turck BL20-GW-CANOPEN, BL20-GWBR-CANOPEN User Manual

Page 1
BL20 –
USER MANUAL FOR CANopen
Page 2
All brand and product names are trademarks or registered trade marks of the owner concerned.
© Hans Tu
All rights reserved, including those of the translation.
No part of this manual may be reproduced in any form (printed, photocopy, microfilm or any other process) or processed, duplicated or distributed by means of electronic systems without written permission of Hans Turck GmbH & Co. KG, Muelheim an der Ruhr.
Subject to alterations without notice
11
rck GmbH, Muelheim an der Ruhr
Page 3
Safety Notes!
Before starting the installation
Disconnect the power supply of the device.
Ensure that devices cannot be accidentally restarted.
Verify isolation from the supply.
Earth and short circuit.
Cover or enclose neighboring units that are live.
Follow the engineering instructions (AWA) of the device concerned.
Only suitably qualified personnel in accordance with EN 50 110-1/-2 (VDE 0 105 Part 100) may
work on this device/system.
Before installation and before touching the device ensure that you are free of electrostatic
charge.
The functional earth (FE) must be connected to the protective earth (PE) or to the potential equa-
lization. The system installer is responsible for implementing this connection.
Connecting cables and signal lines should be installed so that inductive or capacitive interfe-
rence do not impair the automation functions.
Install automation devices and related operating elements in such a way that they are well
protected against unintentional operation.
Suitable safety hardware and software measures should be implemented for the I/O interface so
that a line or wire breakage on the signal side does not result in undefined states in the automa­tion devices.
Ensure a reliable electrical isolation of the low voltage for the 24 volt supply. Only use power
supply units complying with IEC 60 364-4-41 (VDE 0 100 Part 410) or HD 384.4.41 S2.
Deviations of the mains voltage from the rated value must not exceed the tolerance limits given
in the specifications, otherwise this may cause malfunction and dangerous operation.
Emergency stop devices complying with IEC/EN 60 204-1 must be effective in all operating
modes of the automation devices. Unlatching the emergency-stop devices must not cause restart.
Devices that are designed for mounting in housings or control cabinets must only be operated
and controlled after they have been installed with the housing closed. Desktop or portable units must only be operated and controlled in enclosed housings.
Measures should be taken to ensure the proper restart of programs interrupted after a voltage
dip or failure. This should not cause dangerous operating states even for a short time. If neces­sary, emergency-stop devices should be implemented.
Wherever faults in the automation system may cause damage to persons or property, external
measures must be implemented to ensure a safe operating state in the event of a fault or malfunction (for example, by means of separate limit switches, mechanical interlocks etc.).
The electrical installation must be carried out in accordance with the relevant regulations (e. g.
with regard to cable cross sections, fuses, PE).
All work relating to transport, installation, commissioning and maintenance must only be carried
out by qualified personnel. (IEC 60 364 and HD 384 and national work safety regulations).
All shrouds and doors must be kept closed during operation.
Page 4
Page 5
Table of Contents
1 About this Manual
1.1 Documentation Concept.................................................................................................................................1-2
1.2 Description of Symbols Used..........................................................................................................................1-3
1.3 Overview ..........................................................................................................................................................1-4
1.3.1 Prescribed Use .........................................................................................................................................................................................1-4
1.3.2 Notes Concerning Planning /Installation of this Product ........................................................................................................1-4
1.4 List of Revisions ...............................................................................................................................................1-5
2 BL20 Philosophy
2.1 The Basic Concept............................................................................................................................................2-2
2.2 BL20 Components ...........................................................................................................................................2-3
2.2.1 Gateways ...................................................................................................................................................................................................2-3
2.2.2 Power Distribution Modules .............................................................................................................................................................. 2-3
2.2.3 Electronics Modules ..............................................................................................................................................................................2-4
2.2.4 Base Modules ...........................................................................................................................................................................................2-5
2.2.5 End Plate....................................................................................................................................................................................................2-7
2.2.6 End Bracket...............................................................................................................................................................................................2-7
2.2.7 Jumpers...................................................................................................................................................................................................... 2-8
2.2.8 Marking Material.....................................................................................................................................................................................2-8
2.2.9 Shield Connection, 2-Pole for Analog Modules ..........................................................................................................................2-9
3 Short description of CANopen
3.1 CANopen ..........................................................................................................................................................3-2
3.1.1 General .......................................................................................................................................................................................................3-2
3.1.2 Communication ...................................................................................................................................................................................... 3-3
3.2 BL20 and CANopen..........................................................................................................................................3-5
3.3 Electronic data sheet – EDS file ......................................................................................................................3-6
4 BL20 - Gateway for CANopen
4.1 Introduction .....................................................................................................................................................4-2
4.2 Function ...........................................................................................................................................................4-3
4.3 Technical Information .....................................................................................................................................4-4
4.4 Technical Data .................................................................................................................................................4-5
4.4.1 General Technical Data ........................................................................................................................................................................4-5
4.4.2 Structure Diagram of a Gateway.......................................................................................................................................................4-8
4.4.3 Technical Data BL20-GW-CANOPEN................................................................................................................................................4-8
4.4.4 Technical Data BL20-GWBR-CANOPEN ..........................................................................................................................................4-9
4.5 Connections for data cables to BL20-GW-CANOPEN ................................................................................. 4-10
4.5.1 Fieldbus connection via SUB-D socket ........................................................................................................................................ 4-10
4.5.2 Fieldbus connection through direct wiring............................................................................................................................... 4-10
4.6 Connections of the data cables to BL20-GWBR-CANopen ........................................................................ 4-12
4.6.1 Fieldbus connection via Open Style connector ....................................................................................................................... 4-12
D301087 1211 - BL20 CANopen
i
Page 6
4.6.2 Service Interface Connection ..........................................................................................................................................................4-14
4.7 Setting the bit transfer rate through DIP-switches.................................................................................... 4-15
4.8 Node-ID Setting ............................................................................................................................................ 4-17
4.9 Acceptance of the BL20 Station Configuration .......................................................................................... 4-19
4.10 Status Indicators/ Diagnostic Messages Gateway ..................................................................................... 4-20
4.10.1 Diagnostic Messages via LEDs ........................................................................................................................................................4-20
5 BL20 - Communication in CANopen
6 Guidelines for Station Planning
6.1 Random Module Arrangement ...................................................................................................................... 6-2
6.1.1 Complete Planning ............................................................................................................................................................................... 6-2
6.1.2 Maximum System Extension ............................................................................................................................................................. 6-2
6.2 Power Supply .................................................................................................................................................. 6-4
6.2.1 Gateway Supply...................................................................................................................................................................................... 6-4
6.2.2 Module Bus Refreshing ........................................................................................................................................................................ 6-4
6.2.3 Creating Potential Groups .................................................................................................................................................................. 6-8
6.2.4 Protecting the Service Interface on the Gateway ...................................................................................................................... 6-8
6.2.5 C-Rail (Cross Connection).................................................................................................................................................................... 6-9
6.2.6 Direct Wiring of Relay Modules ...................................................................................................................................................... 6-10
6.3 Plugging and Pulling Electronics Modules ................................................................................................. 6-11
6.4 Extending an Existing Station...................................................................................................................... 6-12
6.5 Firmware Download ..................................................................................................................................... 6-13
7 Guidelines for Electrical Installation
7.1 General Notes.................................................................................................................................................. 7-2
7.1.1 General ...................................................................................................................................................................................................... 7-2
7.1.2 Cable Routing.......................................................................................................................................................................................... 7-2
7.1.3 Cable Routing Inside and Outside of Cabinets: .......................................................................................................................... 7-2
7.1.4 Lightning Protection ............................................................................................................................................................................ 7-3
7.1.5 Transmission Cables ............................................................................................................................................................................. 7-3
7.1.6 Cable Types .............................................................................................................................................................................................. 7-3
7.2 Potential Relationships .................................................................................................................................. 7-4
7.2.1 General ...................................................................................................................................................................................................... 7-4
7.2.2 Potential-Free Installation .................................................................................................................................................................. 7-4
7.2.3 Non-isolated Installation ..................................................................................................................................................................... 7-4
7.3 Electromagnetic Compatibility (EMC) ........................................................................................................... 7-5
7.3.1 Ensuring Electromagnetic Compatibility ...................................................................................................................................... 7-5
7.3.2 Grounding of Inactive Metal Components................................................................................................................................... 7-5
7.3.3 PE Connection......................................................................................................................................................................................... 7-5
7.3.4 Earth-Free Operation ............................................................................................................................................................................ 7-5
7.3.5 Mounting Rails ........................................................................................................................................................................................ 7-6
7.3.6 EMC Compliant Cabinet Installation ............................................................................................................................................... 7-7
7.4 Shielding of cables.......................................................................................................................................... 7-8
7.5 Potential Compensation ................................................................................................................................ 7-9
D301087 1211 - BL20 CANopenii
Page 7
7.5.1 Switching Inductive Loads ............................................................................................................................................................... 7-10
7.5.2 Protection against Electrostatic Discharge (ESD) .................................................................................................................... 7-10
7.6 Bus Connection............................................................................................................................................. 7-11
7.7 Two-Pole Shield Connection........................................................................................................................ 7-12
8 BL20-Approvals for Zone 2/ Division 2
9Glossary
10 Index
D301087 1211 - BL20 CANopen
iii
Page 8
D301087 1211 - BL20 CANopeniv
Page 9

1 About this Manual

1.1 Documentation Concept ................................................................................................................... 2
1.2 Description of Symbols Used ............................................................................................................ 3
1.3 Overview ........................................................................................................................................... 4
1.3.1 Prescribed Use............. ....................................... ... ... ... .... ... ....................................... . .........................4
1.3.2 Notes Concerning Planning /Installation of this Product......................................................................4
1.4 List of Revisions ................................................................................................................................ 5
D301087 1211 - BL20 CANopen 1-1
Page 10
About this Manual

1.1 Documentation Concept

This manual contains all information about the BL20-gateway for CANopen (BL20-GW-CANOPEN, BL20-GWBR-CANOPEN).
The following chapters contain a short BL20 system description, a description of the field bus system CANopen, exact information about function and structure of the BL20 CANopen-gateway as well as all bus-specific information concerning the connection to automation devices, the maximum system extension etc.
The bus-independent I/O-modules for BL20 as well as all further fieldbus-independent chapters like mounting, labelling etc. are described in a separate manual.
BL20 I/O-modules (TURCK-Documentation-No.: English D300717)
Furthermore, the manual contains a short description of the project planning and diagnostics software for TURCK I/O-systems, the software I/O-ASSISTANT.
D301087 1211 - BL20 CANopen1-2
Page 11
Description of Symbols Used

1.2 Description of Symbols Used

Danger
This sign can be found next to all notes that indicate a source of hazards. This can refer to danger to personnel or damage to the system (hardware and software) and to the facility.
This sign means for the operator: work with extreme caution.
Attention
This sign can be found next to all notes that indicate a potential hazard.
This can refer to possible danger to personnel and damages to the system (hardware and software) and to the facility.
Note
This sign can be found next to all general notes that supply important information about one or more operating steps. These specific notes are intended to make operation easier and avoid unnecessary work due to incorrect operation.
D301087 1211 - BL20 CANopen
1-3
Page 12
About this Manual

1.3 Overview

This manual includes all information necessary for the prescribed use of BL20 products. It has been specially conceived for personnel with the necessary qualifications.

1.3.1 Prescribed Use

Attention
Please read this section carefully. Safety aspects cannot be left to chance when dealing with electrical equipment.
Danger
The devices described in this manual must be used only in applications prescribed in this manual or in the respective technical descriptions, and only with certified components and devices from third party manufacturers.
Appropriate transport, storage, deployment and mounting as well as careful operating and thorough maintenance guarantee the trouble-free and safe operation of these devices.

1.3.2 Notes Concerning Planning /Installation of this Product

Danger
All respective safety measures and accident protection guidelines must be considered carefully and without exception.
D301087 1211 - BL20 CANopen1-4
Page 13
List of Revisions

1.4 List of Revisions

In comparison to the previous manual edition, the following changes/ revisions have been made:
Table 1-1: List of revisions
Chapter Subject/Description new changed deleted
5/6 BL20 - Communication in CANopen/ Diagnostics -
X Emergency Frames seperate manual D301230
8 BL20-Approvals for Zone 2/ Division 2
X
seperate manual D301255
Note
The publication of this manual renders all previous editions invalid.
D301087 1211 - BL20 CANopen
1-5
Page 14
About this Manual
D301087 1211 - BL20 CANopen1-6
Page 15

2 BL20 Philosophy

2.1 The Basic Concept ............................................................................................................................. 2
2.2 BL20 Components ............................................................................................................................. 3
2.2.1 Gateways..............................................................................................................................................3
– Gateways with integrated power supply...........................................................................................3
– Gateways without power supply ........................................................... .... ... ....................................3
2.2.2 Power Distribution Modules .................................................................................................................3
2.2.3 Electronics Modules .............................................................................................................................4
2.2.4 Base Modules.......................................................................................................................................5
2.2.5 End Plate ..............................................................................................................................................7
2.2.6 End Bracket..........................................................................................................................................7
2.2.7 Jumpers................................................................................................................................................8
2.2.8 Marking Material...................................................................................................................................8
2.2.9 Shield Connection, 2-Pole for Analog Modules ........................ ....................................... ... ... .... ... .......9
D301087 1211 - BL20 CANopen 2-1
Page 16
BL20 Philosophy

2.1 The Basic Concept

BL20 is a modular I/O system for use in industrial automation. It connects the sensors and actuators in the field with the higher-level master.
BL20 offers modules for practically all applications:
Digital input and output modules
Analog input and output modules
Technology modules (counters, RS232 interface...)
A complete BL20 station counts as one station on the bus and therefore occupies one fieldbus address in any given fieldbus structure. A BL20 station consists of a gateway, power distribution modules and I/ O modules.
The connection to the relevant fieldbus is made via the bus-specific gateway, which is responsible for the communication between the BL20 station and the other fieldbus stations.
The communication within the BL20 station between the gateway and the individual BL20 modules is regulated via an internal module bus.
Note
The gateway is the only fieldbus-dependent module on a BL20 station. All other BL20 modules are not dependent on the fieldbus used.
Flexibility
All BL20 stations can be planned to accommodate the exact number of channels to suit your needs, because the modules are available in block and slice design.
A BL20 station can contain modules in any combination, which means it is possible to adapt the system to practically all applications in automated industry.
Compactness
The slim design of the BL20 modules (gateway 50.4 mm / 1.98 inch, slice 12.6 mm / 0.49 inch and block
100.8 mm / 3.97 inch) and their low overall height favor the installation of this system in confined spaces.
Easy to handle
All BL20 modules, with the exception of the gateway, consist of a base module and an electronics module.
The gateway and the base modules are snapped onto a mounting rail. The electronics modules are plugged onto the appropriate base modules.
The base modules are designed as terminal blocks. The wiring is secured by tension clamp or screw connection. The electronics modules can be plugged or pulled when the station is being commissioned or for maintenance purposes, without having to disconnect the field wiring from the base modules.
D301087 1211 - BL20 CANopen2-2
Page 17
BL20 Components

2.2 BL20 Components

For a detailed explanation of the individual BL20 components, please refer to chapter 2 and chapter 4. The "Appendix" to this manual contains (amongst others) a list of all BL20 components and the assignment of electronics modules to base modules.

2.2.1 Gateways

The gateway connects the fieldbus to the I/O modules. It is responsible for handling the entire process data and generates diagnostic information for the higher-level master and the software tool I/Oassistant.
Gateways with integrated power supply
The BL20 gateway BL20-GWBR-CANOPEN offers an integrated power supply unit for feeding the gateway and the connected I/O modules.
It is not necessary to supply each individual module with a separate voltage
Figure 2-1: Gateway BL20-GWBR­CANOPEN
Gateways without power supply
Note
The gateways without integrated power supply unit need an additional power supply module (bus refreshing module) which feeds the gateway an the connected I/O modules.

2.2.2 Power Distribution Modules

D301087 1211 - BL20 CANopen
2-3
Page 18
BL20 Philosophy
Figure 2-2: Power distribu­tion module
The power supply for gateways and I/O modules is fed to the power distribution modules; therefore, it is not necessary to supply each individual module with a separate voltage.

2.2.3 Electronics Modules

Electronics modules contain the functions of the BL20 modules (power distribution modules, digital and analog input/output modules, and technology modules).
Electronics modules are plugged onto the base modules and are not directly connected to the wiring. The assignment table in the Section "Ordering Information" of the "Appendix" shows the possible combinations of electronics and base modules. They can be plugged or pulled when the station is being commissioned or for maintenance purposes, without having to disconnect the field wiring from the base modules.
Figure 2-3: Electronics module in slice design
D301087 1211 - BL20 CANopen2-4
Page 19
BL20 Components
Figure 2-4: Electronics module in block design

2.2.4 Base Modules

The field wiring is connected to the base modules. These are constructed as terminals in block and slice designs and are available in the following variations with either tension clamp or screw connections: 2­/3-wire (2-channel), 4-wire (2-channel) and 4x 2-/3-wire (4-channel).
The assignment table in the Section "Ordering Information" of the "Appendix" shows the possible combinations of electronics and base modules.
Figure 2-5: Base module with tension clamp connection
D301087 1211 - BL20 CANopen
2-5
Page 20
BL20 Philosophy
Figure 2-6: Base module with screw connection
Figure 2-7: Base module in block design
D301087 1211 - BL20 CANopen2-6
Page 21
BL20 Components

2.2.5 End Plate

An end plate on the right-hand side physically completes the BL20 station. An end bracket mounted into the end plate ensures that the BL20 station remains secure on the mounting rail even when subjected to vibration.
Figure 2-8: End plate

2.2.6 End Bracket

A second end bracket to the left of the gateway is necessary, as well as the one mounted into the end plate to secure the station.
Figure 2-9: End bracket
Note
The end plate an the end bracket are delivered together with each gateway.
D301087 1211 - BL20 CANopen
2-7
Page 22
BL20 Philosophy

2.2.7 Jumpers

Jumpers (QVRs) are used to bridge a connection level of a 4-wire base module. They can be used to connect potentials in relay modules (bridging the relay roots); thus considerably reducing the amount of wiring.
Figure 2-10: Jumpers

2.2.8 Marking Material

Labels: for labeling BL20 electronics modules.
Markers: for colored identification of connection levels of BL20 base modules.
Dekafix connector markers: for numbering the mounting slots on BL20 base modules.
Figure 2-11: Marking material
D301087 1211 - BL20 CANopen2-8
Page 23
BL20 Components

2.2.9 Shield Connection, 2-Pole for Analog Modules

The 2-pole shield connection can be used to connect signal-cable shielding to the base modules of analog input and output modules. A special tension-clamp operating tool (BL20-ZBW5-2) is required to mount the shield connection onto the base module.
Figure 2-12: Shield connection
D301087 1211 - BL20 CANopen
2-9
Page 24
BL20 Philosophy
D301087 1211 - BL20 CANopen2-10
Page 25

3 Short description of CANopen

3.1 CANopen .......................................................................................................................................... 2
3.1.1 General .................................................................................................................................................2
3.1.2 Communication ....................................................................................................................................3
– Network Management Messages......................................................................................................3
– Service Data Objects (SDOs).............................................................................................................3
– Process Data Objects (PDOs) ...........................................................................................................4
– Special Function Objects ..................................................................................................................4
3.2 BL20 and CANopen ........................................................................................................................... 5
3.3 Electronic data sheet – EDS file ......................................................................................................... 6
D301087 1211 - BL20 CANopen 3-1
Page 26
Short description of CANopen

3.1 CANopen

Note
The following description of CANopen is an excerpt from the homepage of CiA (CAN in Automation), the international users’ and manufacturers’ organization for CAN.

3.1.1 General

CANopen is an open, non-proprietary network protocol. It consists of a profile family, based on a communication profile and several device profiles. The CANopen communication profile is standardized as CiA DS-301 (Application Layer and Communication Profile).
The CANopen device profile for I/O-modules has been published as CiA DS-401 (Device Profile for I/O­Modules).
CANopen is based on the following standards:
ISO 11 898 (Physical and Data Link Layer)
Layers 1 and 2 of the ISO/OSI communication model
CiA DS-301 (Application Layer and Communication Profile) C ANopen communication profile
CiA DS-302 (Framework for Programmable CANopen Devices) CANopen Network Management
NMT
CiA DS-401 (Device Profile for I/O-modules)
CiA DS-406 (Device Profile for Encoders) CANopen device profile for counter modules
CiA DS-102 (CAN Physical Layer for Industrial Applications) General application in the field sector
(connectors and bit rates) on the basis of ISO 11898
D301087 1211 - BL20 CANopen3-2
Page 27
CANopen

3.1.2 Communication

The lower layers of CANopen are defined according to the ISO-OSI model in the ISO 11898 standard.
Communication between the individual nodes is made by transmitting "Telegrams".
4 different types of telegram message are defined for CANopen:
Network management messages
Service data objects SDO
Process data objects PDO
Predefined messages
Network Management Messages
Network management messages are used in the network to control the nodes and their operating states. This type of message makes it possible, for instance, to configure the data transmission mechanism of a node.
The Network Management objects include Boot-up message, Heartbeat protocol and NMT message.
Boot-up message, Heartbeat and Node Guarding are implemented as single CAN frames with 1-byte data field.
The NMT message is mapped to a single CAN frame with a data length of 2 byte. Its identifier is 0. The first byte contains the command specifier and the second contains the Node-ID of the device that must perform the command (in the case of Node-ID 0 all nodes have to perform the command). The NMT message transmitted by the NMT master forces the nodes to transit to another NMT state. The CANopen state machine specifies the states Initialization, Pre-Operational, Operational and Stopped. After power-on, each CANopen device is in the state Initialization and automatically transits to the state Pre-operational. In this state, transmission of SDOs is allowed. If the NMT master has set one or more nodes into the state Operational, they are allowed to transmit and to receive PDOs. In the state Stopped no communication is allowed except that of NMT objects.
The state Initialization is divided into three sub-states in order to enable a complete or partial reset of a node. In the sub-state Reset Application the parameters of the manufacturer-specific profile area and the standardized device profile area are set to their power-on values. In the sub-state Reset Communication the parameters of the communication profile area are set to their power-on values. The third sub-state is initializing, which a node enters automatically after power-on. Power-on values are the last stored parameters.
The Heartbeat protocol is for error control purposes and signals the presence of a node and its state. The Heartbeat message is a periodic message of the node to one or several other nodes. It indicates that the sending node is still working properly.
A device sends the Boot-up message to indicate to the NMT master that it has reached the state Pre­operational. This occurs whenever the device initially boots-up but also after a power-out during operation. The Boot-up message has the same identifier as the Heartbeat object, however, its data content is zero.
Service Data Objects (SDOs)
A Service Data Object (SDO) reads from entries or writes to entries of the Object Dictionary.
The SDO transport protocol allows transmitting objects of any size. The first byte of the first segment contains the necessary flow control information including a toggle bit to overcome the problem of doubly received CAN frames. The next three bytes of the first segment contain index and sub-index of the Object Dictionary entry to be read or written. The last four bytes of the first segment are available for user data. The second and the following segments (using the very same CAN identifier) contain the control byte and up to seven bytes of user data. The receiver confirms each segment or a block of segments, so that a peer-to-peer communication (client/server) takes place.
D301087 1211 - BL20 CANopen
3-3
Page 28
Short description of CANopen
Process Data Objects (PDOs)
Process Data Objects (PDOs) are mapped to a single CAN frame using up to 8 bytes of the data field to transmit application objects. Each PDO has a unique identifier and is transmitted by only one node, but it can be received by more than one (producer/consumer communication).
PDO transmissions
PDO transmissions may be driven by an internal event, by an internal timer, by remote requests and by the Sync message received:
Event- or timer-driven:
An event (specified in the device profile) triggers message transmission. An elapsed timer additionally triggers the periodically transmitting nodes.
Remotely requested:
Another device may initiate the transmission of an asynchronous PDO by sending a remote transmission request (remote frame).
Synchronous transmission:
In order to initiate simultaneous sampling of input values of all nodes, a periodically transmitted Sync message is required. Synchronous transmission of PDOs takes place in cyclic and acyclic transmission mode. Cyclic transmission means that the node waits for the Sync message, after which it sends its measured values. Acyclically transmitted synchronous PDOs are triggered by a defined application-specific event.
Special Function Objects
CANopen also defines three specific protocols for synchronization, emergency indication, and time­stamp transmission.
Synchronization object (Sync)
The Sync Object is broadcast periodically by the Sync Producer. The time period between Sync messages is defined by the Communication Cycle Period, which may be reset by a configuration tool to the application devices during the boot-up process. There can be a time jitter in transmission by the Sync Producer due to some other objects with higher prior identifiers or by one frame being transmitted just before the Sync message. The Sync message is mapped to a single CAN frame with the identifier 128 by default. The Sync message does not carry any data.
Emergency object (Emcy)
The Emergency message is triggered by the occurrence of a device internal error situation and are transmitted from an Emergency producer on the concerned application device. This makes them suitable for interrupt type error alerts. An Emergency message is transmitted only once per ‘error event’. As long as no new errors occurs on a device, no further Emergency message can be transmitted. Zero or more Emergency consumers may receive these. The reaction of the Emergency consumer is application-specific. CANopen defines several Emergency Error Codes to be transmitted in the Emergency message, which is a single CAN frame with 8 data byte.
Time stamp object (Time)
By means of Time-Stamp, a common time frame reference is provided to application devices. It contains a value of the type Time-of-Day. This object transmission follows the producer/consumer push model. The associated CAN frame has the pre-defined identifier 256 and a data field of 6-byte length.
D301087 1211 - BL20 CANopen3-4
Page 29
BL20 and CANopen

3.2 BL20 and CANopen

BL20 supports the following CANopen functions:
SDO transfer, any length of information
Emergency object
Sync frame evaluation
Event-driven PDOs
Synchronous PDOs (clock-synchronous)
Remote-requested PDO/polling
D301087 1211 - BL20 CANopen
3-5
Page 30
Short description of CANopen

3.3 Electronic data sheet – EDS file

CANopen nodes are embedded in the CANopen structure by the help of a standardized EDS file (Electronic Data Sheet).
The EDS file lists all necessary Objects with their corresponding Sub-indices and the matching entries.
The latest version of a particular EDS file can be downloaded directly from the TURCK Homepage www.turck.com.
D301087 1211 - BL20 CANopen3-6
Page 31

4 BL20 - Gateway for CANopen

4.1 Introduction ...................................................................................................................................... 2
4.2 Function ............................................................................................................................................ 3
4.3 Technical Information ....................................................................................................................... 4
4.4 Technical Data................................................................................................................................... 5
4.4.1 General Technical Data ................................... ....................................... ... .... ... ... ... ..............................5
– Relating to a Station .........................................................................................................................5
– Approvals...........................................................................................................................................7
– Base Modules............................... .... ... ....................................... ... ... ... ... ...........................................7
4.4.2 Structure Diagram of a Gateway ............................................................ ... .... ... ... ... ..............................8
4.4.3 Technical Data BL20-GW-CANOPEN ..................................................................................................8
4.4.4 Technical Data BL20-GWBR-CANOPEN .............................................................................................9
4.5 Connections for data cables to BL20-GW-CANOPEN....................................................................... 10
4.5.1 Fieldbus connection via SUB-D socket..............................................................................................10
4.5.2 Fieldbus connection through direct wiring.........................................................................................10
4.6 Connections of the data cables to BL20-GWBR-CANopen............................................................... 12
4.6.1 Fieldbus connection via Open Style connector..................................................................................12
4.6.2 Service Interface Connection ................................. ....................................... ... ... ... .... ... .....................14
– Connection with I/O-ASSISTANT-Connection Cable......................................................................14
4.7 Setting the bit transfer rate through DIP-switches......................................................................... 15
4.8 Node-ID Setting .............................................................................................................................. 17
4.9 Acceptance of the BL20 Station Configuration............................................................................... 19
4.10 Status Indicators/ Diagnostic Messages Gateway .......................................................................... 20
4.10.1 Diagnostic Messag es via LEDs .............................. ... ....................................... ... ... .... ... ... ..................20
D301087 1211 - BL20 CANopen 4-1
Page 32
BL20 - Gateway for CANopen

4.1 Introduction

This chapter contains a description of BL20 gateways for the standardized fieldbus CANopen. The chapter is divided up as follows: a description of functions, general and specific technical data, a description of addressing and status displays.
Attention
Please note, SWIRE-modules can only be used with the gateways BL20-GW-CANOPEN with firmware version 4.02 and BL20-GWBR-CANOPEN with firmware version 2.02.
Danger
The behavior of the analog inputs is now adapted to the actual CANopen standard DS401. The firmware versions 4.02 for BL20-GW-CANOPEN and version 2.02 for BL20-GWBR­CANOPEN are thus not compatible with older firmware versions relating to the behavior of the analog inputs.
D301087 1211 - BL20 CANopen4-2
Page 33
Function

4.2 Function

The BL20 gateways enable BL20 modules to operate on CANopen. The gateway is the connection between the BL20 modules and a CANopen host system. It regulates the process data between the I/O level and the fieldbus and generates diagnostic data for the higher-level host system.
Information is made available to the software tool I/O-ASSISTANT via the service interface.
D301087 1211 - BL20 CANopen
4-3
Page 34
BL20 - Gateway for CANopen
ERR BUS
GWBR-
CANOPEN
CAN H
SHLD
CAN L
GND
CAN H
SHLD
CAN L
GND
H
Bit Rate
L
1 2 3 4
A B
C D
E
F G
I
H
J
ERR BUS
GWBR
CANopen
H
Bit Rate
L
1 2 3 4
GND
CAN_L
Shield
CAN_H
A B
C D
E
F
G
H
I

4.3 Technical Information

Figure 4-1: BL20-GW­CANOPEN
A Service interface B Type designa-
tion
C LEDs for
module bus
D DIP-switch for
transfer rate
E Rotary encod-
ing switch for Node-ID
F SET button G CANopen, SUB-
D plug
H CANopen,
direct wiring
I LEDs for
CANopen
J CANopen, SUB-
D socket
Figure 4-2: BL20-GWBR­CANOPEN
A Service interface B Type
designation
C LEDs for
module bus
D DIP-switch for
transfer rate
E Rotary encod-
ing switch for Node-ID
F SET button G Screw terminals
for field supply and system sup­ply
H CANopen,
direct wiring
I Open Style con-
nector
D301087 1211 - BL20 CANopen4-4
Page 35
Technical Data

4.4 Technical Data

4.4.1 General Technical Data

Relating to a Station
Note
The auxiliary power supply must comply with the stipulations of SELV (Safety Extra Low Voltage) according to IEC 364-4-41.
Table 4-1: General technical data (station)
Supply voltage/ auxiliary voltage
Nominal value (provision for other modules) 24 V DC
Permissible range according to EN 61131-2 (18 to 30 V DC)
Residual ripple according to EN 61131-2
Potential isolation Yes, via optocoupler
Ambient conditions
Ambient temperature
–T
–T
0 to +55 °C / 32 to 131 °F
Ambient
-25 to +85 °C / 13 to 185 °F
Store
Relative humidity according to IEC 61 131-2/ EN 50 178
Climatic tests according to IEC 61131-2
Noxious gas – SO
2
:
10 ppm (rel. humidity < 75 %, non-condensing)
S:
–H
2
1.0 ppm (rel. humidity < 75 %, non-condensing)
Resistance to vibration according to IEC 61131-2
10 to 57 Hz, Constant amplitude 0.075 mm / 0.003 inch, 1g
57 to 150 Hz, Constant acceleration 1 g Yes
Mode of vibration Frequency sweeps with a change in speed of
Period of oscillation 20 frequency sweeps per axis of coordinate
Shock resistant according to IEC 68-2-27 18 shocks, sinusoidal half-wave 15 g peak value/
Resistance to repetitive shock according to IEC 68-2-29
Topple and fall according to IEC 68-2-31 and free fall according to IEC 68-2-32
Weight < 10 kg
D301087 1211 - BL20 CANopen
Yes
1 Octave/min
11 ms, in each case in +/- direction per space coordinate
1 000 shocks, half-sinus 25 g peak value/6 ms, in each case in +/- direction per space coordinate
4-5
Page 36
BL20 - Gateway for CANopen
Height of fall 1.0 m / 39.37 inch
Weight 10 to 40 kg
Height of fall 0.5 m / 19.69 inch
Test runs 7
Device with packaging, electrically tested printed-circuit board
Electromagnetic compatibility (EMC) according to EN 50 082-2 (Industry)
Static electricity according to EN 61 000-4-2
– Discharge through air (direct) 8 kV
– Relay discharge (indirect) 4 kV
Electromagnetic HF fields according to EN 61 000-4-3 and ENV 50 204
Conducted interferences induced by HF fields according to EN 61 000-4-6
Fast transients (Burst) according to EN 61 000-4-4
Interference criteria A: unrestricted operation, normal operating behavior
Interference criteria B: temporary interference, normal operation possible
Emitted interference according to EN 50 081-2 (Industry)
Reliability
Operational life MTBF min. 120000 h
Electronic modules pull/ plug cycles
Tests according to EN 61 131-2
Cold DIN IEC 68-2-1, temperature -25 °C / -13 °F,
10 V/m
10 V
1 kV
2 kV
according to EN 55 011 Class A, Group 1
20
duration 96 h; not in use
Dry heat DIN IEC 68-2-2, temperature +85 °C / 185 °F,
duration 96 h; device not in use
Damp heat, cyclic DIN IEC 68-2-30, temperature +55 °C / 131 °F,
duration 2 cycles every 12 h; device in use
Temperature change DIN IEC 68-2-14, temperature 0 to +55 °C / 32 to
131 °F, duration 2 cycles, temperature change per minute; device in use
Pollution severity according to IEC 664 (EN 61 131-2)
Protection class according to IEC 529 IP20
D301087 1211 - BL20 CANopen4-6
Page 37
Technical Data
Danger
This device can cause radio disturbances in residential areas and in small industrial areas (residential, business and trading). In this case, the operator can be required to take appropriate measures to suppress the disturbance at his own cost.
Approvals
Table 4-2: Approvals
Table 4-3: Technical data for base modules
CE
CSA
UL
Base Modules
Protection class IP 20
Measurement data according to VDE 0611 Part 1/8.92/ IEC 947-7-1/1989
Insulation stripping length 8 mm / 0.32 inch
Max. wire range 0.5 to 2.5 mm
2
/ 0.0008 to 0.0039 inch2 / 20 to
12 AWG
Crimpable wire
2
"e” solid core H 07V-U 0.5 to 2.5 mm
/ 0.0008 to 0.0039 inch2 / 20 to
12 AWG
2
"f” flexible core H 07V-K 0.5 to 1.5 mm
/ 0.0008 to 0.0023 inch2 / 20 to
16 AWG
2
"f” with ferrules according to DIN 46228/1 (ferrules crimped gas-tight)
0.5 to 1.5 mm 16 AWG
/ 0.0008 to 0.0023 inch2 / 20 to
Plug gauge according to
A1
IEC 947-1/1988
TOP connection technology Tension clamp or screw connection
D301087 1211 - BL20 CANopen
4-7
Page 38
BL20 - Gateway for CANopen
Fieldbus
(External)
Service
interface
External RAM
External
ROM flash
Module bus
(Internal)
Controller
– internal RAM
– WDG
– CAN-Ctr.

4.4.2 Structure Diagram of a Gateway

The BL20 CANopen gateway has the following structure:
Figure 4-3: Gateway struc­ture

4.4.3 Technical Data BL20-GW-CANOPEN

Table 4-4: Technical data BL20-GW­CANOPEN
Designation Value
Supply voltage(as per EN 61131-2)
Nominal value (supply from
5 V DC (4.8 to 5.2 V DC)
bus refreshing module)
Restriction on EN 61131-2
The supply energy required to bridge a supply interruption up to 10 ms is not stored. Please secure the U
for BL20-BR-24VDC-D modules
sys
by using an appropriate power supply unit!
Current drawn from the module bus
Without service/without fieldbus 280 mA
Without service/with fieldbus (1 Mbps) 410 mA
With service/without fieldbus 300 mA
Maximum 350 mA
Dimensions
Width/length/height (mm) 50.6 x 114.8 x 74.4 mm
Service
Connections PS/2 socket
Fieldbus terminations 1x 9-pole SUB-D socket,
1x 9-pole SUB-D plug, 2 x tension spring connector type LPZF, 5.08, 5-pole
Fieldbus shielding connection via BL20-SCH-1
Transfer rate 10, 20, 50, 125, 250, 500, 800 and 1000 kbps
Fieldbus termination SUB-D plug connector or external resistors
2 rotary hex encoder switches with labeling for the Node-ID setting.
D301087 1211 - BL20 CANopen4-8
Page 39
Technical Data

4.4.4 Technical Data BL20-GWBR-CANOPEN

Table 4-5: Technical data BL20-GWBR­CANOPEN
Designation Value
Supply
Field supply
U
Nominal value (range) 24 V DC (18 to 30 V DC)
L
I
max. field current 10 A
L
Isolation voltage (U
to FE)
U
L
to U
L
/ UL to fieldbus/
SYS
500V
eff
Connections 2-pole screw terminal
System supply
U
nominal value (range) 24 V DC (18 to 30 V DC)
SYS
I
(for IMB = 1.2 A/U
SYS
I
(supply to the module bus stations) 1.2 A
MB
Isolation voltage (U
to fieldbus/U
U
SYS
= 18 V DC) max. 900 mA
SYS
500V
SYS
to UL/
SYS
to FE)
eff
Connections 2-pole screw terminal
Physical interfaces
Fieldbus
Transfer rate 10 kbps to 1 Mbps
Isolation voltage (fieldbus to U fieldbus to U
/fieldbus to FE)
L
SYS
/
500V
eff
Fieldbus connections Socket:
MSTBV 2,5/5-GF-5.08 GY AU/Phoenix Contact
Plug: TMSTBP 2,5/5-STF-5.08 AB GY AU/Phoenix Contact (included in delivery)
Fieldbus shielding connection Via connector
Node-ID setting 2 rotary decimal encoding switches
Service
Connections PS/2 socket
Danger
This device can cause radio disturbances in residential areas and in small industrial areas (residential, business and trading). In this case, the operator can be required to take appropriate measures to suppress the disturbance at his own cost.
D301087 1211 - BL20 CANopen
4-9
Page 40
BL20 - Gateway for CANopen
54321
9678

4.5 Connections for data cables to BL20-GW-CANOPEN

4.5.1 Fieldbus connection via SUB-D socket

SUB-D connectors are provided for communication with the BL20-GW-CANOPEN gateway through the CANopen fieldbus.
The passive bus termination must be applied externally if the BL20 gateway is the last station in the bus structure. This external application can be implemented either through separate termination resistors or through a special SUB-D plug which has an integrated bus termination.
The pin assignments for the plug and socket are identical – the socket is shown as an example:
Figure 4-4: SUB-D socket on the gateway (top view)
Table 4-6: Pin assignments for gateway SUB­D plug/socket
A The shielding of
the fieldbus is connected through the metal housing of the SUB-D connector and the contact with the moun­ting rails (see
page 4-11)
Pin No. Designation Meaning
1not used
2 CAN_L inverted data signal (dominant
3 CAN_GND ground (optional for CAN data
4not used
5(CAN_SHLD)
6(GND)
7 CAN_H non-inverted data signal
8not used
9(CAN_V+)

4.5.2 Fieldbus connection through direct wiring

For making connections to the fieldbus you can choose between a SUB-D connection and direct wiring. Direct wiring of the BL20-GW-CANOPEN to the CANopen fieldbus can be made through the two terminal blocks with tension spring connectors.
low)
signals)
A
(dominant high)
D301087 1211 - BL20 CANopen4-10
Page 41
Connections for data cables to BL20-GW-CANOPEN
The passive bus termination must be applied externally if the BL20 gateway is the last station in the bus structure.
Table 4-7: List of connecting leads for direct wiring
Figure 4-5: Shielding connec­tion for an BL20­GW-CANOPEN
Designation Meaning
CAN_L Inverted data signal (dominant low)
GND Ground (optional)
SHLD Shielding (see below)
CAN_H Non-inverted data signal (dominant high)
Attention
If the gateway is wired up directly, then the bus connection must be shielded (e.g. with the help of a BL20-SCH-1 clamp).
Attention
No compensating current should flow through the shielding.
To achieve this, a reliable system of equipotential bonding must be installed.
Note
Equipotential bonding impedance 1/10 shielding impedance
D301087 1211 - BL20 CANopen
4-11
Page 42
BL20 - Gateway for CANopen
CAN L
SHIELD
CAN H
GND

4.6 Connections of the data cables to BL20-GWBR-CANopen

4.6.1 Fieldbus connection via Open Style connector

An Open Style Connector (5-pole) is available for connecting the BL20-GWBR-CANOPEN to the CANopen fieldbus.
The passive bus termination must be applied externally if the BL20 gateway is the last station in the bus structure.
Table 4-8: Pin assignment for the socket
Figure 4-6: Open Style connector (female/top)
Figure 4-7: Open Style connector (female/bottom)
1,2 - red
3,4 - white CAN_H Non-inverted data signal
(dominant high)
5,6 - grey Shield, Shielding braid, not insulated
7,8 - blue CAN_L Inverted data signal
(dominant low)
9,10 - black GND Ground reference (optional)
Figure 4-8: Open Style connector (male)
D301087 1211 - BL20 CANopen4-12
Page 43
Connections of the data cables to BL20-GWBR-CANopen
Figure 4-9: Shielding connec­tion for an BL20-GWBR­CANOPEN
Attention
No compensating current should flow through the shielding.
To achieve this, a reliable system of equipotential bonding must be installed.
D301087 1211 - BL20 CANopen
4-13
Page 44
BL20 - Gateway for CANopen
43
16
25
54321
9678
12345
6987

4.6.2 Service Interface Connection

The following cable can be used to connect the service interface (female PS/2 connector) to a PC for the purpose of using I/O-ASSISTANT (project planning and diagnostic software).
special I/O-ASSISTANT-connection cable from TURCK (IOASSISTANT-ADAPTERKABEL-BL20/BL67;
Ident-no.: 6827133)
Connection with I/O-ASSISTANT-Connection Cable
Figure 4-10: BL20-gateway connected to PC via special cable
A SUB-D socket B BL20 connecting
cable
C PS/2 plug
Figure 4-11: PS/2 male connector on the connection cable to the gateway (top view)
Figure 4-12: 9-pole SUB-D female connector on the cable for connecting to PC (top view)
Table 4-9: Pin assignments for PS/2 and SUB­D interfaces
The I/O-ASSISTANT-cables have a PS/2 male connector (connection for female connector on gateway) and a SUB-D female connector (connection for male connector on PC).
Pin BL20 gateway PS/2
SUB-D interface on PC Pin
socket
1+5 V GwDTR, DSR4, 6
2GNDGND5
3–––
4TxDRxD2
5/CtrlModeRTS7
6RxDTxD3
D301087 1211 - BL20 CANopen4-14
Page 45
Setting the bit transfer rate through DIP-switches

4.7 Setting the bit transfer rate through DIP-switches

The BL20 gateway can communicate with other CANopen nodes at the following transfer rates:
10 kbps 250 kbps
20 kbps 500 kbps
50 kbps 800 kbps
125 kbps 1000 kbps
The default transfer rate is 125 kbps. The transfer rate can be set through the DIP-switches under the cover of the BL20 gateway.
Figure 4-13: DIP-switch to set the transfer rate
Note
All the nodes in a CANopen network must be set to the same transfer rate.
To set a bit transfer rate that is supported by CANopen, proceed as follows:
Switch off the supply voltage for the BL20 gateway.
D301087 1211 - BL20 CANopen
4-15
Page 46
BL20 - Gateway for CANopen
Set the DIP-switches for the required transfer rate according to the following table:
Table 4-10: Setting the transfer rate
Bit transfer rate (kbps) DIP-switches (setting)
1234
1 000 0000
800 1000
500 0100
250 1100
125 0010
50 1010
20 0110
10 1110
reserved x x x 1
Note
The DIP-switches are in the “1” position when they are set to the right, as viewed from the front.
Switch on the supply voltage for the gateway again
D301087 1211 - BL20 CANopen4-16
Page 47
Node-ID Setting

4.8 Node-ID Setting

A Node-ID is assigned to every BL20 gateway in the CANopen structure.
The setting for the Node-ID of the BL20-GW-CANOPEN in a CANopen structure is made through the two rotary hex encoding switches. The setting for the Node-ID of the BL20-GWBR-CANOPEN is made through the two rotary decimal encoding switches. The switches can be found beneath a cover, below the service interface.
The BL20 gateway can be used as a CANopen node at any point in the bus structure.
Figure 4-14: Rotary hex encoding switch for the CANopen address setting of the BL20-GW­CANOPEN
Attention
If the BL20 gateway is used as the the last node in the bus communication, then a special bus connector with a built-in or add-on termination resistor is absolutely necessary!
Attention
A maximum of 127 Node-IDs (1 to 127) can be assigned in a CANopen structure. Each Node-ID can only be assigned once in the complete bus structure.
The Node-ID 000 must not be assigned. It is reserved for telegrams that are directed to all the other bus nodes.
The rotary encoding switches are marked with H for High (more significant digit) and L für Low (less significant digit).
BL20-GW-CANOPEN: The L switch is used to set L × 16 The H switch is used to set L × 16
BL20-GWBR-CANOPEN: The L switch is used to set L × 10 The H switch is used to set L × 10
0
(L = 0 to F).
1
(H = 0 to F).
0
(L = 0 to 9).
1
(H = 0 to 9).
Note
The NODE-ID switch on the BL20-GWBR-CANOPEN can be used to assign Node-IDs from 1 to 99!
D301087 1211 - BL20 CANopen
4-17
Page 48
BL20 - Gateway for CANopen
Note
After setting the Node-ID, the protective cover over the switches must be closed again.
See chapter 6
Note
BL20 does not support the assignment of Node-IDs across the bus network.
, Maximum System Extension, page 6-2.
D301087 1211 - BL20 CANopen4-18
Page 49
Acceptance of the BL20 Station Configuration

4.9 Acceptance of the BL20 Station Configuration

When making a new configuration of the BL20 station or an alteration of the existing station structure (“Module list”), the current configuration must be accepted in the CANopen mirror of the BL20 gateway. This is done through the configuration button between the two rotary encoding switches.
Note
The green "IOs" LED indicates that the current BL20 configuration matches the stored reference module list.
Pressing the set button with a pointed object for at least 2 seconds saves the current station configuration in non-volatile memory. A hardware reset will then be carried out automatically. With this reset, all the CANopen parameters will be restored to their default values, if the newly saved configuration is different to the old one.
Attention
When saving the BL20 configuration, all the CANopen objects must be parameterized again, if their parameter values differ from the default values. The complete parameterization of the station must subsequently be reloaded into the BL20 station.
The actuation of the button is indicated by a rapid (4 Hz) green blinking of the "IOs" LED. After 2 seconds, the LED changes to yellow blinking at 4 Hz, thus indicating that the station configuration is being saved. When the storage procedure is completed, the LED changes to a continuous green light.
D301087 1211 - BL20 CANopen
4-19
Page 50
BL20 - Gateway for CANopen

4.10 Status Indicators/ Diagnostic Messages Gateway

The gateway transmits the following diagnostics: the status of the BL20 station, the communication via the internal module bus, the communication to CANopen and the status of the gateway.
Diagnostic messages are displayed in two ways:
via individual LEDs
via the software of the respective host system or the software-tool I/O-ASSISTANT

4.10.1 Diagnostic Messages via LEDs

Every BL20 gateway displays the following statuses via LEDs:
2 LEDs for module bus communication (module bus LEDs):
GW and IOs
2 LEDs for CANopen communication (fieldbus LEDs):
ERR and Bus
The LED diagnoses shown below apply to both gateway versions:
BL20-GW-CANOPEN
BL20-GWBR-CANOPEN
An additional diagnosis indication is shown for the BL20-GWBR-CANOPEN.
Table 4-11: LED indicators
LED Status Meaning Remedy
GW OFF CPU not supplied.
Green 5 V DC operating voltage is present;
firmware is active; gateway is ready for operation and transfer
GW: green,
Firmware not active Reload the firmware! flashing, 1Hz IOs: red
Green, flashing,
Firmware active, gateway hardware
is defect 4 Hz
Additional diagnosis indication for BL20-GWBR-CANOPEN
-
Replace the gateway.
GW green,
blinking, 1 Hz
: undervoltage or overvoltage
U
SYS
: undervoltage
U
L
Check that the supply voltage is within the permissible range.
D301087 1211 - BL20 CANopen4-20
Page 51
Status Indicators/ Diagnostic Messages Gateway
Table 4-11: LED indicators
LED Status Meaning Remedy
IOs - CPU not supplied. Check the voltage supply.
Green Module bus is running,
­the configured module bus station corresponds to the physically connected station, communication is active.
Green, flashing,
Station is in the I/O-ASSISTANT Force Mode.
Deactivate the I/O-ASSISTANT Force Mode.
1 Hz
Red and LED "GW" off
Controller is not ready, V not within the required range possible reasons:
– too many modules connected to
level is
CC
– Check wiring at the gateway and
the voltage supply. – Dismount modules – Replace the gateway.
the gateway –short circuit in connected module – hardware error in –gateway
Red flashing, 1 Hz
Non-adaptable modification of the physically connected station.
– Compare the planned BL20 station
with the physical station.
– Check the physical station for
defective or incorrectly fitted electronics modules.
Red flashing, 4Hz
Red/green flashing, 1Hz
Red Short circuit or overload at sensor
no module bus communication At least one module has to be
plugged and has to be able to communicate with the gateway.
Adaptable modification of the physically connected station; data transfer possible
Check the physical station for pulled or new but not planned modules.
Automatic restart when
supply sensor supply is switched
debugging.
off
Off No voltage supply. Check the wiring of the voltage
supply.
D301087 1211 - BL20 CANopen
4-21
Page 52
BL20 - Gateway for CANopen
Table 4-11: LED indicators
LED Status Meaning Remedy
ERR Off No errors in communication
– between the BL20-CANopen gateway and other CANopen nodes
Red Faulty or interrupted
communication between BL20­CANopen gateway and other CANopen. Possible causes:
–CAN-BusOff – Heartbeat error – Guarding error – Transmit timeout
– Check that the fieldbus ends with a
termination resistor, if the BL20­CANopen gateway is the last node in the bus topology.
– Check the seating of the CANopen
bus connector (or the joints in the case of direct wiring). All connections must be correct and properly seated.
– Check the CANopen cable for
possible damage, and for correct connections.
– Check that the correct bit rate has
been set.
– Check that the NMT-master is still
functioning properly.
Bus OFF Fieldbus not operating Wait until the firmware download is
finished.
If the download is finished:
hardware error; replace the
gateway.
red NMT-slave state of the BL20-
orange NMT-slave state of the BL20-
green NMT-slave state of the BL20-
ERR + BUS red,
blinking alternately, 4Hz
– CANopen gateway is "Stopped"
– CANopen gateway is "Pre­Operational"
– CANopen gateway is "Operational"
Invalid Node-ID has been set Set the correct Node-ID with the
rotary hexadecimal
or decimal
encoding switches.
D301087 1211 - BL20 CANopen4-22
Page 53

5 BL20 - Communication in CANopen

Note
The CANopen-description for BL20 can be found in a separate manual „BL×× CANopen­object register “ D301230 unter www.turck.de.
D301087 1211 - BL20 CANopen 5-1
Page 54
BL20 - Communication in CANopen
D301087 1211 - BL20 CANopen5-2
Page 55

6 Guidelines for Station Planning

6.1 Random Module Arrangement ......................................................................................................... 2
6.1.1 Complete Planning ................................................................. ... ...........................................................2
6.1.2 Maximum System Extension ................................................................................................................2
6.2 Power Supply .................................................................................................................................... 4
6.2.1 Gateway Supply ...................................................................................................................................4
6.2.2 Module Bus Refreshing ........................................................................................................................4
6.2.3 Creating Potential Groups ....................................................................................................................8
6.2.4 Protecting the Service Interface on the Gat ew ay.......................... ... ... ....................................... ... . ......8
6.2.5 C-Rail (Cross Connection)....................................................................................................................9
6.2.6 Direct Wiring of Relay Modules ..........................................................................................................10
6.3 Plugging and Pulling Electronics Modules...................................................................................... 11
6.4 Extending an Existing Station......................................................................................................... 12
6.5 Firmware Download........................................................................................................................ 13
D301087 1211 - BL20 CANopen 6-1
Page 56
Guidelines for Station Planning

6.1 Random Module Arrangement

The arrangement of the I/O-modules within a BL20 station can basically be chosen at will.
Nevertheless, it can be useful with some applications to group certain modules together.
Note
The mixed usage of base modules with screw connections and base modules with tension clamp connections requires a further power supply module to be mounted. Thereby, it must be ensured that the base modules are fitted with the same connection technology (screw or tension clamp) as the power supply module.

6.1.1 Complete Planning

The planning of a BL20 station should be thorough to avoid faults and increase operating reliability.
Attention
If there are more than two empty slots next to one another, the communication is interrupted to all following BL20 modules.

6.1.2 Maximum System Extension

A BL20 station can consist of a gateway and a maximum of 74 modules in slice design (equivalent to 1 m in length of mounting rail including the end bracket and end plate). The maximum number of modules is less when using block modules (1 block module is equivalent to 8 modules in slice design).
D301087 1211 - BL20 CANopen6-2
Page 57
Random Module Arrangement
The following overview shows the maximum number of channels possible, on condition that the entire station is made up of that respective type of channel only:
Table 6-1: Maximum system extension
A plus 1 Bus Ref-
reshing module B plus 2 Bus Refreshing modules C plus 3 Bus Refreshing modules
Channels Modules
Type Max. no. Type Max. no.
72 B
B
Digital inputs 288 BL20-4DI-24VDC-P 72
Digital outputs 288 BL20-4DO-24VDC-
0.5A-P
Analog inputs, current 126 BL20-2AI-I(0/4...20MA) 63 C
Analog inputs, voltage 126 BL20-2AI-U(-10/
63
C
0...+10VDC)
Analog inputs, voltage/
112 BL20-4AI-U/I 28
A
current
Analog inputs, PT /Ni 126 BL20-2AI-PT/NI-2/3 63
Analog inputs,
126 BL20-2AI-THERMO-PI 63
C
C
Thermocouple
Analog outputs,
126 BL20-2AO-I(0/4...20MA) 63
C
current
Analog inputs, voltage 126 BL20-2AO-U(-10/
63
C
0...+10VDC)
Counter 31 BL20-1CNT-24VDC 31 A
RS232 31 BL20-1RS232 31 A
RS485/422 31 BL20-1RS485/422 31 A
SSI 31 BL20-1SSI 31 A
SWIRE 16 BL20-E-1SWIRE 16 A
Further limitations can be placed on the maximum possible number of BL20 modules by the use of the Power Feeding modules BL20-PF-24VDC-D or BL20-PF-120/230VAC-D; these being used either for creating potential groups or by insufficient field supply.
Attention
Ensure that a sufficient number of Power Feeding or Bus Refreshing modules are used if the system is extended to its maximum.
Note
If the system limits are exceeded, the software I/O-ASSISTANT gen-erates an error message when the user activates the "Station Verify" command.
D301087 1211 - BL20 CANopen
6-3
Page 58
Guidelines for Station Planning

6.2 Power Supply

6.2.1 Gateway Supply

Note
On a BL20 station including a gateway without integrated power supply unit, the first module to be mounted after the gateway is a Bus Refreshing module with either a BL20-P3x-SBB or a BL20-P4x-SBBC base module with tension clamp or screw connection.

6.2.2 Module Bus Refreshing

The number of BL20 modules that can be supplied by the gateway or a separate Bus Refreshing module via the internal module bus depends on the respective nominal current consumption of the individual modules on the module bus.
Attention
The sum total of the nominal current consumption of the connected BL20 modules must not exceed 1.5 A.
The following examples show the calculation for the required number of Bus Refreshing modules:
Example 1:
The BL20 station consists of 20 BL20-1AI-I(0/4...20MA) modules. The number of additional Bus Refreshing modules required is calculated as follows:
Gateway 430 mA
20 BL20-1AI-I(0/4...20MA) 20 x 41 mA 820 mA
Total: 1250 mA
Maximum permissible current via module bus: 1 500 mA
The calculation shows that no further Bus Refreshing module is required.
D301087 1211 - BL20 CANopen6-4
Page 59
Power Supply
Example 2:
The BL20 station comprises 15 BL20-1AI-U(-10/0...+10VDC) modules, 10 BL20-2AO-U(-10/0...+10VDC) modules, 10 BL20-2DI-24VDC-P modules and 5 BL20-2DO-24VDC-0.5A-P modules. The required number of Bus Refreshing modules is calculated as follows:
Gateway 430 mA
15 BL20-1AI-U(-10/0...+10VDC) 15 x 41 mA 615 mA
10 BL20-2AO-U(-10/0...+10VDC) 10 x 43 mA 430 mA
10 BL20-2DI-24VDC-P 10 x 28 mA 280 mA
5 BL20-2DO-24VDC-0.5A-P 5 x 32 mA 160 mA
Total: 1 915 mA
Table 6-2: Nominal current consumption of the BL20 modules on the module bus
Maximum permissible current via module bus: 1 500 mA
The calculation shows that an additional/further Bus Refreshing module is required at the latest following the last BL20-2AO module. This Bus Refreshing module is sufficient to supply the remaining modules.
Note
The power requirements of the BL20 gateway is to be considered when calculating the required number of Bus Refreshing modules.
The following table offers an overview of the nominal current consumption of the individual BL20 modules on the module bus:
Module Supply Nominal current consumption
Gateway 1 500 mA 430 mA
BL20-PF-24VDC-D 28 mA
BL20-PF-120/230VAC-D 25 mA
BL20-2DI-24VDC-P 28 mA
BL20-2DI-24VDC-N 28 mA
BL20-2DI-120/230VAC 28 mA
BL20-4DI-24VDC-P 29 mA
BL20-4DI-24VDC-N 28 mA
BL20-E-8DI-24VDC-P 15 mA
BL20-16DI-24VDC-P 45 mA
D301087 1211 - BL20 CANopen
6-5
Page 60
Guidelines for Station Planning
Table 6-2: Nominal current consumption of the BL20 modules on the module bus
Module Supply Nominal current consumption
BL20-E-16DI-24VDC-P 15 mA
BL20-32DI-24VDC-P 30 mA
BL20-1AI-I(0/4...20MA) 41 mA
BL20-2AI-I(0/4...20MA) 35 mA
BL20-1AI-U(-10/0...+10VDC) 41 mA
BL20-2AI-U(-10/0...+10VDC) 35 mA
BL20-2AI-PT/NI-2/3 45 mA
BL20-2AI-THERMO-PI 45 mA
BL20-4AI-U/I 50 mA
BL20-2DO-24VDC-0.5A-P 32 mA
BL20-2DO-24VDC-0.5A-N 32 mA
BL20-2DO-24VDC-2A-P 33 mA
BL20-4DO-24VDC-0.5A-P 30 mA
BL20-E-8DO-24VDC-P 15 mA
BL20-16DO-24VDC-0.5A-P 120 mA
BL20-E-16DO-24VDC-P 25 mA
BL20-32DO-24VDC-0.5A-P 30 mA
BL20-1AO-I(0/4...20MA) 39 mA
BL20-2AO-I(0/4...20MA) 40 mA
BL20-2AO-U(-10/0...+10VDC) 43 mA
BL20-2DO-R-NC 28 mA
BL20-2DO-R-NO 28 mA
BL20-2DO-R-CO 28 mA
BL20-1CNT-24VDC 40 mA
BL20-1RS232 140 mA
BL20-1RS485/422 60 mA
BL20-1SSI 50 mA
BL20-2RFID 30 mA
BL20-E-1SWIRE 60 mA
D301087 1211 - BL20 CANopen6-6
Page 61
Power Supply
23
22
21
13
12
11
23 23
22 22
21 21
13 13
12 12
11 11
24
23
22
21
14
13
12
11
24
23
22
21
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
–+
Field supply
TS
2 DO 2 DI 2 DO 2 DI BR
SBBC-B
2 DIAI1AO NO
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
2 DI
Gateway
GND-
CAN_L
Shield
CAN_H
+–
+–
Field supply
System supply
23
22
21
13
12
11
23 23
22 22
21 21
13 13
12 12
11 11
24 24
23 23
22 22
21 21
14 14
13 13
12 12
11 11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
+–
+
–+
=
Field supply
System supply
Field supply
GatewayTSBR
SBBC
2 DO 2 DI 2 DO 2 DI BR
SBBC-B
2 DIAI1AO NO
CANH
SHLD
CANL
GND
CANH
SHLD
CANL
GND
Figure 6-1: Power supply at BL20-GWBR­CANOPEN
If the power supply from the module bus is not guaranteed, thereby making a further Bus Refreshing module necessary, the software I/O-ASSISTANT generates an error message when the user activates the command “Station Verify“.
Note
Bus Refreshing modules which do not supply the gateway with power are to be combined with either a BL20-P3T-SBB-B or a BL20-P4T-SBBC-B (tension clamp connection) base module or with the base modules BL20-P3S-SBB-B or BL20-P4S-SBBC-B (screw connection).
Figure 6-2: Power supply at BL20-GW­CANOPEN
With the system supply, it must be ensured that the same ground potential and ground connections are used. Compensating currents flow via the module bus if different ground potentials or ground connections are used, which can lead to the destruction of the Bus Refreshing module.
All Bus Refreshing modules are connected to one another via the same ground potential.
The power to the module bus is supplied via the connections 11 and 21 on the base module.
D301087 1211 - BL20 CANopen
6-7
Page 62
Guidelines for Station Planning
23
22
21
13
12
11
23 23
22 22
21 21
13 13
12 12
11
24
23 23
22 22
21 21
14
13 13
12 12
11 11
Potential group 2
2L+ 2L-
2 DO 2 DI PF 2 DO2 DI
24
23
22
21
14
13
12
11
Potential group 1
TS
2 DIAI NO
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
NO
AI
24
23
22
21
14
13
12
11
Gateway
GND
CAN_L
Shield
CAN_H
+–
+
System supply
Field supply

6.2.3 Creating Potential Groups

Bus Refreshing and Power Feeding modules can be used to create potential groups. The potential isolation of potential groups to the left of the respective power distribution modules is provided by the base modules.
Attention
Ensure that the correct base modules are planned for when using Bus Refreshing modules.
Figure 6-3: Example for creating potential groups with BL20-GWBR­CANOPEN
Note
The system can be supplied with power independent of the potential group formation described above.
When using a digital input module for 120/230 V AC, it should be ensured that a potential group is created in conjunction with the Power Feeding module BL20-PF-120/230VAC-D.
Attention
It is not permitted to use the modules with 24 V DC and 120/230 V AC field supply in a joint potential group.

6.2.4 Protecting the Service Interface on the Gateway

During operation, the cover protecting the service interface and the rotary coding-switches must remain closed due to EMC and ESD.
D301087 1211 - BL20 CANopen6-8
Page 63
Power Supply

6.2.5 C-Rail (Cross Connection)

The C-rail runs through all base modules. The C-rail of the base modules for power distribution modules is mechanically separated; thus potentially isolating the adjoining supply groups.
Access to the C-rail is possible with the help of base modules with a C in their designation (for example, BL20-S4T-SBCS). The corresponding connection level is indicated on these modules by a thick black line. The black line is continuous on all I/O modules. On power distribution modules, the black line is only above the connection 24. This makes clear that the C-rail is separated from the adjoining potential group to its left.
Figure 6-4: C-rail front view
Figure 6-5: C-rail side view
Danger
It is permitted to load the C-rail with a maximum of 24 V. Not 230 V!
The C-rail can be used as required by the application, for example, as a protective earth (PE). In this case, the PE connection of each power distribution module must be connected to the mounting rail via an additional PE terminal, which is available as an accessory.
Note
For information about introducing a BL20 station into a ground reference system, please read chapter 7.
D301087 1211 - BL20 CANopen
6-9
Page 64
Guidelines for Station Planning
23
22
21
13
12
11
23 23
22 22
21 21
13 13
12 12
11 11
23 2323
22 2222
21 2121
13 1313
12 1212
11 1111
24 24
23 23
22 22
21 21
14 14
13 13
12 12
11 11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
Gateway
TS
BR
SBBC
2 DO
SBC
2 DI
SBBC
2 DO
SBC
2 DI
SBBPFSBBC
2 DI2 DO
SBBCSBC
2 DO
SBC
2 DI
SBB
C-rail (PE) C-rail (PE)
PE
terminal
Gateway
23
22
21
13
12
11
23 23
22 22
21 21
13 13
12 12
11 11
24 24
23 23
22 22
21 21
14 14
13 13
12 12
11 11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
yyy
TS
Gateway
PE
terminal
BR
SBBC
2 DO
SBC
2 DI
SBBC
2 DO
SBC
2 DI
SBB
PF NCNO
SBCSSBCS
NO
SBCSNCSBCS
C-rail (24 V DC)C-rail (PE)
SBBC
Figure 6-6: Using the C-rail as a protective earth
C-rails can be used for a common voltage supply when relay modules are planned. To accomplish this, the load voltage is connected to a Power Feeding module with the BL20-P4x-SBBC base module with tension clamp or screw connection. All the following relay modules are then supplied with power via the C-rail.
Figure 6-7: Using the C-rail as protective earth and for the power supply with relay modules
Attention
When relay modules are planned and the C-rail is used for a common voltage supply, a further power distribution module must be used for the potential isolation to the following modules. The C-rail can only again be used as a PE following potential isolation.
Cross-connecting relay module roots is achieved by the use of jumpers. The corresponding wiring diagram including the jumpers can be found in chapter 4.

6.2.6 Direct Wiring of Relay Modules

As well as the options mentioned above, relay modules can be wired directly. In this case, base modules without C-rail connections should be chosen to guarantee the potential isolation to the adjoining modules.
D301087 1211 - BL20 CANopen6-10
Page 65
Plugging and Pulling Electronics Modules

6.3 Plugging and Pulling Electronics Modules

BL20 enables the pulling and plugging of electronics modules without having to disconnect the field wiring. The BL20 station remains in operation if an electronics module is pulled. The voltage and current supplies as well as the protective earth connections are not interrupted.
Attention
If the field and system supplies remain connected when electronics modules are plugged or pulled, short interruptions to the module bus communications can occur in the BL20 station. This can lead to undefined statuses of individual inputs and outputs of different modules.
D301087 1211 - BL20 CANopen
6-11
Page 66
Guidelines for Station Planning

6.4 Extending an Existing Station

Attention
Please note that extensions to the station (mounting further modules) should be carried out only when the station is off-circuit.
Once alterations have been made to the order of the modules on the BL20 station, the new configuration must be saved to the ”actual configuration memory” of the BL20 gateway. This is done by either pressing the SET button between the two decimal rotary coding switches (see chapter 2) or by making the appropriate settings in the configuration software (see chapter 3).
D301087 1211 - BL20 CANopen6-12
Page 67
Firmware Download

6.5 Firmware Download

Firmware can be downloaded via the service interface on the gateway using the software tool I/O-ASSISTANT. More information is available in the program’s online help.
Attention
The station should be disconnected from the fieldbus when downloading.
Firmware must be downloaded by authorized personnel only.
The field level must be isolated.
D301087 1211 - BL20 CANopen
6-13
Page 68
Guidelines for Station Planning
D301087 1211 - BL20 CANopen6-14
Page 69

7 Guidelines for Electrical Installation

7.1 General Notes.................................................................................................................................... 2
7.1.1 General .................................................................................................................................................2
7.1.2 Cable Routing........ .... ... ....................................... ... ... ... .... ...................................... ..............................2
7.1.3 Cable Routing Inside and Outside of Cabinets: ........................................ .... ... ....................................2
– Cable Routing Outside Buildings ......................................................................................................2
7.1.4 Lightning Protection .............................................................................................................................3
7.1.5 Transmission Cables ............................................................................................................................3
7.1.6 Cable Types.................................. ... .... ...................................... .... ... ... ... ..............................................3
7.2 Potential Relationships..................................................................................................................... 4
7.2.1 General .................................................................................................................................................4
7.2.2 Potential-Free Installation.....................................................................................................................4
7.2.3 Non-isolated Installation.......................................................................................................................4
7.3 Electromagnetic Compatibility (EMC)............................................................................................... 5
7.3.1 Ensuring Electromagnetic Compatibility ..............................................................................................5
7.3.2 Grounding of Inactive Metal Components ...........................................................................................5
7.3.3 PE Connection......................................................................................................................................5
7.3.4 Earth-Free Operation............................................................................................................................5
– Protect against high frequency interference signals .........................................................................6
7.3.5 Mounting Rails......................................................................................................................................6
7.3.6 EMC Compliant Cabinet Installation ....................................................................................................7
7.4 Shielding of cables ............................................................................................................................ 8
7.5 Potential Compensation ................................................................................................................... 9
7.5.1 Switching Inductive Loads ..................... ... ....................................... ... ... ... .... ... ..................................10
7.5.2 Protection against Electrostatic Disc ha rg e (ESD ) ........ .... ... ... ....................................... ... ... ... .... ........10
7.6 Bus Connection ............................................................................................................................... 11
7.7 Two-Pole Shield Connection ........................................................................................................... 12
7.8
D301087 1211 - BL20 CANopen 7-1
Page 70
Guidelines for Electrical Installation

7.1 General Notes

7.1.1 General

Cables should be grouped together, for example: signal cables, data cables, heavy current cables, power supply cables.
Heavy current cables and signal or data cables should always be routed in separate cable ducts or bundles. Signal and data cables must always be routed as close as possible to ground potential surfaces (for example support bars, cabinet sides etc.).

7.1.2 Cable Routing

Correct cable routing prevents or suppresses the reciprocal influencing of parallel routed cables.

7.1.3 Cable Routing Inside and Outside of Cabinets:

To ensure EMC-compatible cable routing, the cables should be grouped as follows:
Various types of cables within the groups can be routed together in bundles or in cable ducts.
Group 1:
shielded bus and data cables
shielded analog cables
unshielded cables for DC voltage 60 V
unshielded cables for AC voltage 25 V
Group 2:
unshielded cables for DC voltage > 60 V and 400 V
unshielded cables for AC voltage > 25 V and 400 V
Group 3:
unshielded cables for DC and AC voltages > 400 V
The following group combination can be routed only in separate bundles or separate cable ducts (no minimum distance apart):
Group 1/Group 2
The group combinations:
Group 1/Group 3 and Group 2/Group 3
must be routed in s eparate cable ducts with a mi nimum dista nce of 10 cm apart. Th is is equ ally val id for inside buildings as well as for inside and outside of switchgear cabinets.
Cable Routing Outside Buildings
Outside of buildings, cables should be routed in closed (where possible), cage-type cable ducts made of metal. The cable duct joints must be electrically connected and the cable ducts must be earthed.
Danger
Observe all valid guidelines concerning internal and external lightning protection and grounding specifications when routing cables outside of buildings.
D301087 1211 - BL20 CANopen7-2
Page 71
General Notes
Station 0
Station 63Station x
terminating resistor
terminating resistor
R
t
R
t

7.1.4 Lightning Protection

The cables must be routed in double-grounded metal piping or in reinforced concrete cable ducts.
Signal cables must be protected against overvoltage by varistors or inert-gas filled overvoltage arrestors. Varistors and overvoltage arrestors must be installed at the point where the cables enter the building.

7.1.5 Transmission Cables

The slaves on the bus are connected to one another with fieldbus lines that correspond to the DeviceNet specification (ODVA Spec. Rel. V2.0).
The bus cables must be terminated at the beginning and end with a bus terminating resistor. This can be connected via the number 4 DIP switch on the gateway.
Figure 7-1: Representation of a bus cable

7.1.6 Cable Types

TURCK offers a variety of premoulded bus cables - please refer to the BL20-catalog (TURCK documentation number: D300418).
D301087 1211 - BL20 CANopen
7-3
Page 72
Guidelines for Electrical Installation
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
Gateway
Power Feeding
Bus Refreshing
I/O moduleI/O module I/O module
Bus Refreshing
Logic Logic
5V
Logic
24 V
2 O 2 O 4 I
24 V24 VField-
bus
24 V230 V
Logic
DC DC
DC DC
+V -V

7.2 Potential Relationships

7.2.1 General

The potential relationship of a CANopen system realized with BL20 modules is characterized by the following:
The system’s power supply to the gateway, I/O modules and the field level is distributed via a Bus
Refreshing module.
All BL20 modules (gateway, Bus Refreshing, Power Feeding and I/O modules), are connected
capacitively via base modules to the mounting rails.
Separate power supplies for the system and the field level allow a potential-free installation.
The block diagram shows the arrangement of a typical BL20 station.
Figure 7-2: Block diagram of a BL20 station

7.2.2 Potential-Free Installation

In a potential-free installation, the reference potentials of control and load circuitry are galvanically isolated from each other.
A potential-free installation is necessary with
All AC load circuits (for example, when using the Power Feeding module BL20-PF-120/230VAC-D)
Floating DC load circuits
The potential-free installation does not depend on the method of grounding.

7.2.3 Non-isolated Installation

In a non-isolated installation, the reference potentials of the control and load circuitry are galvanically connected.
D301087 1211 - BL20 CANopen7-4
Page 73
Electromagnetic Compatibility (EMC)

7.3 Electromagnetic Compatibility (EMC)

BL20 products comply in full with the requirements pertaining to EMC regulations.
Nevertheless, an EMC plan should be made before installation. Hereby, all potential electromechanical sources of interference should be considered such as galvanic, inductive and capacitive couplings as well as radiation couplings.

7.3.1 Ensuring Electromagnetic Compatibility

The EMC of BL20 modules is guaranteed when the following basic rules are adhered to:
Correct and large surface grounding of inactive metal components.
Correct shielding of cables and devices.
Proper cable routing – correct wiring.
Creation of a standard reference potential and grounding of all electrically operated devices.
Special EMC measures for special applications.

7.3.2 Grounding of Inactive Metal Components

All inactive metal components (for example: switchgear cabinets, switchgear cabinet doors, supporting bars, mounting plates, tophat rails, etc.) must be connected to one another over a large surface area and with a low impedance (grounding). This guarantees a standardized reference potential area for all control elements and reduces the influence of coupled disturbances.
In the areas of screw connections, the painted, anodized or isolated metal components must be
freed of the isolating layer. Protect the points of contact against rust.
Connect all free moving groundable components (cabinet doors, separate mounting plates, etc.) by
using short bonding straps to large surface areas.
Avoid the use of aluminum components, as its quick oxidizing properties make it unsuitable for
grounding.
Danger
The grounding must never – including cases of error – take on a dangerous touch potential. For this reason, always protect the ground potential with a protective cable.

7.3.3 PE Connection

A central connection must be established between ground and PE connection (protective earth).

7.3.4 Earth-Free Operation

Observe all relevant safety regulations when operating an earthfree system.
D301087 1211 - BL20 CANopen
7-5
Page 74
Guidelines for Electrical Installation
Protect against high frequency interference signals
Attention
In order to comply with radiation limit values in accordance with EN 55 011/2 000, the supply lines of the power distribution module BL20-BR-24VDC-D for supplying the gateway with power are to be fed through a ferrite ring (BL20PS416-ZBX-405). This is to be placed immediately next to the connection terminals. From there on, it is not permitted to make connections to further devices.

7.3.5 Mounting Rails

All mounting rails must be mounted onto the mounting plate with a low impedance, over a large surface area, and must be correctly earthed.
Figure 7-3: Mounting options
A TS 35 B Mounting rail C Mounting plate D TS 35
Mount the mounting rails over a large surface area and with a low impedance to the support system using screws or rivets.
Remove the isolating layer from all painted, anodized or isolated metal components at the connection point. Protect the connection point against corrosion (for example with grease; caution: use only suitable grease).
D301087 1211 - BL20 CANopen7-6
Page 75
Electromagnetic Compatibility (EMC)
abc d e
A
BC D
E

7.3.6 EMC Compliant Cabinet Installation

Figure 7-4: EMC compliant cabinet installa­tion
A Bonding straps
Bonding straps connect inactive metal components, if it is not possible to create a large surface area contact. Use short bonding straps with large surface areas.
B Mounting plates
Mounting plates used to hold control components must have a large surface area contact with the cabinet housing.
C Protective conductor rail
The protective conductor rail must also be connected over a large surface area to the mounting plates and additionally with an external cable (cross-section at least 10 mm2 / 0,015 inch2) to the protective conductor system to avoid interference currents.
D Protective conductor terminal block
The protective conductor terminal block must be connected to the protective conductor rail.
E Protective conductor system cable (grounding point)
The cable must be connected over a large surface area with the protective conductor system.
D301087 1211 - BL20 CANopen
7-7
Page 76
Guidelines for Electrical Installation

7.4 Shielding of cables

Shielding is used to prevent interference from voltages and the radiation of interference fields by cables. Therefore, use only shielded cables with shielding braids made from good conducting materials (copper or aluminum) with a minimum degree of coverage of 80 %.
The cable shield should always be connected to both sides of the respective reference potential (if no exception is made, for example, such as high-resistant, symmetrical, analog signal cables). Only then can the cable shield attain the best results possible against electrical and magnetic fields.
A one-sided shield connection merely achieves an isolation against electrical fields.
Attention
When installing, please pay attention to the following...
– the shield should be connected immediately when entering the –system, – the shield connection to the shield rail should be of low –impedance, – the stripped cable-ends are to be kept as short as possible, – the cable shield is not to be used as a bonding conductor.
The insulation of the shielded data-cable should be stripped and connected to the shield rail when the system is not in operation. The connection and securing of the shield should be made using metal shield clamps. The shield clamps must enclose the shielding braid and in so doing create a large surface contact area. The shield rail must have a low impedance (for example, fixing points of 10 to 20 cm apart) and be connected to a reference potential area.
The cable shield should not be severed, but routed further within the system (for example, to the switchgear cabinet), right up to the interface connection.
Note
Should it not be possible to ground the shield on both sides due to switching arrangements or device specific reasons, then it is possible to route the second cable shield side to the local reference potential via a capacitor (short connection distances). If necessary, a varistor or resistor can be connected parallel to the capacitor, to prevent disruptive discharges when interference pulses occur.
A further possibility is a double-shielded cable (galvanically separated), whereby the innermost shield is connected on one side and the outermost shield is connected on both sides.
D301087 1211 - BL20 CANopen7-8
Page 77
Potential Compensation
Reference potential
Potential compensation cable
Shield
Reference potential

7.5 Potential Compensation

Potential differences can occur between installation components that are in separate areas and these
are fed by different supplies,
have double-sided conductor shields which are grounded on different installation components.
A potential-compensation cable must be routed to the potential compensation.
Danger
Never use the shield as a potential compensation.
Connection 1 Connection 2
CAN_H 0 --------- 0 CAN_H
CAN_L 0 --------- 0 CAN_L
GND 0 --------- 0 GND
Figure 7-5: Potential compensation
A potential compensation cable must have the following characteristics:
Low impedance. In the case of compensation cables that are routed on both sides, the
compensation line impedance must be considerably smaller than that of the shield connection (max. 10 % of shield connection impedance).
Should the length of the compensation cable be less than 200 m, then its cross-section must be at
least 16 mm 25 mm
2
/ 0.025 inch2. If the cable length is greater than 200 m, then a cross-section of at least
2
/ 0.039 inch2 is required.
The compensation cable must be made of copper or zinc coated steel.
The compensation cable must be connected to the protective conductor over a large surface area
and must be protected against corrosion.
D301087 1211 - BL20 CANopen
7-9
Page 78
Guidelines for Electrical Installation
Potential compensation
Compensation cables and data cables should be routed as close together as possible, meaning the
enclosed area should be kept as small as possible.
Figure 7-6: Potential compensation between switch­gear cabinets

7.5.1 Switching Inductive Loads

In the case of inductive loads, a protective circuit on the load is recommended.

7.5.2 Protection against Electrostatic Discharge (ESD)

Attention
Electronic modules and base modules are at risk from electrostatic discharge when disassembled. Avoid touching the bus connections with bare fingers as this can lead to ESD damage.
D301087 1211 - BL20 CANopen7-10
Page 79
Bus Connection

7.6 Bus Connection

An Open Style Connector (5-pole) is available for connecting the BL20-GWBR-CANopen to the CANopen fieldbus.
The shield connection is made via the shielding braid of the cable.
For detailed information about the bus connection of the gateway please refer to chapter 4.6,
Connections of the data cables to BL20-GWBR-CANopen (page 4-12).
D301087 1211 - BL20 CANopen
7-11
Page 80
Guidelines for Electrical Installation

7.7 Two-Pole Shield Connection

The 2-pole shield connection can be used to connect signal-cable shielding to the base modules of analog input and output modules. A special tension-clamp operating tool (BL20-ZBW5-2) is required to mount the shield connection onto the base module.
Figure 7-7: Two-pole shield connection for analog modules
The following cable diameters are permissible for the shield connection:
Diameter of the shielding braid:max. 4.9 mm / 0.19 inch
Outer diameter of the cable: max. 6.5 mm / 0.26 inch
D301087 1211 - BL20 CANopen7-12
Page 81

8 BL20-Approvals for Zone 2/ Division 2

Note
The Zone 2 - approval certificates for BL20 can be found in a separate manual for approvals
D301255 on www.turck.de.
D301087 1211 - BL20 CANopen 8-1
Page 82
BL20-Approvals for Zone 2/ Division 2
D301087 1211 - BL20 CANopen8-2
Page 83
D301087 1211 - BL20 CANopen
8-3
Page 84
BL20-Approvals for Zone 2/ Division 2
D301087 1211 - BL20 CANopen8-4
Page 85
D301087 1211 - BL20 CANopen
8-5
Page 86
BL20-Approvals for Zone 2/ Division 2
D301087 1211 - BL20 CANopen8-6
Page 87

9Glossary

A
B
Acknowledge
Acknowledgment of a signal received.
Active metal component
Conductor or conducting component that is electrically live during operation.
Address
Identifier of, e.g. a memory position, a system or a module within a network.
Addressing
Allocation or setting of an address, e. g. for a module in a network.
Analog
Infinitely variable value, e. g. voltage. The value of an analog signal can take on any value, within certain limits.
Attribute
Attributes represent the data that a device makes available via the DeviceNet fieldbus (e. g. status of an object, serial number of the device, process data).
Automation device
A device connected to a technical process with inputs and outputs for control. Programmable logic controllers (PLC) are a special group of automation devices.
Baud
Baud is a measure for the transmission speed of data. 1 Baud corresponds to the transmission of one bit per second (Bit/s).
Baud rate
Unit of measurement for data transmission speeds in Bit/s.
Bidirectional
Working in both directions.
Bit Strobe
A Bit Strobe I/O connection is a connection between a DeviceNet client and an undetermined number of servers, these being queried by commands sent by the client.
Bonding strap
Flexible conductor, normally braided, that joins inactive components, e. g. the door of a switchgear cabinet to the cabinet main body.
Bus
Bus system for data exchange, e. g. between CPU, memory and I/O levels. A bus can consist of several parallel
cables for data transmission, addressing, control and power supply.
Bus cycle time
Time required for a master to serve all slaves or stations in a bus system, i. e. reading inputs and writing outputs.
D301087 1211 - BL20 CANopen 9-1
Page 88
Glossary
CDE
Bus line
Smallest unit connected to a bus, consisting of a PLC, a coupling element for modules on the bus and a module.
Bus system
All units which communicate with one another via a bus.
Capacitive coupling
Electrical capacitive couplings occur between cables with different potentials. Typical sources of interference are, e. g. parallel-routed signal cables, contactors and electrostatic discharges.
Class
A group of Objects that all describe the same system components. All Objects of a Class are identical in form and behavior, they can though contain different attributes.
COB
Communication Object, which is made of one or more CAN frames. Any information transmitted via CANopen has to be mapped into COBs (Source: CiA DS 401 V2.1).
COB-ID
COB-Identifier. Identifies a COB uniquely in a CAN network. The identifier determines the priority of that COB in the data link layer, too (Source: CiA DS 401 V2.1).
Coding elements
Two-piece element for the unambiguous assignment of electronic and base modules.
Configuration
Systematic arrangement of the I/O modules of a station.
CPU
Central Processing Unit. Central unit for electronic data processing, the processing core of the PC.
Cyclic
Messages are triggered time-controlled in Cyclic I/O connections by means of a time generator.
Digital
A value (e. g. a voltage) which can adopt only certain statuses within a finite set, mostly defined as 0 and 1.
DIN
German acronym for German Industrial Standard.
EDS
Electronic Device Data Sheet which contains standardized DeviceNet station descriptions. They simplify the planning of the DeviceNet nodes.
EIA
Electronic Industries Association – association of electrical companies in the United States.
D301087 1211 - BL20 CANopen9-2
Page 89
Electrical components
FGH
I
All objects that produce, convert, transmit, distribute or utilize electrical power (e. g. conductors, cable, machines, control devices).
EMC
Electromagnetic compatibility – the ability of an electrical part to operate in a specific environment without fault and without exerting a negative influence on its environment.
EN
German acronym for European Standard.
ESD
Electrostatic Discharge.
Field power supply
Voltage supply for devices in the field as well as the signal voltage.
Fieldbus
Data network on sensor/actuator level. A fieldbus connects the equipment on the field level. Characteristics of a fieldbus are a high transmission security and real-time behavior.
Force Mode
Software mode which enables the user to set his plant to a required state by forcing certain variables on the input and output modules.
GND
Abbreviation of ground (potential "0").
Ground
Expression used in electrical engineering to describe an area whose electrical potential is equal to zero at any given point. In neutral grounding devices, the potential is not necessarily zero, and one speaks of the ground reference.
Ground connection
One or more components that have a good and direct contact to earth.
Ground reference
Potential of ground in a neutral grounding device. Unlike earth whose potential is always zero, it may have a potential other than zero.
Hexadecimal
System of representing numbers in base 16 with the digits 0... 9, and further with the letters A, B, C, D, E and F.
Hysteresis
A sensor can get caught up at a certain point, and then "waver" at this position. This condition results in the counter content fluctuating around a given value. Should a reference value be within this fluctuating range, then the relevant output would be turned on and off in rhythm with the fluctuating signal.
I/O
Input/output.
D301087 1211 - BL20 CANopen
9-3
Page 90
Glossary
LMMOP
Impedance
Total effective resistance that a component or circuit has for an alternating current at a specific frequency.
Inactive metal components
Conductive components that cannot be touched and are electrically isolated from active metal components by insulation, but can adopt voltage in the event of a fault.
Inductive coupling
Magnetic inductive couplings occur between two cables through which an electrical current is flowing. The magnetic effect caused by the electrical currents induces an interference voltage. Typical sources of interference are for example, transformers, motors, parallel-routed network and HF signal cables.
Instance
An Instance is defined as being an Object that is actually set up in a device.
Load value
Predefined value for the counter module with which the count process begins.
Lightning protection
All measures taken to protect a system from damage due to overvoltages caused by lightning strike.
Low impedance connection
Connection with a low AC impedance.
LSB
Least Significant Bit
Mass
All interconnected inactive components that do not take on a dangerous touch potential in the case of a fault.
Module bus
The module bus is the internal bus in a BL20 station. The BL20 modules communicate with the gateway via the module bus which is independent of the fieldbus.
MSB
Most Significant Bit
NMT
see chapter 3 Short description of CANopen (Seite 3-1).
Overhead
System administration time required by the system for each transmission cycle.
PDO
see chapter 3 Short description of CANopen (Seite 3-1).
PLC
Programmable Logic Controller.
D301087 1211 - BL20 CANopen9-4
Page 91
Polling
R
S
Establish a Polled I/O Connection, i. e. a conventional Master/Slave relationship between a controller and a DeviceNet device.
Potential compensation
The alignment of electrical levels of electrical components and external conductive components by means of an electrical connection.
Potential free
Galvanic isolation of the reference potentials in I/O modules of the control and load circuits.
Potential linked
Electrical connection of the reference potentials in I/O modules of the control and load circuits.
Protective earth
Electrical conductor for protection against dangerous shock currents. Generally represented by PE (protective earth).
Radiation coupling
A radiation coupling appears when an electromagnetic wave hits a conductive structure. Voltages and currents are induced by the collision. Typical sources of interference are e. g. sparking gaps (spark plugs, commutators from electric motors) and transmitters (e. g., radio), that are operated near to conducting structures.
Reaction time
The time required in a bus system between a reading operation being sent and the receipt of an answer. It is the time required by an input module to change a signal at its input until the signal is sent to the bus system.
SDO
see chapter 3 Short description of CANopen (Seite 3-1).
D301087 1211 - BL20 CANopen
9-5
Page 92
Glossary
D301087 1211 - BL20 CANopen9-6
Page 93

10 Index

A
addressing
B
BL20 gateway –function
bus connection ............................................................7-11
C
cable types
CANopen ........................................................................ 3-1
–Boot-up message ......................................................... 3-3
–Communication ........................................................... 3-3
–EDS file .......................................................................... 3-6
–Emergency object (Emcy) ............................................ 3-4
–General ......................................................................... 3-2
–Network management messages ............................... 3-3
–Process data objects (PDOs) ........................................ 3-4
–Service data objects (SDOs) ......................................... 3-3
–Special function objects .............................................. 3-4
–Synchronization object ................................................ 3-4
–Time stamp object (Time) ............................................3-4
D
diagnostic messages
Division 2 ........................................................................8-1
......................................................................4-2
........................................................................4-3
.....................................................................7-3
....................................................4-20
N
Node-ID
Node-ID setting ............................................................4-17
P
parameter assignment
PE connection .................................................................7-5
planning ..........................................................................6-2
potential relationships ...................................................7-4
potential-compensation cable .......................................7-9
power distribution ..........................................................2-3
power supply ..................................................................6-4
Process data objects (PDOs) ...........................................3-4
product overview ...........................................................2-1
R
Rotary encoding switches –decimal
–hexadecimal ...............................................................4-17
S
service interface
shielding .........................................................................7-8
status displays .................................................................4-2
status indicators ...........................................................4-19
Supply voltage ................................................................4-8
.........................................................................4-17
...................................................4-2
.......................................................................4-17
............................................................4-14
E
earth-free operation
electromagnetic compatibility ...................................... 7-5
electronic modules ........................................................ 2-4
electrostatic discharge .................................................7-10
EMC .................................................................................7-5
empty slot ....................................................................... 6-2
ESD, electrostatic discharge ........................................7-10
F
Fieldbus connection –Direct wiring
–Open Style connector ................................................ 4-12
G
gateway
gateway function ...........................................................4-3
I
inductive loads, protective circuit
L
LEDs
M
mounting rail
.......................................................................... 2-3
.............................................................................. 4-20
.......................................................7-5
...............................................................4-10
............................... 7-10
..................................................................7-6
T
transmission cables
Z
.............................................................................8-1
Zone 2
........................................................7-3
D301087 1211 - BL20 CANopen 10-1
Page 94
Index
D301087 1211 - BL20 CANopen10-2
Page 95
www.turck.com
Hans Turck GmbH & Co. KG
45472 Mülheim an der Ruhr Germany Witzlebenstraße 7 Tel. +49 (0) 208 4952-0 Fax +49 (0) 208 4952-264 E-Mail more@turck.com Internet www.turck.com
D301087 1211
Loading...