNet™ 16 Configurable Digital PNP Channels BLCDN-16M8L-8XSG-P-8XSG-P
Type designation BLCDN-16M8L-8XSG-P-8XSG-P
Ident-No. 6811073
Electrical isolation The 8XSG I/O cards have a common reference po-
On-machine Compact fieldbus I/O block
DeviceNet™ slave
125 / 250 / 500 kbps
Two 5-pole M12 connectors for fieldbus
connection
2 rotary switches for node address
IP67
M8 I/O connectors
LEDs indicating status and diagnostics
Electronics galvanically separated from
the field level via optocouplers
16 Configurable digital PNP channels,
24 VDC
Max. 0.5A per channel
Selection of filtering times (Input delay)
Invertible inputs
Fieldbus transmission rate 125/250/500 kbps
Adjustment transmission rate Automatic detection Fieldbus connection technology 2 × M12, 5-pole Fieldbus address range 0...63
64…80 (programmable MACID)
81…99 (manufacturer specific) Fieldbus addressing 2 decimally coded rotary switches Service interface RS232 interface Vendor ID 48 Product type 12 Product code 11073
Digital inputs
Input type PNP Type of input diagnostics Group diagnostics Low level signal voltage < 4.5 VDC High level signal voltage 7 ... 30 VDC Low level signal current < 1.5 mA High level signal current 2.1 ... 3.7 mA Input delay (configurable) 0.25 or 2.5 ms
Digital outputs
Output type PNP Output voltage 24 VDC Output current per channel 0.5 A Output delay 3 ms Load type resistive, inductive, lamp load Load resistance, resistive Load resistance, inductive < 1.2 H Lamp load < 3 W Switching frequency, resistive < 200 Hz Switching frequency, inductive < 2 Hz Switching frequency, lamp load < 20 Hz Short-circuit protection yes
> 48 ò
Edition • Rev. A • 2019-02-04T21:41:17+01:00
1 / 5 TURCK Inc.
BL compact™ fieldbus station for DeviceNet™ 16 Configurable Digital PNP Channels BLCDN-16M8L-8XSG-P-8XSG-P
Vibration test according to IEC 61131-2
Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility according to IEC 61131-2 Approvals and certificates CE, cULus
Dimensions (W x L x H) 71 x 168 x 32.5mm Operating temperature -40...+70 ºC Storage temperature -40...+85 ºC Relative humidity 15 to 95% (non-condensing) Protection class IP67 Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Window material Lexan Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Weight 530 ± 20 g Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque