All rights reserved, including those of the translation.
No part of this manual may be reproduced in any form (printed, photocopy, microfilm or any other
process) or processed, duplicated or
permission of Hans Turck GmbH & Co. KG, Muelheim an der Ruhr.
Subject to alterations without notice
der Ruhr
im an
distributed by means of electronic systems without written
1.2Explanation of symbols used..........................................................................................................................1-3
1.3.1Prescribed use ......................................................................................................................................................................................... 1-4
1.3.2Notes concerning planning/installation of this product ......................................................................................................... 1-4
1.4List of revisions ................................................................................................................................................1-5
2.1.2Easy to handle .........................................................................................................................................................................................2-3
3.1General technical data ....................................................................................................................................3-3
3.6.1Default setting of the gateway....................................................................................................................................................... 3-18
3.6.2Address setting via rotary coding switch (rotary mode)....................................................................................................... 3-19
3.6.3Address setting via BootP-mode (300)........................................................................................................................................3-20
3.6.4Address setting via DHCP-mode (400) ........................................................................................................................................3-20
3.6.5Address setting via PGM-mode (500) .......................................................................................................................................... 3-21
3.6.6Address setting via the mode PGM-DHCP (universal mode, 600) ..................................................................................... 3-22
D300815 0215- BL67 multiprotocol
i
Page 4
3.6.7F_Reset (reset to factory settings, 900)....................................................................................
3.6.8Addressing via I/O-ASSISTANT 3 (FDT/DTM) ............................................................................................................................. 3-23
3.6.9Address assignment via Web server (only VN ≥ 03-00)..........................................................................................................3-26
3.7Reset to factory settings............................................................................................................................... 3-27
3.8.1Safety in the web server ....................................................................................................................................................................3-28
3.8.12 Usage of mobile devices ................................................................................................................................................................... 3-36
3.8.13 Web server logout ............................................................................................................................................................................... 3-36
3.8.14 Deactivating the web server............................................................................................................................................................3-37
3.9Status and Control Word of the BL67-stations ........................................................................................... 3-38
3.9.2Control Word .........................................................................................................................................................................................3-38
3.11.1 Diagnostic messages via LEDs ........................................................................................................................................................3-40
3.12 Parameters of the I/O-modules .................................................................................................................. 3-43
3.13Diagnostics of the I/O-modules ................................................................................................................... 3-44
4.2.2QuickConnect in BL67 .......................................................................................................................................................................... 4-4
4.3Device Level Ring (DLR).................................................................................................................................. 4-6
4.4Diagnostic messages via the process data ................................................................................................... 4-7
4.5Classes and Instances of the EtherNet/IP™ stations..................................................................................... 4-8
4.5.1EtherNet/IP™ Standard Classes ......................................................................................................................................................... 4-8
4.5.5Ethernet Link Object (0×F6).............................................................................................................................................................4-18
4.6VSC-Vendor Specific Classes........................................................................................................................ 4-23
4.6.1Class instance of the VSC .................................................................................................................................................................. 4-23
4.6.2Gateway Class (VSC 100, 64h) ......................................................................................................................................................... 4-24
4.6.3Process Data Class (VSC102, 66h).................................................................................................................................................. 4-27
4.6.4Miscellaneous Parameters Class (VSC 126) ................................................................................................................................ 4-29
5Application example: BL67-GW-EN with EtherNet/IP™ (Allen Bradley)
5.2.1Configuration of the network in "RS Logix 5000" .......................................................................................................................5-3
5.2.2Downloading the I/O configuration................................................................................................................................................5-8
5.3I/O data mapping.......................................................................................................................................... 5-10
5.4Process data access ...................................................................................................................................... 5-12
6.3.1Structure of the packed in-/output process data .................................................................................................................... 6-11
6.3.5Register 0×113C and 0×113D: "Restore Modbus-Connection-Parameters".................................................................. 6-15
6.3.6Register 0×113E and 0×113F: "Save Modbus-Connection-Parameters"......................................................................... 6-15
6.4The Service Object ........................................................................................................................................ 6-16
6.5Bit areas: mapping of input-discrete- and coil-areas ................................................................................ 6-18
6.6Output module behavior in case of an error .............................................................................................. 6-19
7Application example: BL67-GW-EN with Modbus TCP (CODESYS Win V3)
7.3Programming with CODESYS .........................................................................................................................7-4
7.3.2Creating a new project .........................................................................................................................................................................7-5
7.3.3Defining the communication settings............................................................................................................................................7-7
7.3.4Adding the Ethernet Adapter ............................................................................................................................................................7-9
7.3.5Adding the Modbus master............................................................................................................................................................. 7-10
7.3.6Adding a Modbus TCP slave............................................................................................................................................................ 7-11
7.3.8CODESYS: Global variables ............................................................................................................................................................... 7-14
7.3.10 Building, login and start ....................................................................................................................................................................7-27
7.3.11 Reading out the process data ......................................................................................................................................................... 7-29
8.2.2FSU in BL67............................................................................................................................................................................................... 8-4
8.7Diagnosis in PROFINET ................................................................................................................................... 8-7
8.7.2Channel-specific error codes of the I/O-modules ...................................................................................................................... 8-8
8.9Description of user data for acyclic services............................................................................................... 8-16
8.9.1Description of the acyclic gateway user data............................................................................................................................8-16
8.9.2Description of the acyclic module user data .............................................................................................................................8-17
9Application example: BL67-GW-EN with PROFINET (S7)
9.1Application example ...................................................................................................................................... 9-2
9.1.3New project in the SIMATIC Manager ............................................................................................................................................ 9-3
9.1.4Setting the PG/PC-interface ............................................................................................................................................................... 9-3
9.1.5Installation of the GSDML-files.......................................................................................................................................................... 9-4
9.1.7Configuring the BL67-station ..........................................................................................................................................................9-10
9.1.8Scanning the network for PROFINET nodes...............................................................................................................................9-11
9.1.9PROFINET neighborhood detection via LLDP ........................................................................................................................... 9-13
9.1.11 Fast Start-Up - configuration of fieldbus nodes .......................................................................................................................9-17
9.2Diagnosis with Step 7 ................................................................................................................................... 9-19
9.2.1Diagnostic messages in the hardware configuration.............................................................................................................9-19
9.2.2Diagnostic telegram with error code ...........................................................................................................................................9-20
10.1.1 Random module arrangement .......................................................................................................................................................10-2
10.3Maximum system extension ........................................................................................................................ 10-3
10.4Creating potential groups ........................................................................................................................... 10-4
10.5Plugging and pulling electronics modules................................................................................................. 10-4
10.6Extending an existing station...................................................................................................................... 10-5
11.3.2 Grounding of inactive metal components................................................................................................................................. 11-5
11.3.3 PE connection....................................................................................................................................................................................... 11-5
11.4Shielding of cables ....................................................................................................................................... 11-7
11.5.2 Protection against Electrostatic Discharge (ESD) .................................................................................................................... 11-8
12Appendix
12.1Changing the IP address of a PC/ network interface card ......................................................................... 12-2
12.1.1 Changing the IP address in Windows .......................................................................................................................................... 12-2
12.1.2 Changing the IP address via PACTware™ FDT/DTM (I/O-ASSISTANT V3) ...................................................................... 12-4
12.2Deactivating/ adapting the firewall in Windows ....................................................................................... 12-5
12.3Addressing via DHCP.................................................................................................................................... 12-7
12.4Nominal current consumption of modules on Ethernet ........................................................................... 12-9
12.5Ident codes of the BL67-modules.............................................................................................................. 12-11
1.3.1Prescribed use .......................................................................................................................................................................................4
1.3.2Notes concerning planning/installation of this product .......................................................................................................4
1.4List of revisions ................................................................................................................................. 5
This manual contains all information about the multiprotocol-gateway of the product line BL67 (BL67GW-EN).
In addition to a short BL67-system description and the protocol-independent properties of the gateway
and if necessary of the I/O-modules (technical properties, diagnostics, parameters, etc.), the following
chapters contain two protocol-dependent chapters respectively.
The protocol-dependent chapters contain on the one hand the protocol-specific gateway-properties
and on the other hand an application example for the respective Ethernet-protocol, describing the
device's connection to automation devices.
EtherNet/IP™
– chapter 4, Implementation of EtherNet/IP™
– chapter 5, Application example: BL6
Modbus TCP
– chapter 6, Implementation of Modbus TCP
– chapter 7, Application example: BL67-GW-EN with Modb
PROFINET
7-GW-EN with EtherNet/IP™ (Allen Bradley)
us TCP (CODESYS Win V3)
– chapter 8, Implementation of PROFINET
– chapter 9, Application example: BL67-GW-EN with PROFINET (S7)
Addition
electrical installation, etc.
ally, the manual contain protocol-independent guideline for station configuration, the
1.1.1Additional documentation
BL67 I/O-modules (TURCK-documentation no.: German D300572; English D300529).
The bus-independent I/O-modules of the BL67-system as well as all bus independent information
as mounting, labeling etc. are described in a separate manual.
In addition to that, the manual contains a short description of the I/O-ASSISTANT, the project
planning and configuration software tool for TURCK I/O-systems-
Action-related warnings are placed next to potentially dangerous work steps and are marked by
phic symbols. Each warning is initiated by a warning sign and a signal word that expresses the grav-
gra
ity of the danger. The warnings have absolutely to be observed.
DANGER!
DANGER indicates an immediatel
injury, if not avoided.
WARNING!
WARNING indicates a potentially dangerous situatio
injury, if not avoided.
CAUTION!
WARNING indicates a potentially dangerous situatio
injury, if not avoided.
y dangerous situation, with high risk, the death or severe
n with medium risk, the death or severe
n with medium risk, the death or severe
1.2.1Further notes
CALL TO ACTION
This symbol identifies steps that the user has to perform.
RESULTS OF ACTION
This symbol identifies relevant results of steps
ATTENTION!
ATTENTION indicates a situation that may lead to property
NOTE
In NOTES you find tips, recommendations and important information. The notes facilitate
work, provide more informat
ing the correct procedure.
TECHNICAL BASICS
The TECHNICAL BASICS offer technical information, basics
information lead to a better understanding of the device functions for example. The experienced user can skip this information.
ion on specific actions and help to avoid overtime by not follow-
Please read this section carefully. Safety aspects cannot be left to chance when dealing with electrical
equipment.
This manual includes all information necessary for the prescribed use of the BL67-gateways. It has been
specially conceived for personnel with the necessary qualifications.
1.3.1Prescribed use
The devices described in this manual must be used only
the respective technical descriptions, and only with certified components and devices from third party
manufacturers.
Appropriate transport, storage, deployment and mounting as well as careful operating and thorough
maintenance guarantee the trouble-free and safe operation of these devices.
in applications prescribed in this manual or in
1.3.2Notes concerning planning/installation of this product
All respective safety measures and accident protection guidelines must be considered carefully and
without exception.
2.1.2Easy to handle .......................................................................................................................................................................................3
– Power feeding modules.................................................................................................................................................................5
BL67 is a modular I/O system of protection class IP67 for use in industrial automation. It connects the
sensors and actuators in the field with the higher-level master.
BL67 offers modules for practically all applications:
Digital input and output modules
Analog input and output modules
Technology modules (SSI-, RS232-module,...).
A complete BL67 station counts as one station on the bus and therefore occupies one fieldbus address
given fieldbus structure.
in any
A BL67 station consists of a gateway, power distribution modules and I/O modules.
The connection to the relevant fieldbus is made via the bus-specific gateway, which is responsible for
the communication between the BL67 station and the other fieldbus stations.
The communication within the BL67 station between the gateway and the individual BL67 modules is
regulated via an internal module bus.
NOTE
The gateway is the only fieldbus-dependent module on a BL67 station. All other BL67 modules are
A BL67 station can contain modules in any combination, which means it is possible to adapt the system
to practically all applications in automated industry.
2.1.2Easy to handle
All BL67 modules of the standard line, with the exception of the gateway, consist of a base module and
an electronics module.
The gateway and the base modules are either snapped onto a mounting rail or are directly mounted
onto the machine frame. The electronic modules are plugged onto the appropriate base modules.
The electronics modules can be plugged or pulled when the station is being commissioned or for maintenance purposes, without having to disconnect the field wiring from the base modules.
The gateway connects the fieldbus to the I/O modules. It is responsible for handling the entire process
data and generates diagnostic information for the higher-level master and the software tool I/O-ASSISTANT.
The standard electronics modules contain the I/O-functions of the BL67 modules (power distribution
modules, digital and analog input/output modules, and technology modules).
They are plugged onto the base modules and are not directly connected to the wiring and can be
plugged or pulled when the station is being commissioned or for maintenance purposes, without having to disconnect the field wiring from the base modules.
Figure 2-3:
Example of an
electronic module
Power feeding modules
Power Feeding modules distribute the required 24 V DC field voltage to the I/O-modules. They are necessary f
ply voltage for the outputs cannot be guaranteed.
The adjoining power supply module and modules to the left are potentially isolated.
or building groups of modules with different potentials within a BL67 station, or if the rated sup-
2.2.3Base modules
The field wiring is connected to the base modules.
These are available in the following connection variations:
1 × M12, 2 × M12, 2 × M12-P, 4 × M12, 4 × M12-P
4 × M8, 8 × M8
1 × M12-8
1 × M23, 1 × M23-19
NOTE
For detailed information about the individual BL67 I/
ters 2 to 8 of the manual "BL67- I/O-modules" (TURCK Documentation-No.: German D300572;
English: D300529).
The "Appendix" to the manual mentioned above contains (amongst others) a list of all BL67
components and the assignment of electronic modules to base modules.
3.3QuickConnect (QC) and Fast Start-Up (FSU)...................................................................................... 6
3.4Technical data ................................................................................................................................... 7
3.4.4Technical data .......................................................................................................................................................................................9
– Ethernet-connection for QC-/FSU-applications.................................................................................................................13
3.5.2Voltage supply via 7/8"-connector ............................................................................................................................................. 14
– Connection with I/O-ASSISTANT-connection cable......................................................................................................... 15
– Connection using commercially available cables ............................................................................................................. 15
– LED behavior................................................................................................................................................................................... 17
3.6.1Default setting of the gateway..................................................................................................................................................... 18
– Resetting the IP-address, switch position "000" ................................................................................................................ 18
3.6.2Address setting via rotary coding switch (rotary mode).....................................................................................................19
3.6.3Address setting via BootP-mode (300)...................................................................................................................................... 20
3.6.4Address setting via DHCP-mode (400) ...................................................................................................................................... 20
3.6.5Address setting via PGM-mode (500) ........................................................................................................................................21
3.6.6Address setting via the mode PGM-DHCP (universal mode, 600)................................................................................... 22
– Permanent IP-address assignment using the Rockwell BOOTP/DHCP-server........................................................ 22
3.6.7F_Reset (reset to factory settings, 900) ..................................................................................................................................... 22
3.6.8Addressing via I/O-ASSISTANT 3 (FDT/DTM)...........................................................................................................................23
3.6.9Address assignment via Web server (only VN ≥ 03-00) ....................................................................................................... 26
3.7Reset to factory settings ................................................................................................................. 27
3.8.1Safety in the web server.................................................................................................................................................................. 28
– Configuration of the field bus interface ................................................................................................................................34
– Reset to Factory Defaults............................................................................................................................................................34
– Parameterization of the in-/outputs.......................................................................................................................................35
3.8.12Usage of mobile devices .................................................................................................................................................................36
3.9Web server logout........................................................................................................................... 37
3.9.1Deactivating the web server..........................................................................................................................................................37
3.10Status and Control Word of the BL67-stations................................................................................38
3.10.1Status Word .........................................................................................................................................................................................38
– Meaning of the status bits..........................................................................................................................................................38
3.12.1Diagnostic messages via LEDs ......................................................................................................................................................40
The BL67-GW-EN (> VN 03-00) is used as multiprotocol-interface between the BL67-system and the
Ethernet-protocols Modbus TCP, EtherNet/IP™ and PROFINET.
3.1.2Version overview
Please observe, that the previous versions of the gateway did not support all protocols.
Version < VN 03-0
BL67-gateway supports only the Ethernet protocol
–Modbus TCP
Version VN
BL67-gateway supports the Ethernet protocols
–Modbus TCP
0
03-01
– EtherNet/IP™
Version ≥VN
BL67-gateway supports the Ethernet protocols
–Modbus TCP
– EtherNet/IP™
–PROFINET
03-02
NOTE
´The multi protocol Ethernet gateway replaces all previous versions and is completely
compatible.
On
ly the LED-designation has changed. Please find detailed information under Diagnostic
The gateway BL67-GW-EN (VN ≥ 03-00) supports QuickConnect- and Fast Start-Up (see also QuickCon-
nect in BL67 (page 4-4) or PROFINET (page 8-2).
The following table shows the BL67 electronic modules, which are ready for QuickConnect or respectively Fast Start-Up.
Table 3-2:
Modules ready for
QuickConnect or
Fast Start-Up
BL67 modules
ModuleReady for QC/FSU from VN
BL67-4DI-PVN 01-03
BL67-4DI-PD
VN 01-07
BL67-8DI-PVN 01-03
BL67-8DI-PDVN 01-06
BL67-16DI-PVN 01-01
BL67-4DO-0.5A-PVN 01-07
BL67-4DO-2A-PVN 01-07
BL67-4DO-4A-PVN 01-01
BL67-8DO-0.5A-PVN 01-07
BL67-16DO-0.1A-PVN 01-07
BL67-8XSG-PVN 01-01
BL67-8XSG-PDVN 01-06
BL67-4DI4DO-PDVN 01-06
BL67-PF-24VDCVN 01-03
NOTE
The start up behavior of the complete BL67-sta
tion is changed if modules which are not ready
for QC or FSU are used within a station. The start up time of a station is determined by the
slowest module.
In this case, QuickConnect or respectively Fast Start-Up can not be guaranteed.
according to IEC 61000-4-5
0,5 kV CM, 12Ω/9 μF
0,5 kV DM, 2Ω/18 μF
Criteria B
Reliability
Pull/plug cycles of electronic modules20
Housing materialPC-V0 (Lexan)
Size
Width x length x height (mm/inch)64,5 × 145,0 × 77,5/2,54 × 5,71 × 3,05
WARNING!
This device can cause radio disturbances in residential
areas and in small industrial areas (residential, business and trading). In this case, the operator can be required to take appropriate
measures to suppress the disturbance at his own cost.
The female PS/2 connector is used to connect the gateway to the project planning and diagnostic software I/O-ASSISTANT.
The service interface is designed as a 6 pole mini-DIN-connection.
Two types of cables can be used to connect the service interface (female PS/2 connector) to a PC for the
purpose of using I/O-ASSISTANT (project planning and diagnostic software).
special I/O-ASSISTANT-connection cable from TURCK (IOASS
Ident-no.: 6827133)
Commercially available PS/2 cable with adapter cable SUB-D/PS/2
on with I/O-ASSISTANT-connection cable
Figure 3-7:
PS/2 male connector on the connection cable to
the gateway (top
view)
Connecti
The I/O-ASSISTANT-cables have a PS/2 male connector (connection for female connector on gateway)
d a SUB-D female connector (connection for male connector on PC).
an
ISTANT-ADAPTERKABEL-BL20/BL67;
Figure 3-8:
9-pole SUB-D
female connector
on the cable for
connecting to PC
(top view)
Figure 3-9:
PS/2 male connector on the connection cable to
the gateway (top
view)
Connection using commercially available cables
A further possibility to connect PC an
d BL67 gateway is to use a commercially available connection and
adapter cable.
The connection shown in the following figure (PS2-male/PS2-male) is a 6-wire 1:1 connection.
The following two cables are necessary:
1 x PS/2 cable (PS/2 male connector/PS/2 male connector) (commercially available keyboard exten-
sion cable)
1 x adapter cable (PS/2 female connector/SUB-D female connector) (commercially available exten-
sion cable for a PC mouse)
Figure 3-10:
PS/2 female connector on the
gateway (top
view)
The object provides the following control functions:
IP address192.168.1.254
subnet mask 255.255.255.0
default gateway192.168.1.1
NOTE
The stations can be reset by the user to these
To reset the module, set the three coding-switches on the gateway to "000" followed by a
power-on reset.
NOTE
After every change of the address-mode, a v
Resetting the IP-address, switch position "000"
With this setting the DIP-switches to "00
192.168.1.254 for IP-based services (seeDefault setting of the gateway (page 3-18)).
default settings at any time.
oltage reset must be carried done.
0" followed by a voltage reset, the module is set to the address
This setting allows for example the I/O-ASSISTANT 3 (FDT/DTM) to communicate with the station, the
device's WEB-server can be accessed using the IP-address 192.168.1.254.
NOTE
This setting is no operation mode! Please set
the IP address to the default values.
Address setting is carried out by a BootP-server in the network after the start-up of the gateway.
In order to activate the BootP-mode, the rotary coding-switches have to be set to "300".
NOTE
The IP address, as well as the default subnet mask
server, are stored in the module’s EEPROM.
If the gateway is subsequently switched to rotary- or PGM-mode, the settings carried out via
BootP (IP address, subnet mask, etc) will be read from the module’s EEPROM.
3.6.4Address setting via DHCP-mode (400)
Address setting is carried out by a DHCP-server in the network after the start-up of the gateway (see also
Addressing via DHCP (page 12-7).
In order to activate the DHCP-mode, the rotary coding-switches have to be set to "400".
assigned to the gateway by the BootP-
NOTE
The IP address, as well as the default subnet mask
server, are stored in the module’s EEPROM.
If the gateway is subsequently switched to rotary- or PGM-mode, the settings carried out via
BootP (IP address, subnet mask, etc) will be read from the module’s EEPROM.
DHCP supports three mechanisms for IP address allocation:
In "automatic allocation", the
In "dynamic allocation", DHCP assigns an IP address to
time, or until the client explicitly relinquishes the address, the address can be re-assigned.
In "manual allocation", a client's IP address is assign
used simply to convey the assigned address to the client.
PROFINET
Please assure, that in PROFINET-applications, the address assigned
the address, which is assigned in the configuration tool.
DHCP-server assigns a permanent IP address to a client.
3.6.6Address setting via the mode PGM-DHCP (universal mode, 600)
In order to activate the PGM-DHCP-mode, the rotary coding-switches have to be set to "600".
The device sends DHCP-requests until it gets a permanent address.
The DHCP-client in the device is deactivated as soon as the devices gets a permanent address via the I/
O-ASSISTANT V3 (FDT/DTM), the Web-server or the PROFINET-controller.
If the IP-address assignment is done via BOOTP/DHCP-server, the device usually gets a new IP-address
after every start-up (see also Addressing via DHCP (page 12-7)).
Permanent IP-address assignment using the Rockwell BOOTP/DHCP-server
The Rockwell BOOTP/DHCP-server can also be use
For that purpose, deactivate the DHCP-client in the respective device using "Disable BOOTP/DHCP" in
the BOOTP/DHCP-server The device stores the set IP-address even after start-up.
PROFINET
This mode assures a PROFINET-compliant operation of the
d to assign a permanent IP-address.
modules.
3.6.7F_Reset (reset to factory settings, 900)
This mode sets all device-settings back to the default values and deletes all data in the device's internal
flash.
NOTE
This setting is no operation mode! Please set
the IP address to the default values.
The software-tool I/O-ASSISTANT 3 (FDT/DTM) enables direct access to the Ethernet-network via the
Ethernet cable.
The IP address, as well as the subnet mask of the TURCK Ethernet stations, can be changed according
to the application by using the Busaddress Management function of the BL Service Ethernet interface
(TCP/IP) in the software I/O-ASSISTANT 3 (FDT/DTM).
Besides the hardware rest using the rotary coding switches (seeF_Reset (reset to factory settings, 900)
(page 3-22)), the TURCK IP Address Tool as well as the web server (see Reset to Factory Defaults (page
3-34)) offer the possibility to reset the devices to the factory settings.
Figure 3-17:
IP Address Tool,
reset to factory
settings
The page "Ethernet Statistics" shows information like the port-status, telegram and error counters etc.
The page can above all be useful for analyzing network problems.
Figure 3-21:
Ethernet Statistics
D300815 0215- BL67 multiprotocol3-30
Page 51
Web server - remote access/configuration (only VN ≥ 03-00)
This page contains for example a link to the product page on the TURCK-homepage.
3.8.7Login/password
In order to obtain administrator rights and thus full access to the extended functions of the web server
(Network Configuration, Station Configuration, etc.), you have to log-on to the web server as administrator.
For the first login use the default password "password".
The default-password should be changed by the administrator. To do so, please follow the instructions
under Change Admin Password (page 3-32).
e device has accepted the new settings, the settings are active
Th
NOTE
"Reset" only resets the changes done in the web ser
function does not influence the device itself.
3.8.12Usage of mobile devices
The internal web server has a responsive design. This means, the web functions can also be executed
using a mobile device, e.g. a smartphone.
The web content is automatically adapted to the smaller display in order to assure an optimized web
server representation.
The BL67-gateway and the mobile device have to be nodes of the same network. Please assure therefore that the IP addresses of both devices are part of the same subnet (e.g. 255.255.255.0).
In addition to that, a WLAN access has to be available for the mobile device.
ver mask back to the original values. The
Figure 3-27:
Access to the web
server via smartphone
3.8.13Web server logout
In order to disconnect a logged in user/PC with administrator rights from the web server, a logout is
necessary.
If only the web browser is closed, the last active access is reactivated when opening the web server
again from the same PC, which means, possibly with all administrator rights.
D300815 0215- BL67 multiprotocol3-36
Page 57
Web server - remote access/configuration (only VN ≥ 03-00)
If, for safety reasons, the web server has to be
the protocol specific mechanisms (Modbus TCP: parameter registers, seepage 6-8/
EtherNet/IP™: Class Instance Attribute, see page 4-26/PROFINET: GSDML configuration, see
page 8-15) as well as via the web server itself (see page 3-34).
If the web server is deactivated using the web server itself, further access to it is only possible
following a device reset to the factory settings (see page 3-22).
The SET-button at the gateway serves to take-over the Current Configuration of the BL67-station as
Required Configuration to the gateway’s non-volatile memory.
Please press the button for approx. 10 seconds in order to store the Current Configuration as Required
Configuration (reference configuration).
NOTE
Storing the Current Configuration via
Modbus TCP. In PROFINET, the Required Configuration is defined by the master.
SET-Taster is necessary in EtherNet/IP™ as well as for
4.1.1Communications Profile for BL67...................................................................................................................................................3
4.2.2QuickConnect in BL67 ........................................................................................................................................................................4
– QuickConnect via Configuration Assembly............................................................................................................................5
– Quick Connect via Class Instance Attribute............................................................................................................................5
– QuickConnect via web server ......................................................................................................................................................5
4.3Device Level Ring (DLR) .................................................................................................................... 6
4.4Diagnostic messages via the process data........................................................................................ 7
4.5Classes and Instances of the EtherNet/IP™ stations .......................................................................... 8
4.5.1EtherNet/IP™ Standard Classes .......................................................................................................................................................8
– Process data instances ................................................................................................................................................................ 12
– Mapping of process data............................................................................................................................................................ 13
4.6VSC-Vendor Specific Classes ........................................................................................................... 23
4.6.1Class instance of the VSC................................................................................................................................................................ 23
4.6.2Gateway Class (VSC 100, 64h)....................................................................................................................................................... 24
– Class instance ................................................................................................................................................................................. 24
4.6.3Process Data Class (VSC102, 66h) ................................................................................................................................................ 27
– Class instance ................................................................................................................................................................................. 27
– Object instance 1, standard output process data (compressed) ................................................................................ 27
EtherNet/IP™ is based on a connection-oriented communi
only possible to exchange data via specified connections assigned to the devices.
Communication between the nodes in the EtherNet/IP™ network can be carried out either via
I/O Messages or Explicit Messages.
I/O Messages
I/O Messages serve to exchange high priority pr
Communication between the slaves in the EtherNet/IP™ network is carried out according to
the Server/Client Model,
which means a producing application transmits data to another or a number of consuming
applications. It is quite possible that information is passed to a number of Application Objects
in a single device.
Explicit Messages
Explicit Messages are used to tra
data or diagnostic data between two specific devices. This is a point-to-point connection in a
Server/Client System that requires a request from a client always to be confirmed by a
response from the server.
– Message Router Request
Consists of a service code, path size value, a message router path and service data. An
EPATH is used in the message router path to indicate the target object.
– Message Router Response
Consists of a service field with the most significant bit set. This is an echo of the service
code in the request message with the most significant bit set. A reserved byte follows the
service code, which is followed by the General Status code.
cation model. This means that it is
ocess and application data over the network.
nsmit low-priority configuration data, general management
BL67 behaves as an EtherNet/IP™ Server in the network; the scanner of the higher-level controller operates as a EtherNet/IP™ Client.
The following EtherNet/IP™ communications types are supported:
Unicast
Multicast
Cyclic Connection
Unconnected (UCMM) Explicit Messaging
Connected Explicit Messaging
TECHNICAL BASICS
Unicast
A po
int-to-point connection that exists between two nodes only.
Multicast
A packet with a special destination address, wh
willing to receive.
ich multiple nodes on the network may be
COS I/O Connection
COS (Change Of State) I/O Connections establish event-controlled connections. This means
at the EtherNet/IP™ devices generate messages as soon as a change of status occurs.
th
Cyclic I/O Connection
Messages are triggered time-control
tor.
UCMM
The EtherNet/IP™ gateway offers th
port (Unconnected Message Manager Port).
UCMM-based explicit messaging is normally used for random, non-periodic requests.
It is not recommended for frequent messaging because the UCMM input queue in a product
is typically limited to just a few messages. Once this limit is reached, subsequent requests are
ignored and must be retried.
Connected Explicit Messaging
CIP is a connection-based syste
used.
A connection is a path or a virtual circuit between two or more end points in a system. The
purpose is to transfer data in the most efficient manner possible.
The Connection ID is a number that is associated with a communication relationship. Receiving nodes decode this key to know whether they must accept the data or not.
led in Cyclic I/O connections by means of a time genera-
e option of establishing explicit messaging via the UCMM
m. For most communications between nodes, a connection is
QuickConnect enables a PLC to build up connections to EtherNet/IP™ devices in less than 300 ms after
switching-on the power supply for the EtherNet/IP™ network. This fast start up of devices is above all
necessary for robotic tool changes for example in the automobile industry.
NOTE
Please read Et
the correct Ethernet-cabling in QC-applications with BL67,
4.2.2QuickConnect in BL67
The TURCK BL67-gateway BL67-GW-EN (VN ≥ 03-00) supports QuickConnect.
QuickConnect is activated:
hernet-connection for QC-/FSU-applications (page 3-13) for information about
via the configuration data in the PLC-program per
Assembly Class
(see also chapter 5.5, Activating QuickConnect (page 5-15))
The Device Level Ring (DLR)-redundancy protocol is used to increase the sta
EtherNet/IP™ networks.
DLR-capable products provide an integrated switch and can thus be integrated into a ring
topology.
The DLR-protocol is used to recognize a ring fault. In case of an interruption of the data line,
data are sent through an alternative network section, so that the network can be reconfigured
as soon as possible.
DLR-capable network nodes are provided with extended diagnostic functions which enable
the devices to localize errors and thus decrease the time for error search and maintenance.
Besides the evaluation of diagnostic data via Explicit Messages, BL67 with EtherNet/IP™ offers the
possibility of mapping diagnostic data into the process data (see also the process data mappings (page
4-13 ff.).
2 different forms of diagnostic data handling are provided:
Summarized diagnostics
Scheduled Diagnostics
4.4.1Summarized Diagnostics
The summarized diagnostic data mode will send back 1 bit for each slice within the station.
This bit will be "0" if there are no diagnostic flags set on the slice. If there are any diagnostic events on
the device, the bit will be set to "1".
The diagnostic bits are placed at the end of the input data. The diagnostic data start WORD aligned (see
page 4-13).
Bit "I/O Diag Warn"
0 = OK, no diagnostics present
= at least one module sends diagnostics (acc. to VSC 100, Gateway Class, Attr. 116, page 4-24)
1
4.4.2Scheduled Diagnostics
If scheduled diagnostics is activated (Process Data Class (VSC102, 66h) (page 4-27)), the manufacturer
specific diagnostic bits are mapped into the station's process data(page 4-7 ff.).
The scheduled diagnostic data is placed at the end of the input data and after the summarized
diagnostic data (see page 4-13).
The scheduled diagnostic data is a time sliced module related data block, which holds diagnostic data
of all modules with active diagnostics using a round robin mechanism.
This diagnostic "window" visualizes a specific module diagnostic data for approx. 125 ms and changes
over to the next active diagnostics afterwards. This is done automatically by the gateway.
The data length for the scheduled diagnostics is set according to properties of the modules attached to
the gateway.
Word ByteData
00Slot-no. of the module which sends an emergency-frame.
1
Status of diagnostic message:
bit 5 = 1: diagnostic active
bit 6 = 1: wrong module
bit 7 = 1 Module pulled
(acc. to VSC 100, Gateway Class, Attr. 116, page 4-24)
nModule diagnostics from the module actually referenced by the round-
The following description of the Ethernet Link Object is taken from the CIP specification, Vol. 2, Rev. 2.1
by ODVA & ControlNet International Ltd. and adapted to BL67.
Class attributes
Table 4-2:
Class attributes
Table 4-3:
Instance attribute, obje
ct
instance 1
Attr. No.
1 (0×01)
2 (0×02)
6 (0×06)
7 (0×07)
Object insta
Attr. No.
1 (0×01)
2 (0×02)
3 (0×03)
Attribute nameGet/
TypeValue
Set
REVISIONGUINT1
MAX OBJECT INSTANCEGUINT1
MAX CLASS ATTRIBUTEGUINT7
MAX INSTANCE ATTRIBUTEGUINT7
nce 1 - instance attribute
Attribute nameGet/
TypeDescription
Set
VENDORGUINTContains the vendor ID.
TURCK = 48
PRODUCT TYPEGUINTIndicates the general type of product.
Communications Adapter
= 0×0C
12
dec
PRODUCT CODEGUINTIdentifies a particular product within a device
type.
Default: 27247
dec =
6A6F
4 (0×04)
5 (0×05)
6 (0×06)
7 (0×07)
REVISION
Major Minor
GSTRUCT
OF:
USINT
USINT
Revision of the item the Identity Object is
representing.
0×01
0×06
DEVICE STATUSGWORDsee Table 4-4:Device Status
SERIAL NUMBERGUDINTContains the ident-no. of the product (3 last
→ The application of the device has been configured
(≠ default-settings).
reserveddefault = 0
Extended Device
Status
reserveddefault = 0
ClassInstanceService name
yesyesGet_Attribute_All
noyesReset
0011 = no I/O connection established
0110 = At least one I/O connection in run mode
0111 = At least one I/O connection established, all in IDLE
mode
All other settings = reserved
Returns a predefined list of the object‘s attributes.
Starts the reset service for the device.
14 (0×0E)
yesyesGet_Attribute_Single
Returns the contents of a specified attribute.
D300815 0215- BL67 multiprotocol4-10
Page 75
Classes and Instances of the EtherNet/IP™ stations
Assembly Objects bind attributes of multiple objects to allow data to or from each object to be sent or
received over a single connection.
The following description of the Ethernet Link Object is taken from the CIP specification, Vol. 2, Rev. 2.1
by ODVA & ControlNet International Ltd. and adapted to BL67.
The process data of successive modules of the same type, with process data of less than 1 word, are
grouped together until 16 bits of process data is reached.
The process data is written in a new word when:
16-bit input data is reached and further
16-bit output data is reached and fu
An input module, whose process data length cannot be completely incorporated in the preceding
rd, follows on from another input module
wo
An output module, whose process data length cannot be completely incorporated in the preceding
rd, follows on from another output module 16-bit input data is reached and further input
wo
modules follow
Produced D
(word no.)
0Status Word of the gateway
1 to n Input data of modules
ata
rther output modules follow
Eingangsdaten
Mapping can be disabled using attr. 138 in VSC100, object instance
2, page 4-24)
An example mapping can be found in chapter 5.3, I/O data
mapping (page 5-10).
depicted in WORD-format (16 bit).
input modules follow
n + xSummarized diagnostic data (page 4-7) of individual length (1 bit
per module which sends diagnostics).
Can be enabled/disabled using VSC102, Object instance 3, attr.
104, page 4-27 ff.
(x = the no. of following bytes depending on the no. of slices within
the station)
n + yScheduled diagnostic data (page 4-7). Can be enabled/disabled
using VSC102, Object instance 3, attr. 105, page 4-27 ff.
(y = data length for the scheduled diagnostics set according to the
properties of the modules attached to the gateway)
Consumed Data
ord no.)
(w
0Control word of the gateway. The mapping can be disabled using
1- nOutput data of modules
Note
The data mapping can be structured individually. All parts ex
of the station can be enabled/disabled independently from each other.
Ausgangsdaten
attribute 139 "GW CONTROL REGISTER" in the Gateway Class (VSC
100), object instance 2 (see page 4-26).
An example mapping can be found in chapter 5, I/O data mapping
The following description of the Ethernet Link Object is taken from the CIP specification, Vol. 2, Rev. 1.1
by ODVA & ControlNet International Ltd. and adapted to BL67.
Class attributes
Table 4-10:
Class attributes
Table 4-11:
Instance attri-
object
bute,
instance 1
Attr. No.
1 (0×01)
2 (0×02)
3 (0×03)
Object insta
Attr. No.
1 (0×01)
2 (0×02)
3 (0×03)
4 (0×04)
Attribute nameGet/
Set
REVISIONGUINT1
MAX OBJECT INSTANCEGUINT1
NUMBER OF INSTANCESGUINT1
nce 1: Instance attribute
Attribute nameGet/
STATUS GDWORDInterface status (see page 4-15, Table 4-13:
CONFIGURATION
CAPABILITY
CONFIGURATION
CONTROL
PHYSICAL LINK
OBJECT
TypeDescription
Set
Interface Status)
GDWORDInterface Capability Flag (see page 4-15, Table
4-14:Configuration Capability)
G/SDWORDInterface Control Flag (see page 4-16, Table 4-
15:Configuration Control)
GSTRUCT
TypeValue
5 (0×05)
6 (0×06)
Path sizeUINTNumber of 16 bit words: 0×02
Path:Padded
EPATH
INTERFACE
CONFIGURATION
IP addressGUDINTActual IP address
NETWORK MASKGUDINTCurrent network mask
GATEWAY ADDR.GUDINTActual default gateway
NAME SERVERGUDINT0 = no name server address configured
NAME SERVER 2GUDINT0 = no secondary name server address config-
DOMAIN NAMEGUDINT0 = no Domain Name configured
HOST NAMEGSTRING0 = no Host Name configured (see page 4-16)
GStructure
of:
0×20, 0×F6, 0×24, 0×01
TCP/IP Network Interface Configuration (see
page 4-16)
ured
D300815 0215- BL67 multiprotocol4-14
Page 79
Classes and Instances of the EtherNet/IP™ stations
tus attribute indicates the status of the TCP/IP network interface.
a description of object states as they relate to the Status attribute.
TypeDescription
Set
G/SSTRUCT
of:
0 = deactivated
1 = activated
If ACD is activated, attribute 11 (0×0B) contains
the return value.
Contains information about the last detected
conflict, ACD diagnostics parameter
1 = activate
Table 4-13:
Interface Status
Table 4-14:
Configuration
ability
Cap
Bit(s)
0-3
4 to 31
Configuration Capability
Bit(s)
0
1
2
NameDefinition
Interface Configuration
Status
reserved
The Configuration Capability indicates the
capability.
NameDefinitionvalue
BOOTP ClientThe device is capable of obtaining its
DNS ClientThe device is capable of resolving host
DHCP ClientThe device is capable of obtaining its
Indicates the status of the Interface Configuration attribute:
0 = The Interface Configuration attribute has not been configured
1 = The Interface Configuration attribute contains valid configuration.
2 to 15: reserved
device’s support for optional network configuration
e Configuration Control attribute is used to control network configuration options.
Th
Table 4-15:
Configuration
Control
Bit(s)
0-3
4
5-31
Interface Configuration
NameDefinition
Startup
Configuration
DNS EnableAlways 0.
reservedSet to 0.
This attribute
To modify the Interface Configuration attribute, get the Interface Configuration attribute first,
change the desired parameters, then set the attribute.
The TCP/IP Interface Object applies the new configuration upon completion of the Set service. If the
value of the Startup Configuration bits (Configuration Control attribute) is 0, the new configuration
is stored in non-volatile memory.
The device does not reply to the set service until the values are safely stored to non-volatile memory.
An attempt to set any of the components of the Interface Configuration attribute to invalid values
results in an error (status code 0×09) returned from the Set service.
If initial configuration is obtained via BOOTP or DHCP, the Interface Configuration attribute
components are all 0 until the BOOTP or DHCP reply is received.
Upon receipt of the BOOTP or DHCP reply, the Interface Configuration attribute shows the
configuration obtained via BOOTP/DHCP.
contains the configuration parameters required to operate as a TCP/IP node.
Determines how the device shall obtain its initial configuration
at
0 = The device shall use the interface configuration values
previously stored (for example, in non-volatile memory or via
hardware switches, etc).
1 to 3: reserved
Host Name
Host Name attribute contains the device’s host name.
The
The host name attribute is used when the device supports the DHCP-DNS Update capability and has
been configured to use DHCP upon start up.
The mechanism allows the DHCP client to transmit its host name to the DHCP server. The DHCP
server then updates the DNS records on behalf of the client.
D300815 0215- BL67 multiprotocol4-16
Page 81
Classes and Instances of the EtherNet/IP™ stations
The following description of the Ethernet Link Object is taken from the CIP specification, Vol. 2, Rev. 1.1
by ODVA & ControlNet International Ltd. and adapted to BL67.
Class attributes
Table 4-16:
Class attributes
Table 4-17:
Instance attribute
Attr. No.
1 (0×01)
2 (0×02)
3 (0×03)
stance attributes (instance 1 = port 1/instance 2 = port 2)
2 to 4Negotiation StatusIndicates the status of the automatic
5
6
NameDefinitionDefault value
duplex detection (Autonegotiation)
0 = Autonegotiation in progress
1 = Autonegotiation and speed detection
failed.
Using default values for speed and duplex
(10 Mbps/half duplex).
2 = Auto negotiation failed but detected
speed (default: half duplex). Half duplex
3 = Successfully negotiated speed and
duplex.
4 = Auto-negotiation not attempted.
Forced speed and duplex.
Manual Setting
Requires Reset
Local Hardware Fault 0 = interface detects no local hardware
0 = interface can activate changes to link
parameters (auto-negotiate, duplex mode,
interface speed) automatically
1 = device requires a Reset service to be
issued to its Identity Object in order to
adapt the changes
1Forced Duplex ModeIf bit "Auto-negotiate" is 0, bit "Forced
2-15
Forced Interface Speed
If the Auto-negotiate bit is 0, the "F
shall operate. Speed is specified in megabits per second (e.g., for 10 Mbps Ethernet, the Interface Speed
shall be 10).
Interfaces not supporting the requested speed should return a error code 0×09 (Invalid Attribute
Value).
NameDefinitionDefault value
Auto-negotiate0 = Autonegotiation deactivated
1 = Autonegotiation activated
Depends on appliDuplex Mode" shows if the interface
should work in Full or Half Duplex-mode.
0 = Half Duplex
1 = Full Duplex
Interfaces which do not support the
selected duplex-mode, send an error code
0×09 (Invalid Attribute Value).
If auto-negotiation is enabled, attempting
to set the Forced Duplex Mode bits shall
result in a error code 0×0C (Object State
Conflict).
reserved
orced Interface Speed" bits indicate the speed at which the interface
cation
Table 4-20:
Common
rvices
Se
If auto-negotiation is enabled, attempting to set the Forced Interface Speed bits shall result in a error
code 0×0C (Object State Conflict).
Common Services
Service code
14 (0×0E)
16 (0×10)
ClassInstanceService name
yesyesGet_Attribute_Single
no yesSet_Attribute_Single
D300815 0215- BL67 multiprotocol4-20
Page 85
Classes and Instances of the EtherNet/IP™ stations
Quality of Service (QoS) is used for prioritizing or parameterizing of the data transmission of a device.
Each change is only accepted after a power-cycle of the device.
The DSCP-value is part of the EtherNet/IP™ data telegram and is used to define data priorities in data
handling.
Instance attribute
Table 4-24:
Instance attribute
Table 4-25:
Common
rvices
Se
Attr. No.
4 (0×04)
5 (0×05)
6 (0×06)
07 (0×07)
08 (0×08)
Common
Service code
14 (0×0E)
16 (0×10)
Services
Attribute nameGet/
DSCP UrgentSUSINTDSCP value for CIP transport class 0/1 Urgent
DSCP ScheduledSUSINTDSCP value for CIP transport class 0/1 Sched-
DSCP High SUSINTDSCP value for CIP transport class 0/1 High
DSCP LowSUSINTDSCP value for CIP transport class 0/1 Low
DSCP ExplicitSUSINTDSCP value for CIP explicit messages (trans-
This class contains all information which refers to the whole station not to the different
I/O channels.
Class instance
NOTE
Please refer to paragraph C
instance for the VSC.
ject Instance 1
Ob
lass instance of the VSC (page 4-23) for the description of the class
Table 4-28:
Object Instance
1
Boot instance
Attr. No.
dec.
ex.)
(h
100
(64h)
101
(65h)
102
(66h)
103
(67h)
104
(68h)
Attribute name
MAX INSTANCE
ATTRIBUTE
Hardware revision GSTRUCT Contains the hardware revision number of the
Firmware revisionGSTRUCT Contains the firmware revision of the boot
Service tool ident
number
Hardware
info
Get/
TypeDescription
Set
GUSINT Contains the number of the last object attri-
bute to be implemented.
station (USINT Maj./USINT Min.)
firmware (maj./min.).
GUDINT Contains the BOOT ID number that serves as
an identification number for the software I/OASSISTANT
GSTRUCT Contains station hardware information (UINT):
– count (number of the following entries)
– CLOCK FREQUENCY (kHz)
– MAIN FLASH (in kB)
– MAIN FLASH SPEED (ns)
–SECOND FLASH (kB)
–RAM (kB),
– RAM SPEED (ns),
– RAM data WIDTH (bit),
– SERIAL EEPRPOM (kbit)
– RTC SUPPORT (in #)
– AUTO SERVICE BSL SUPPORT (BOOL)
–HDW SYSTEM
Status register 2GSTRUCT The Status Word contains general station
status information,
Station
– Bit 15: reserved
Bit 14: "Force Mode Active Error" The Force
–
Mode is activated.
– Bit 13: reserved
– Bit 12: reserved
Internal bus
– Bit 11: "I/O Cfg Modified Error"
e configuration has been changed in an
Th
incompatible way.
– Bit 10: "I/O Communication Lost Error"
Communication on the internal module bus
disturbed.
Voltage errors
–Bit 09: "U
too low" System voltage (VI) too
sys
low (< 18 VDC).
–Bit 08: "U
too high" System voltage (VI) too
sys
high (< 30 VDC).
–Bit 07: "U
too low" Load voltage (VO) too low
L
(< 18 VDC).
– Bit 06: reserved
– Bit 05: reserved
– Bit 04: reserved
Warnings
– Bit 03: "I/O Cfg Modified Warning" The station
nfiguration has changed.
co
– Bit 02: reserved
– Bit 01: reserved
– Bit 00: "I/O Diags Active W arning" At leas t one
I/O-channel sends active diagnostics.
115
(73h)
ON IO
CONNECTION
TIMEOUT
G/SENUM
USINT
Reaction to the I/O connection exceeding the
time limit.
SWITCH IO FAULTED (0):
The modules are switched to Faulted State.
SWITCH IO OFF (1):
The gateway switches off the outputs of the
modules.
SWITCH IO HOLD (2):
No further changes to the I/O-data. The
outputs are held.
138
(0×8A)
GW Status
Register
Get/
DWORDAllows to enable/disable the status register
Set
which is part of the input data.
0 = deactivated
1 = activated (default)
G/SBOOL0 = disabled
manufacturer
specific diagnostics (scheduled
diagnostics)
Attribute name
Get/
Set
TypeDescription
1 = yes
1 bit of diagnosis mapped at the end of the
input data image (page 4-7).
Changes become valid after a start-up!
1 = yes
The channel-specific diagnostic bits are
mapped into the process input data (see
page 4-7).
Changes become valid after a start-up!
104 (68h)COS data
mapping
G/SENUM
USINT
The actual data are loaded to the non-volatile memory of the station.
Changes become valid after a start-up!
0 = standard: Data of COS message
→ input data.
1 = process input data (only the process
data input image is transferred to scanner)
2 to 7: reserved
5.2.1Configuration of the network in "RS Logix 5000".....................................................................................................................3
– Configuration of the controller ...................................................................................................................................................3
– Configuration of the EtherNet/IP™ Bridge ..............................................................................................................................4
– Configuring the BL67-station ......................................................................................................................................................5
5.2.2Downloading the I/O configuration..............................................................................................................................................8
5.3I/O data mapping ............................................................................................................................ 10
5.4Process data access ......................................................................................................................... 12
BL67-stations are delivered in the address-mode "PGM-DHCP" and can be reached using IP-address
192.168.1.254.
NOTE
In order to build up the communica
interface card, both devices have to be hosts in the same network.
achieve this, you have either:
To
to adjust the gateway‘s IP address via BootP, DHCP etc. for integrating it into your own network (for
detailed information about the different possibilities for address setting, please read chapter 3.6,
Address assignment (page 3-17),.
or
to change the IP address of the used PC or network interface card (for detailed information, please
read Changing the IP address of a PC/ network interface card (page 12-2).
tion between the BL67-station and a PLC/ PC or a network
5.2.1Configuration of the network in "RS Logix 5000"
The EtherNet/IP™ hosts (PLC, EtherNet/IP™ interface, I/O stations) have to be configured using the
software "RSLogix 5000" (in this example version 15) from Rockwell Automation.
Start RS Logix and open a new project using the "File" menu.
Configuration of the controller
er the information related to the controller depending on your configuration, as well as a name
1 Ent
for the project.
Figure 5-1:
Configuration
of the controller
2 Your project will be opened offline.
D300815 0215- BL67 multiprotocol
5-3
Page 98
Application example: BL67-GW-EN with EtherNet/IP™ (Allen Bradley)
If the variable Assembly Instances 103 and 104 (see page 4-11)
Parameters have to be set according to the actual station configuration.
This means:
The in- and output sizes have to match the sizes definitely required by the station.
This required in- and output size can be determined as follows:
Create a station report for the station using the TURCK DTMs for BLxx (see also Figure 5-6:Eth-
erNet/IP™ report (PLC configuration) (page 5-6))
OR
Read out the correct size of in- and output data via Assembly Class (0×04), Instance
0×04 and Assembly Class (0×04), Instance 0×68, Attr. 0×04.