BL compact™ fieldbus station for CANopen
8 Configurable Digital PNP Channels
BLCCO-4M12S-8XSG-P
Type designation BLCCO-4M12S-8XSG-P
Ident-No. 6811302
Electrical isolation The 8XSG I/O cards have a common reference po-
tential for operating and load voltage due to their
freely selectable digital channels. Subsequently, all
voltage sources (VI / VO / V+) present on this device
must be concurrently connected to suitable power
supplies.
■ On-machine Compact fieldbus I/O block
■ CANopen slave
■ 10, 20, 50, 125, 250, 500, 800, or 1000
kbps
■ Two 5-pole M12 connectors for fieldbus
connection
■ 2 rotary switches for node address
■ IP67, IP69K
■ M12 I/O connectors
■ LEDs indicating status and diagnostics
■ Electronics galvanically separated from
the field level via optocouplers
■ 8 Configurable digital PNP channels, 24
VDC
■ Max. 0.5A per channel
■ Selection of filtering times (Input delay)
■ Invertible inputs
Fieldbus transmission rate 10 kbps …1 Mbps
Adjustment transmission rate Automatic detection
Fieldbus connection technology 2 × M12, 5-pole
Fieldbus address range 1...99
Fieldbus addressing 2 decimally coded rotary switches
Service interface RS232 interface
Digital inputs from 8XSG
Input type PNP
Type of input diagnostics Group diagnostics
Low level signal voltage < 4.5 VDC
High level signal voltage 7 ... 30 VDC
Low level signal current < 1.5 mA
High level signal current 2.1 ... 3.7 mA
Input delay (configurable) 0.25 or 2.5 ms
Digital outputs from 8XSG
Output type PNP
Output voltage 24 VDC
Output current per channel 0.5 A
Output delay 3 ms
Load type resistive, inductive, lamp load
Load resistance, resistive
Load resistance, inductive < 1.2 H
Lamp load < 3 W
Switching frequency, resistive < 200 Hz
Switching frequency, inductive < 2 Hz
Switching frequency, lamp load < 20 Hz
Short-circuit protection yes
> 48 ò
Vibration test according to IEC 61131-2
Extended vibration resistance
- up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery
Shock test according to IEC 61131-2
Electromagnetic compatibility according to IEC 61131-2
Approvals and certificates CE, cULus
Edition • Rev. A • 2019-01-21T17:12:09+01:00
1 / 5 TURCK Inc.

BL compact™ fieldbus station for CANopen
8 Configurable Digital PNP Channels
BLCCO-4M12S-8XSG-P
Dimensions (W x L x H) 71 x 93 x 32.5mm
Operating temperature -40...+70 ºC
Storage temperature -40...+85 ºC
Relative humidity 15 to 95% (non-condensing)
Protection class IP67
IP69K
Housing material Glass-filled nylon, nickel plated brass connectors
Housing color Black
Window material Lexan
Material screw Nickel-plated brass
Material label Polyester with polycarbonate overlay
Ground label material Nickel plated brass
Weight 320 ± 20 g
Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque
Edition • Rev. A • 2019-01-21T17:12:09+01:00
2 / 5 TURCK Inc.