All rights reserved, including those of the translation.
No part of this manual may be reproduced in any form (printed, photocopy, microfilm or any
other process) or processed, duplicated or distributed by means of electronic systems
without written permission of Hans Turck GmbH & Co. KG, Muelheim an der Ruhr.
Subject to alterations without notice
11
rck GmbH, Muelheim an der Ruhr
Page 3
Safety Notes!
Before starting the installation
Disconnect the power supply of the device.
Ensure that devices cannot be accidentally restarted.
Verify isolation from the supply.
Earth and short circuit.
Cover or enclose neighboring units that are live.
Follow the engineering instructions (AWA) of the device concerned.
Only suitably qualified personnel in accordance with EN 50 110-1/-2 (VDE 0 105 Part 100) may
work on this device/system.
Before installation and before touching the device ensure that you are free of electrostatic
charge.
The functional earth (FE) must be connected to the protective earth (PE) or to the potential equa-
lization. The system installer is responsible for implementing this connection.
Connecting cables and signal lines should be installed so that inductive or capacitive interfe-
rence do not impair the automation functions.
Install automation devices and related operating elements in such a way that they are well
protected against unintentional operation.
Suitable safety hardware and software measures should be implemented for the I/O interface so
that a line or wire breakage on the signal side does not result in undefined states in the automation devices.
Ensure a reliable electrical isolation of the low voltage for the 24 volt supply. Only use power
supply units complying with IEC 60 364-4-41 (VDE 0 100 Part 410) or HD 384.4.41 S2.
Deviations of the mains voltage from the rated value must not exceed the tolerance limits given
in the specifications, otherwise this may cause malfunction and dangerous operation.
Emergency stop devices complying with IEC/EN 60 204-1 must be effective in all operating
modes of the automation devices. Unlatching the emergency-stop devices must not cause
restart.
Devices that are designed for mounting in housings or control cabinets must only be operated
and controlled after they have been installed with the housing closed. Desktop or portable units
must only be operated and controlled in enclosed housings.
Measures should be taken to ensure the proper restart of programs interrupted after a voltage
dip or failure. This should not cause dangerous operating states even for a short time. If necessary, emergency-stop devices should be implemented.
Wherever faults in the automation system may cause damage to persons or property, external
measures must be implemented to ensure a safe operating state in the event of a fault or
malfunction (for example, by means of separate limit switches, mechanical interlocks etc.).
The electrical installation must be carried out in accordance with the relevant regulations (e. g.
with regard to cable cross sections, fuses, PE).
All work relating to transport, installation, commissioning and maintenance must only be carried
out by qualified personnel. (IEC 60 364 and HD 384 and national work safety regulations).
All shrouds and doors must be kept closed during operation.
1.2Description of Symbols Used..........................................................................................................................1-3
1.3.1Prescribed Use .........................................................................................................................................................................................1-4
1.3.2Notes Concerning Planning /Installation of this Product ........................................................................................................1-4
1.4List of Revisions ...............................................................................................................................................1-5
2.2.2Power Distribution Modules .............................................................................................................................................................. 2-3
2.2.9Shield Connection, 2-Pole for Analog Modules ..........................................................................................................................2-9
3.2BL20 and CANopen..........................................................................................................................................3-5
3.3Electronic data sheet – EDS file ......................................................................................................................3-6
4.3Technical Information .....................................................................................................................................4-4
4.4Technical Data .................................................................................................................................................4-5
4.4.1General Technical Data ........................................................................................................................................................................4-5
4.4.2Structure Diagram of a Gateway.......................................................................................................................................................4-8
4.4.3Technical Data BL20-GW-CANOPEN................................................................................................................................................4-8
4.4.4Technical Data BL20-GWBR-CANOPEN ..........................................................................................................................................4-9
4.5Connections for data cables to BL20-GW-CANOPEN ................................................................................. 4-10
4.5.1Fieldbus connection via SUB-D socket ........................................................................................................................................ 4-10
4.5.2Fieldbus connection through direct wiring............................................................................................................................... 4-10
4.6Connections of the data cables to BL20-GWBR-CANopen ........................................................................ 4-12
4.6.1Fieldbus connection via Open Style connector ....................................................................................................................... 4-12
6.1.2Maximum System Extension ............................................................................................................................................................. 6-2
6.2.2Module Bus Refreshing ........................................................................................................................................................................ 6-4
6.2.3Creating Potential Groups .................................................................................................................................................................. 6-8
6.2.4Protecting the Service Interface on the Gateway ...................................................................................................................... 6-8
6.2.6Direct Wiring of Relay Modules ...................................................................................................................................................... 6-10
6.3Plugging and Pulling Electronics Modules ................................................................................................. 6-11
6.4Extending an Existing Station...................................................................................................................... 6-12
7.1.3Cable Routing Inside and Outside of Cabinets: .......................................................................................................................... 7-2
7.3.2Grounding of Inactive Metal Components................................................................................................................................... 7-5
7.4Shielding of cables.......................................................................................................................................... 7-8
1.3.2Notes Concerning Planning /Installation of this Product......................................................................4
1.4List of Revisions ................................................................................................................................ 5
D301087 1211 - BL20 CANopen1-1
Page 10
About this Manual
1.1Documentation Concept
This manual contains all information about the BL20-gateway for CANopen (BL20-GW-CANOPEN,
BL20-GWBR-CANOPEN).
The following chapters contain a short BL20 system description, a description of the field bus system
CANopen, exact information about function and structure of the BL20 CANopen-gateway as well as all
bus-specific information concerning the connection to automation devices, the maximum system
extension etc.
The bus-independent I/O-modules for BL20 as well as all further fieldbus-independent chapters like
mounting, labelling etc. are described in a separate manual.
BL20 I/O-modules (TURCK-Documentation-No.: English D300717)
Furthermore, the manual contains a short description of the project planning and diagnostics software
for TURCK I/O-systems, the software I/O-ASSISTANT.
D301087 1211 - BL20 CANopen1-2
Page 11
Description of Symbols Used
1.2Description of Symbols Used
Danger
This sign can be found next to all notes that indicate a source of hazards. This can refer to
danger to personnel or damage to the system (hardware and software) and to the facility.
This sign means for the operator: work with extreme caution.
Attention
This sign can be found next to all notes that indicate a potential hazard.
This can refer to possible danger to personnel and damages to the system (hardware and
software) and to the facility.
Note
This sign can be found next to all general notes that supply important information about one
or more operating steps. These specific notes are intended to make operation easier and
avoid unnecessary work due to incorrect operation.
D301087 1211 - BL20 CANopen
1-3
Page 12
About this Manual
1.3Overview
This manual includes all information necessary for the prescribed use of BL20 products. It has been
specially conceived for personnel with the necessary qualifications.
1.3.1Prescribed Use
Attention
Please read this section carefully. Safety aspects cannot be left to chance when dealing with
electrical equipment.
Danger
The devices described in this manual must be used only in applications prescribed in this
manual or in the respective technical descriptions, and only with certified components and
devices from third party manufacturers.
Appropriate transport, storage, deployment and mounting as well as careful operating and thorough
maintenance guarantee the trouble-free and safe operation of these devices.
1.3.2Notes Concerning Planning /Installation of this Product
Danger
All respective safety measures and accident protection guidelines must be considered
carefully and without exception.
D301087 1211 - BL20 CANopen1-4
Page 13
List of Revisions
1.4List of Revisions
In comparison to the previous manual edition, the following changes/ revisions have been made:
Table 1-1:
List of revisions
ChapterSubject/Descriptionnewchangeddeleted
5/6BL20 - Communication in CANopen/ Diagnostics -
X
Emergency Frames
→ seperate manual D301230
8BL20-Approvals for Zone 2/ Division 2
X
→ seperate manual D301255
Note
The publication of this manual renders all previous editions invalid.
A complete BL20 station counts as one station on the bus and therefore occupies one fieldbus address
in any given fieldbus structure. A BL20 station consists of a gateway, power distribution modules and I/
O modules.
The connection to the relevant fieldbus is made via the bus-specific gateway, which is responsible for
the communication between the BL20 station and the other fieldbus stations.
The communication within the BL20 station between the gateway and the individual BL20 modules is
regulated via an internal module bus.
Note
The gateway is the only fieldbus-dependent module on a BL20 station. All other BL20
modules are not dependent on the fieldbus used.
Flexibility
All BL20 stations can be planned to accommodate the exact number of channels to suit your needs,
because the modules are available in block and slice design.
A BL20 station can contain modules in any combination, which means it is possible to adapt the system
to practically all applications in automated industry.
Compactness
The slim design of the BL20 modules (gateway 50.4 mm / 1.98 inch, slice 12.6 mm / 0.49 inch and block
100.8 mm / 3.97 inch) and their low overall height favor the installation of this system in confined
spaces.
Easy to handle
All BL20 modules, with the exception of the gateway, consist of a base module and an electronics
module.
The gateway and the base modules are snapped onto a mounting rail. The electronics modules are
plugged onto the appropriate base modules.
The base modules are designed as terminal blocks. The wiring is secured by tension clamp or screw
connection. The electronics modules can be plugged or pulled when the station is being commissioned
or for maintenance purposes, without having to disconnect the field wiring from the base modules.
D301087 1211 - BL20 CANopen2-2
Page 17
BL20 Components
2.2BL20 Components
For a detailed explanation of the individual BL20 components, please refer to chapter 2 and chapter 4.
The "Appendix" to this manual contains (amongst others) a list of all BL20 components and the
assignment of electronics modules to base modules.
2.2.1Gateways
The gateway connects the fieldbus to the I/O modules. It is responsible for handling the entire process
data and generates diagnostic information for the higher-level master and the software tool
I/Oassistant.
Gateways with integrated power supply
The BL20 gateway BL20-GWBR-CANOPEN offers an integrated power supply unit for feeding the
gateway and the connected I/O modules.
It is not necessary to supply each individual module with a separate voltage
Figure 2-1:
Gateway
BL20-GWBRCANOPEN
Gateways without power supply
Note
The gateways without integrated power supply unit need an additional power supply
module (bus refreshing module) which feeds the gateway an the connected I/O modules.
2.2.2Power Distribution Modules
D301087 1211 - BL20 CANopen
2-3
Page 18
BL20 Philosophy
Figure 2-2:
Power distribution module
The power supply for gateways and I/O modules is fed to the power distribution modules; therefore, it
is not necessary to supply each individual module with a separate voltage.
2.2.3Electronics Modules
Electronics modules contain the functions of the BL20 modules (power distribution modules, digital
and analog input/output modules, and technology modules).
Electronics modules are plugged onto the base modules and are not directly connected to the wiring.
The assignment table in the Section "Ordering Information" of the "Appendix" shows the possible
combinations of electronics and base modules. They can be plugged or pulled when the station is
being commissioned or for maintenance purposes, without having to disconnect the field wiring from
the base modules.
Figure 2-3:
Electronics
module in slice
design
D301087 1211 - BL20 CANopen2-4
Page 19
BL20 Components
Figure 2-4:
Electronics
module in block
design
2.2.4Base Modules
The field wiring is connected to the base modules. These are constructed as terminals in block and slice
designs and are available in the following variations with either tension clamp or screw connections: 2/3-wire (2-channel), 4-wire (2-channel) and 4x 2-/3-wire (4-channel).
The assignment table in the Section "Ordering Information" of the "Appendix" shows the possible
combinations of electronics and base modules.
Figure 2-5:
Base module with
tension clamp
connection
D301087 1211 - BL20 CANopen
2-5
Page 20
BL20 Philosophy
Figure 2-6:
Base module with
screw connection
Figure 2-7:
Base module in
block design
D301087 1211 - BL20 CANopen2-6
Page 21
BL20 Components
2.2.5End Plate
An end plate on the right-hand side physically completes the BL20 station. An end bracket mounted
into the end plate ensures that the BL20 station remains secure on the mounting rail even when
subjected to vibration.
Figure 2-8:
End plate
2.2.6End Bracket
A second end bracket to the left of the gateway is necessary, as well as the one mounted into the end
plate to secure the station.
Figure 2-9:
End bracket
Note
The end plate an the end bracket are delivered together with each gateway.
D301087 1211 - BL20 CANopen
2-7
Page 22
BL20 Philosophy
2.2.7Jumpers
Jumpers (QVRs) are used to bridge a connection level of a 4-wire base module. They can be used to
connect potentials in relay modules (bridging the relay roots); thus considerably reducing the amount
of wiring.
Figure 2-10:
Jumpers
2.2.8Marking Material
Labels: for labeling BL20 electronics modules.
Markers: for colored identification of connection levels of BL20 base modules.
Dekafix connector markers: for numbering the mounting slots on BL20 base modules.
Figure 2-11:
Marking material
D301087 1211 - BL20 CANopen2-8
Page 23
BL20 Components
2.2.9Shield Connection, 2-Pole for Analog Modules
The 2-pole shield connection can be used to connect signal-cable shielding to the base modules of
analog input and output modules. A special tension-clamp operating tool (BL20-ZBW5-2) is required to
mount the shield connection onto the base module.
– Service Data Objects (SDOs).............................................................................................................3
– Process Data Objects (PDOs) ...........................................................................................................4
– Special Function Objects ..................................................................................................................4
3.2BL20 and CANopen ........................................................................................................................... 5
3.3Electronic data sheet – EDS file ......................................................................................................... 6
D301087 1211 - BL20 CANopen3-1
Page 26
Short description of CANopen
3.1CANopen
Note
The following description of CANopen is an excerpt from the homepage of CiA (CAN in
Automation), the international users’ and manufacturers’ organization for CAN.
3.1.1General
CANopen is an open, non-proprietary network protocol. It consists of a profile family, based on a
communication profile and several device profiles. The CANopen communication profile is
standardized as CiA DS-301 (Application Layer and Communication Profile).
The CANopen device profile for I/O-modules has been published as CiA DS-401 (Device Profile for I/OModules).
CANopen is based on the following standards:
ISO 11 898 (Physical and Data Link Layer)
Layers 1 and 2 of the ISO/OSI communication model
CiA DS-301 (Application Layer and Communication Profile) C ANopen communication profile
CiA DS-302 (Framework for Programmable CANopen Devices) CANopen Network Management
NMT
CiA DS-401 (Device Profile for I/O-modules)
CiA DS-406 (Device Profile for Encoders) CANopen device profile for counter modules
CiA DS-102 (CAN Physical Layer for Industrial Applications) General application in the field sector
(connectors and bit rates) on the basis of ISO 11898
D301087 1211 - BL20 CANopen3-2
Page 27
CANopen
3.1.2Communication
The lower layers of CANopen are defined according to the ISO-OSI model in the ISO 11898 standard.
Communication between the individual nodes is made by transmitting "Telegrams".
4 different types of telegram message are defined for CANopen:
Network management messages
Service data objects SDO
Process data objects PDO
Predefined messages
Network Management Messages
Network management messages are used in the network to control the nodes and their operating
states. This type of message makes it possible, for instance, to configure the data transmission
mechanism of a node.
The Network Management objects include Boot-up message, Heartbeat protocol and NMT message.
Boot-up message, Heartbeat and Node Guarding are implemented as single CAN frames with 1-byte
data field.
The NMT message is mapped to a single CAN frame with a data length of 2 byte. Its identifier is 0. The
first byte contains the command specifier and the second contains the Node-ID of the device that must
perform the command (in the case of Node-ID 0 all nodes have to perform the command). The NMT
message transmitted by the NMT master forces the nodes to transit to another NMT state. The
CANopen state machine specifies the states Initialization, Pre-Operational, Operational and Stopped.
After power-on, each CANopen device is in the state Initialization and automatically transits to the state
Pre-operational. In this state, transmission of SDOs is allowed. If the NMT master has set one or more
nodes into the state Operational, they are allowed to transmit and to receive PDOs. In the state Stopped
no communication is allowed except that of NMT objects.
The state Initialization is divided into three sub-states in order to enable a complete or partial reset of a
node. In the sub-state Reset Application the parameters of the manufacturer-specific profile area and
the standardized device profile area are set to their power-on values. In the sub-state Reset
Communication the parameters of the communication profile area are set to their power-on values.
The third sub-state is initializing, which a node enters automatically after power-on. Power-on values
are the last stored parameters.
The Heartbeat protocol is for error control purposes and signals the presence of a node and its state.
The Heartbeat message is a periodic message of the node to one or several other nodes. It indicates that
the sending node is still working properly.
A device sends the Boot-up message to indicate to the NMT master that it has reached the state Preoperational. This occurs whenever the device initially boots-up but also after a power-out during
operation. The Boot-up message has the same identifier as the Heartbeat object, however, its data
content is zero.
Service Data Objects (SDOs)
A Service Data Object (SDO) reads from entries or writes to entries of the Object Dictionary.
The SDO transport protocol allows transmitting objects of any size. The first byte of the first segment
contains the necessary flow control information including a toggle bit to overcome the problem of
doubly received CAN frames. The next three bytes of the first segment contain index and sub-index of
the Object Dictionary entry to be read or written. The last four bytes of the first segment are available
for user data. The second and the following segments (using the very same CAN identifier) contain the
control byte and up to seven bytes of user data. The receiver confirms each segment or a block of
segments, so that a peer-to-peer communication (client/server) takes place.
D301087 1211 - BL20 CANopen
3-3
Page 28
Short description of CANopen
Process Data Objects (PDOs)
Process Data Objects (PDOs) are mapped to a single CAN frame using up to 8 bytes of the data field to
transmit application objects. Each PDO has a unique identifier and is transmitted by only one node, but
it can be received by more than one (producer/consumer communication).
PDO transmissions
PDO transmissions may be driven by an internal event, by an internal timer, by remote requests and by
the Sync message received:
Event- or timer-driven:
An event (specified in the device profile) triggers message transmission. An elapsed timer
additionally triggers the periodically transmitting nodes.
Remotely requested:
Another device may initiate the transmission of an asynchronous PDO by sending a remote
transmission request (remote frame).
Synchronous transmission:
In order to initiate simultaneous sampling of input values of all nodes, a periodically transmitted
Sync message is required. Synchronous transmission of PDOs takes place in cyclic and acyclic
transmission mode. Cyclic transmission means that the node waits for the Sync message, after
which it sends its measured values. Acyclically transmitted synchronous PDOs are triggered by a
defined application-specific event.
Special Function Objects
CANopen also defines three specific protocols for synchronization, emergency indication, and timestamp transmission.
Synchronization object (Sync)
The Sync Object is broadcast periodically by the Sync Producer. The time period between Sync
messages is defined by the Communication Cycle Period, which may be reset by a configuration
tool to the application devices during the boot-up process. There can be a time jitter in transmission
by the Sync Producer due to some other objects with higher prior identifiers or by one frame being
transmitted just before the Sync message. The Sync message is mapped to a single CAN frame with
the identifier 128 by default. The Sync message does not carry any data.
Emergency object (Emcy)
The Emergency message is triggered by the occurrence of a device internal error situation and are
transmitted from an Emergency producer on the concerned application device. This makes them
suitable for interrupt type error alerts. An Emergency message is transmitted only once per ‘error
event’. As long as no new errors occurs on a device, no further Emergency message can be
transmitted. Zero or more Emergency consumers may receive these. The reaction of the Emergency
consumer is application-specific. CANopen defines several Emergency Error Codes to be
transmitted in the Emergency message, which is a single CAN frame with 8 data byte.
Time stamp object (Time)
By means of Time-Stamp, a common time frame reference is provided to application devices. It
contains a value of the type Time-of-Day. This object transmission follows the producer/consumer
push model. The associated CAN frame has the pre-defined identifier 256 and a data field of 6-byte
length.
D301087 1211 - BL20 CANopen3-4
Page 29
BL20 and CANopen
3.2BL20 and CANopen
BL20 supports the following CANopen functions:
SDO transfer, any length of information
Emergency object
Sync frame evaluation
Event-driven PDOs
Synchronous PDOs (clock-synchronous)
Remote-requested PDO/polling
D301087 1211 - BL20 CANopen
3-5
Page 30
Short description of CANopen
3.3Electronic data sheet – EDS file
CANopen nodes are embedded in the CANopen structure by the help of a standardized EDS file
(Electronic Data Sheet).
The EDS file lists all necessary Objects with their corresponding Sub-indices and the matching entries.
The latest version of a particular EDS file can be downloaded directly from the TURCK Homepage
www.turck.com.
4.10.1Diagnostic Messag es via LEDs .............................. ... ....................................... ... ... .... ... ... ..................20
D301087 1211 - BL20 CANopen4-1
Page 32
BL20 - Gateway for CANopen
4.1Introduction
This chapter contains a description of BL20 gateways for the standardized fieldbus CANopen. The
chapter is divided up as follows: a description of functions, general and specific technical data, a
description of addressing and status displays.
Attention
Please note, SWIRE-modules can only be used with the gateways BL20-GW-CANOPEN with
firmware version ≥ 4.02 and BL20-GWBR-CANOPEN with firmware version ≥ 2.02.
Danger
The behavior of the analog inputs is now adapted to the actual CANopen standard DS401.
The firmware versions ≥ 4.02 for BL20-GW-CANOPEN and version ≥ 2.02 for BL20-GWBRCANOPEN are thus not compatible with older firmware versions relating to the behavior of
the analog inputs.
D301087 1211 - BL20 CANopen4-2
Page 33
Function
4.2Function
The BL20 gateways enable BL20 modules to operate on CANopen. The gateway is the connection
between the BL20 modules and a CANopen host system. It regulates the process data between the
I/O level and the fieldbus and generates diagnostic data for the higher-level host system.
Information is made available to the software tool I/O-ASSISTANT via the service interface.
D301087 1211 - BL20 CANopen
4-3
Page 34
BL20 - Gateway for CANopen
ERR BUS
GWBR-
CANOPEN
CAN H
SHLD
CAN L
GND
CAN H
SHLD
CAN L
GND
H
Bit Rate
L
1
2
3
4
A
B
C
D
E
F
G
I
H
J
ERR BUS
GWBR
CANopen
H
Bit Rate
L
1
2
3
4
GND
CAN_L
Shield
CAN_H
A
B
C
D
E
F
G
H
I
4.3Technical Information
Figure 4-1:
BL20-GWCANOPEN
A Service interface
B Type designa-
tion
C LEDs for
module bus
D DIP-switch for
transfer rate
E Rotary encod-
ing switch for
Node-ID
F SET button
G CANopen, SUB-
D plug
H CANopen,
direct wiring
I LEDs for
CANopen
J CANopen, SUB-
D socket
Figure 4-2:
BL20-GWBRCANOPEN
A Service interface
B Type
designation
C LEDs for
module bus
D DIP-switch for
transfer rate
E Rotary encod-
ing switch for
Node-ID
F SET button
G Screw terminals
for field supply
and system supply
H CANopen,
direct wiring
I Open Style con-
nector
D301087 1211 - BL20 CANopen4-4
Page 35
Technical Data
4.4Technical Data
4.4.1General Technical Data
Relating to a Station
Note
The auxiliary power supply must comply with the stipulations of SELV (Safety Extra Low
Voltage) according to IEC 364-4-41.
Table 4-1:
General technical
data (station)
Supply voltage/ auxiliary voltage
Nominal value (provision for other modules)24 V DC
Permissible rangeaccording to EN 61131-2 (18 to 30 V DC)
Residual rippleaccording to EN 61131-2
Potential isolationYes, via optocoupler
Ambient conditions
Ambient temperature
–T
–T
0 to +55 °C / 32 to 131 °F
Ambient
-25 to +85 °C / 13 to 185 °F
Store
Relative humidity according to IEC 61 131-2/ EN 50 178
Climatic testsaccording to IEC 61131-2
Noxious gas– SO
2
:
10 ppm (rel. humidity < 75 %, non-condensing)
S:
–H
2
1.0 ppm (rel. humidity < 75 %, non-condensing)
Resistance to vibration according to IEC 61131-2
10 to 57 Hz, Constant
amplitude 0.075 mm / 0.003 inch, 1g
57 to 150 Hz, Constant acceleration 1 gYes
Mode of vibrationFrequency sweeps with a change in speed of
Period of oscillation20 frequency sweeps per axis of coordinate
Shock resistant according to IEC 68-2-2718 shocks, sinusoidal half-wave 15 g peak value/
Resistance to repetitive shock according to
IEC 68-2-29
Topple and fall according to IEC 68-2-31 and free fall according to IEC 68-2-32
Weight< 10 kg
D301087 1211 - BL20 CANopen
Yes
1 Octave/min
11 ms, in each case in +/- direction per space
coordinate
1 000 shocks, half-sinus 25 g peak value/6 ms, in
each case in +/- direction per space coordinate
4-5
Page 36
BL20 - Gateway for CANopen
Height of fall1.0 m / 39.37 inch
Weight10 to 40 kg
Height of fall0.5 m / 19.69 inch
Test runs7
Device with packaging, electrically tested printed-circuit board
Electromagnetic compatibility (EMC) according to EN 50 082-2 (Industry)
Static electricity according to EN 61 000-4-2
– Discharge through air (direct)8 kV
– Relay discharge (indirect)4 kV
Electromagnetic HF fields according to EN 61
000-4-3 and ENV 50 204
Conducted interferences induced by HF fields
according to EN 61 000-4-6
Fast transients (Burst) according to EN 61 000-4-4
Interference criteria A: unrestricted operation,
normal operating behavior
Interference criteria B: temporary interference,
normal operation possible
Emitted interference according to EN 50 081-2
(Industry)
Reliability
Operational life MTBF min. 120000 h
Electronic modules pull/
plug cycles
Tests according to EN 61 131-2
ColdDIN IEC 68-2-1, temperature -25 °C / -13 °F,
10 V/m
10 V
1 kV
2 kV
according to EN 55 011 Class A, Group 1
20
duration 96 h; not in use
Dry heatDIN IEC 68-2-2, temperature +85 °C / 185 °F,
duration 96 h; device not in use
Damp heat, cyclicDIN IEC 68-2-30, temperature +55 °C / 131 °F,
duration 2 cycles every 12 h; device in use
Temperature changeDIN IEC 68-2-14, temperature 0 to +55 °C / 32 to
131 °F, duration 2 cycles, temperature change per
minute; device in use
Pollution severity according to IEC 664 (EN 61 131-2)
Protection class according to IEC 529IP20
D301087 1211 - BL20 CANopen4-6
Page 37
Technical Data
Danger
This device can cause radio disturbances in residential areas and in small industrial areas
(residential, business and trading). In this case, the operator can be required to take
appropriate measures to suppress the disturbance at his own cost.
Approvals
Table 4-2:
Approvals
Table 4-3:
Technical data for
base modules
CE
CSA
UL
Base Modules
Protection classIP 20
Measurement data according to VDE 0611 Part 1/8.92/ IEC 947-7-1/1989
Insulation stripping length8 mm / 0.32 inch
Max. wire range0.5 to 2.5 mm
2
/ 0.0008 to 0.0039 inch2 / 20 to
12 AWG
Crimpable wire
2
"e” solid core H 07V-U0.5 to 2.5 mm
/ 0.0008 to 0.0039 inch2 / 20 to
12 AWG
2
"f” flexible core H 07V-K0.5 to 1.5 mm
/ 0.0008 to 0.0023 inch2 / 20 to
16 AWG
2
"f” with ferrules according to
DIN 46228/1 (ferrules crimped gas-tight)
0.5 to 1.5 mm
16 AWG
/ 0.0008 to 0.0023 inch2 / 20 to
Plug gauge according to
A1
IEC 947-1/1988
TOP connection technologyTension clamp or screw connection
D301087 1211 - BL20 CANopen
4-7
Page 38
BL20 - Gateway for CANopen
Fieldbus
(External)
Service
interface
External RAM
External
ROM flash
Module bus
(Internal)
Controller
– internal RAM
– WDG
– CAN-Ctr.
4.4.2Structure Diagram of a Gateway
The BL20 CANopen gateway has the following structure:
Figure 4-3:
Gateway structure
4.4.3Technical Data BL20-GW-CANOPEN
Table 4-4:
Technical data
BL20-GWCANOPEN
DesignationValue
Supply voltage(as per EN 61131-2)
Nominal value (supply from
5 V DC (4.8 to 5.2 V DC)
bus refreshing module)
Restriction on
EN 61131-2
The supply energy required to bridge a supply
interruption up to 10 ms is not stored. Please
secure the U
for BL20-BR-24VDC-D modules
sys
by using an appropriate power supply unit!
Current drawn from the module bus
Without service/without fieldbus≈ 280 mA
Without service/with fieldbus (1 Mbps)≈ 410 mA
With service/without fieldbus≈ 300 mA
Maximum≈ 350 mA
Dimensions
Width/length/height (mm)50.6 x 114.8 x 74.4 mm
Service
ConnectionsPS/2 socket
Fieldbus terminations1x 9-pole SUB-D socket,
1x 9-pole SUB-D plug, 2 x tension spring
connector type LPZF, 5.08, 5-pole
Fieldbus shielding connectionvia BL20-SCH-1
Transfer rate10, 20, 50, 125, 250, 500, 800 and 1000 kbps
Fieldbus terminationSUB-D plug connector or external resistors
2 rotary hex encoder switches with labeling for
the Node-ID setting.
D301087 1211 - BL20 CANopen4-8
Page 39
Technical Data
4.4.4Technical Data BL20-GWBR-CANOPEN
Table 4-5:
Technical data
BL20-GWBRCANOPEN
DesignationValue
Supply
Field supply
U
Nominal value (range)24 V DC (18 to 30 V DC)
L
I
max. field current 10 A
L
Isolation voltage (U
to FE)
U
L
to U
L
/ UL to fieldbus/
SYS
500V
eff
Connections2-pole screw terminal
System supply
U
nominal value (range)24 V DC (18 to 30 V DC)
SYS
I
(for IMB = 1.2 A/U
SYS
I
(supply to the module bus stations)1.2 A
MB
Isolation voltage (U
to fieldbus/U
U
SYS
= 18 V DC)max. 900 mA
SYS
500V
SYS
to UL/
SYS
to FE)
eff
Connections2-pole screw terminal
Physical interfaces
Fieldbus
Transfer rate10 kbps to 1 Mbps
Isolation voltage (fieldbus to U
fieldbus to U
/fieldbus to FE)
L
SYS
/
500V
eff
Fieldbus connectionsSocket:
MSTBV 2,5/5-GF-5.08 GY AU/Phoenix Contact
Plug:
TMSTBP 2,5/5-STF-5.08 AB GY AU/Phoenix
Contact (included in delivery)
Fieldbus shielding connectionVia connector
Node-ID setting2 rotary decimal encoding switches
Service
ConnectionsPS/2 socket
Danger
This device can cause radio disturbances in residential areas and in small industrial areas
(residential, business and trading). In this case, the operator can be required to take
appropriate measures to suppress the disturbance at his own cost.
D301087 1211 - BL20 CANopen
4-9
Page 40
BL20 - Gateway for CANopen
54321
9678
4.5Connections for data cables to BL20-GW-CANOPEN
4.5.1Fieldbus connection via SUB-D socket
SUB-D connectors are provided for communication with the BL20-GW-CANOPEN gateway through the
CANopen fieldbus.
The passive bus termination must be applied externally if the BL20 gateway is the last station in the bus
structure. This external application can be implemented either through separate termination resistors
or through a special SUB-D plug which has an integrated bus termination.
The pin assignments for the plug and socket are identical – the socket is shown as an example:
Figure 4-4:
SUB-D socket on
the gateway (top
view)
Table 4-6:
Pin assignments
for gateway SUBD plug/socket
A The shielding of
the fieldbus is
connected
through the
metal housing
of the SUB-D
connector and
the contact
with the mounting rails (see
page 4-11)
Pin No.DesignationMeaning
1not used
2CAN_Linverted data signal (dominant
3CAN_GNDground (optional for CAN data
4not used
5(CAN_SHLD)
6(GND)
7CAN_Hnon-inverted data signal
8not used
9(CAN_V+)
4.5.2Fieldbus connection through direct wiring
For making connections to the fieldbus you can choose between a SUB-D connection and direct wiring.
Direct wiring of the BL20-GW-CANOPEN to the CANopen fieldbus can be made through the two
terminal blocks with tension spring connectors.
low)
signals)
A
(dominant high)
D301087 1211 - BL20 CANopen4-10
Page 41
Connections for data cables to BL20-GW-CANOPEN
The passive bus termination must be applied externally if the BL20 gateway is the last station in the bus
structure.
Table 4-7:
List of connecting
leads for direct
wiring
Figure 4-5:
Shielding connection for an BL20GW-CANOPEN
DesignationMeaning
CAN_LInverted data signal (dominant low)
GNDGround (optional)
SHLDShielding (see below)
CAN_HNon-inverted data signal (dominant high)
Attention
If the gateway is wired up directly, then the bus connection must be shielded (e.g. with the
help of a BL20-SCH-1 clamp).
Attention
No compensating current should flow through the shielding.
To achieve this, a reliable system of equipotential bonding must be installed.
4.6Connections of the data cables to BL20-GWBR-CANopen
4.6.1Fieldbus connection via Open Style connector
An Open Style Connector (5-pole) is available for connecting the BL20-GWBR-CANOPEN to the
CANopen fieldbus.
The passive bus termination must be applied externally if the BL20 gateway is the last station in the bus
structure.
Table 4-8:
Pin assignment
for the socket
Figure 4-6:
Open Style
connector
(female/top)
Figure 4-7:
Open Style
connector
(female/bottom)
1,2 - red
3,4 - white CAN_HNon-inverted data signal
(dominant high)
5,6 - greyShield, Shielding braid, not insulated
7,8 - blueCAN_LInverted data signal
(dominant low)
9,10 - blackGNDGround reference (optional)
Figure 4-8:
Open Style
connector (male)
D301087 1211 - BL20 CANopen4-12
Page 43
Connections of the data cables to BL20-GWBR-CANopen
Figure 4-9:
Shielding connection for an
BL20-GWBRCANOPEN
Attention
No compensating current should flow through the shielding.
To achieve this, a reliable system of equipotential bonding must be installed.
D301087 1211 - BL20 CANopen
4-13
Page 44
BL20 - Gateway for CANopen
43
16
25
54321
9678
12345
6987
4.6.2Service Interface Connection
The following cable can be used to connect the service interface (female PS/2 connector) to a PC for the
purpose of using I/O-ASSISTANT (project planning and diagnostic software).
special I/O-ASSISTANT-connection cable from TURCK (IOASSISTANT-ADAPTERKABEL-BL20/BL67;
Ident-no.: 6827133)
Connection with I/O-ASSISTANT-Connection Cable
Figure 4-10:
BL20-gateway
connected to PC
via special cable
A SUB-D socket
B BL20 connecting
cable
C PS/2 plug
Figure 4-11:
PS/2 male
connector on the
connection cable
to the gateway
(top view)
Figure 4-12:
9-pole SUB-D
female connector
on the cable for
connecting to PC
(top view)
Table 4-9:
Pin assignments
for PS/2 and SUBD interfaces
The I/O-ASSISTANT-cables have a PS/2 male connector (connection for female connector on gateway)
and a SUB-D female connector (connection for male connector on PC).
PinBL20 gateway PS/2
SUB-D interface on PC Pin
socket
1+5 V GwDTR, DSR4, 6
2GNDGND5
3–––
4TxDRxD2
5/CtrlModeRTS7
6RxDTxD3
D301087 1211 - BL20 CANopen4-14
Page 45
Setting the bit transfer rate through DIP-switches
4.7Setting the bit transfer rate through DIP-switches
The BL20 gateway can communicate with other CANopen nodes at the following transfer rates:
10 kbps 250 kbps
20 kbps 500 kbps
50 kbps 800 kbps
125 kbps 1000 kbps
The default transfer rate is 125 kbps.
The transfer rate can be set through the DIP-switches under the cover of the BL20 gateway.
Figure 4-13:
DIP-switch to set
the transfer rate
Note
All the nodes in a CANopen network must be set to the same transfer rate.
To set a bit transfer rate that is supported by CANopen, proceed as follows:
Switch off the supply voltage for the BL20 gateway.
D301087 1211 - BL20 CANopen
4-15
Page 46
BL20 - Gateway for CANopen
Set the DIP-switches for the required transfer rate according to the following table:
Table 4-10:
Setting the
transfer rate
Bit transfer rate (kbps)DIP-switches (setting)
1234
1 0000000
8001000
5000100
2501100
1250010
501010
200110
101110
reservedxxx1
Note
The DIP-switches are in the “1” position when they are set to the right, as viewed from the
front.
Switch on the supply voltage for the gateway again
D301087 1211 - BL20 CANopen4-16
Page 47
Node-ID Setting
4.8Node-ID Setting
A Node-ID is assigned to every BL20 gateway in the CANopen structure.
The setting for the Node-ID of the BL20-GW-CANOPEN in a CANopen structure is made through the two
rotary hex encoding switches. The setting for the Node-ID of the BL20-GWBR-CANOPEN is made
through the two rotary decimal encoding switches. The switches can be found beneath a cover, below
the service interface.
The BL20 gateway can be used as a CANopen node at any point in the bus structure.
Figure 4-14:
Rotary hex
encoding switch
for the CANopen
address setting of
the BL20-GWCANOPEN
Attention
If the BL20 gateway is used as the the last node in the bus communication, then a special bus
connector with a built-in or add-on termination resistor is absolutely necessary!
Attention
A maximum of 127 Node-IDs (1 to 127) can be assigned in a
CANopen structure. Each Node-ID can only be assigned once in the complete bus structure.
The Node-ID 000 must not be assigned. It is reserved for telegrams that are directed to all the
other bus nodes.
The rotary encoding switches are marked with H for High (more significant digit) and L für Low (less
significant digit).
BL20-GW-CANOPEN:
The L switch is used to set L × 16
The H switch is used to set L × 16
BL20-GWBR-CANOPEN:
The L switch is used to set L × 10
The H switch is used to set L × 10
0
(L = 0 to F).
1
(H = 0 to F).
0
(L = 0 to 9).
1
(H = 0 to 9).
Note
The NODE-ID switch on the BL20-GWBR-CANOPEN can be used to assign Node-IDs from 1 to
99!
D301087 1211 - BL20 CANopen
4-17
Page 48
BL20 - Gateway for CANopen
Note
After setting the Node-ID, the protective cover over the switches must be closed again.
See chapter 6
Note
BL20 does not support the assignment of Node-IDs across the bus network.
, Maximum System Extension, page 6-2.
D301087 1211 - BL20 CANopen4-18
Page 49
Acceptance of the BL20 Station Configuration
4.9Acceptance of the BL20 Station Configuration
When making a new configuration of the BL20 station or an alteration of the existing station structure
(“Module list”), the current configuration must be accepted in the CANopen mirror of the BL20 gateway.
This is done through the configuration button between the two rotary encoding switches.
Note
The green "IOs" LED indicates that the current BL20 configuration matches the stored
reference module list.
Pressing the set button with a pointed object for at least 2 seconds saves the current station
configuration in non-volatile memory. A hardware reset will then be carried out automatically. With this
reset, all the CANopen parameters will be restored to their default values, if the newly saved
configuration is different to the old one.
Attention
When saving the BL20 configuration, all the CANopen objects must be parameterized again,
if their parameter values differ from the default values. The complete parameterization of the
station must subsequently be reloaded into the BL20 station.
The actuation of the button is indicated by a rapid (4 Hz) green blinking of the "IOs" LED. After 2
seconds, the LED changes to yellow blinking at 4 Hz, thus indicating that the station configuration is
being saved. When the storage procedure is completed, the LED changes to a continuous green light.
The gateway transmits the following diagnostics: the status of the BL20 station, the communication via
the internal module bus, the communication to CANopen and the status of the gateway.
Diagnostic messages are displayed in two ways:
via individual LEDs
via the software of the respective host system or the software-tool I/O-ASSISTANT
4.10.1Diagnostic Messages via LEDs
Every BL20 gateway displays the following statuses via LEDs:
2 LEDs for module bus communication (module bus LEDs):
GW and IOs
2 LEDs for CANopen communication (fieldbus LEDs):
ERR and Bus
The LED diagnoses shown below apply to both gateway versions:
BL20-GW-CANOPEN
BL20-GWBR-CANOPEN
An additional diagnosis indication is shown for the BL20-GWBR-CANOPEN.
Table 4-11:
LED indicators
LEDStatusMeaningRemedy
GWOFFCPU not supplied.
Green5 V DC operating voltage is present;
firmware is active; gateway is ready
for operation and transfer
GW: green,
Firmware not activeReload the firmware!
flashing,
1Hz
IOs: red
Green,
flashing,
Firmware active, gateway hardware
is defect
4 Hz
Additional diagnosis indication for BL20-GWBR-CANOPEN
-
Replace the gateway.
GWgreen,
blinking, 1
Hz
: undervoltage or overvoltage
U
SYS
: undervoltage
U
L
Check that the supply voltage is
within the permissible range.
D301087 1211 - BL20 CANopen4-20
Page 51
Status Indicators/ Diagnostic Messages Gateway
Table 4-11:
LED indicators
LEDStatusMeaningRemedy
IOs-CPU not supplied.Check the voltage supply.
GreenModule bus is running,
the configured module bus station
corresponds to the physically
connected station, communication
is active.
Green,
flashing,
Station is in the
I/O-ASSISTANT Force Mode.
Deactivate the
I/O-ASSISTANT Force Mode.
1 Hz
Red and
LED "GW"
off
Controller is not ready, V
not within the required range →
possible reasons:
– too many modules connected to
level is
CC
– Check wiring at the gateway and
the voltage supply.
– Dismount modules
– Replace the gateway.
the gateway
–short circuit in connected module
– hardware error in
–gateway
Red
flashing,
1 Hz
Non-adaptable modification of the
physically connected station.
– Compare the planned BL20 station
with the physical station.
– Check the physical station for
defective or incorrectly fitted
electronics modules.
Red
flashing,
4Hz
Red/green
flashing,
1Hz
RedShort circuit or overload at sensor
no module bus communicationAt least one module has to be
plugged and has to be able to
communicate with the gateway.
Adaptable modification of the
physically connected station;
data transfer possible
Check the physical station for
pulled or new but not planned
modules.
Automatic restart when
supply → sensor supply is switched
debugging.
off
OffNo voltage supply.Check the wiring of the voltage
supply.
D301087 1211 - BL20 CANopen
4-21
Page 52
BL20 - Gateway for CANopen
Table 4-11:
LED indicators
LEDStatusMeaningRemedy
ERROffNo errors in communication
–
between the BL20-CANopen
gateway and other CANopen nodes
RedFaulty or interrupted
communication between BL20CANopen gateway and other
CANopen.
Possible causes:
The arrangement of the I/O-modules within a BL20 station can basically be chosen at will.
Nevertheless, it can be useful with some applications to group certain modules together.
Note
The mixed usage of base modules with screw connections and base modules with tension
clamp connections requires a further power supply module to be mounted. Thereby, it must
be ensured that the base modules are fitted with the same connection technology (screw or
tension clamp) as the power supply module.
6.1.1Complete Planning
The planning of a BL20 station should be thorough to avoid faults and increase operating reliability.
Attention
If there are more than two empty slots next to one another, the communication is interrupted
to all following BL20 modules.
6.1.2Maximum System Extension
A BL20 station can consist of a gateway and a maximum of 74 modules in slice design (equivalent to
1 m in length of mounting rail including the end bracket and end plate). The maximum number of
modules is less when using block modules (1 block module is equivalent to 8 modules in slice design).
D301087 1211 - BL20 CANopen6-2
Page 57
Random Module Arrangement
The following overview shows the maximum number of channels possible, on condition that the entire
station is made up of that respective type of channel only:
Table 6-1:
Maximum system
extension
A plus 1 Bus Ref-
reshing module
B plus 2
Bus Refreshing
modules
C plus 3
Bus Refreshing
modules
ChannelsModules
TypeMax. no.TypeMax. no.
72 B
B
Digital inputs288BL20-4DI-24VDC-P72
Digital outputs288BL20-4DO-24VDC-
0.5A-P
Analog inputs, current126BL20-2AI-I(0/4...20MA)63 C
Analog inputs, voltage126BL20-2AI-U(-10/
63
C
0...+10VDC)
Analog inputs, voltage/
112BL20-4AI-U/I28
A
current
Analog inputs, PT /Ni126BL20-2AI-PT/NI-2/363
Analog inputs,
126BL20-2AI-THERMO-PI63
C
C
Thermocouple
Analog outputs,
126BL20-2AO-I(0/4...20MA) 63
C
current
Analog inputs, voltage126BL20-2AO-U(-10/
63
C
0...+10VDC)
Counter31BL20-1CNT-24VDC31 A
RS23231BL20-1RS23231 A
RS485/42231BL20-1RS485/422 31 A
SSI31BL20-1SSI31 A
SWIRE16BL20-E-1SWIRE16 A
Further limitations can be placed on the maximum possible number of BL20 modules by the use of the
Power Feeding modules BL20-PF-24VDC-D or BL20-PF-120/230VAC-D; these being used either for
creating potential groups or by insufficient field supply.
Attention
Ensure that a sufficient number of Power Feeding or Bus Refreshing modules are used if the
system is extended to its maximum.
Note
If the system limits are exceeded, the software I/O-ASSISTANT gen-erates an error message
when the user activates the "Station → Verify" command.
D301087 1211 - BL20 CANopen
6-3
Page 58
Guidelines for Station Planning
6.2Power Supply
6.2.1Gateway Supply
Note
On a BL20 station including a gateway without integrated power supply unit, the first module
to be mounted after the gateway is a Bus Refreshing module with either a BL20-P3x-SBB or a
BL20-P4x-SBBC base module with tension clamp or screw connection.
6.2.2Module Bus Refreshing
The number of BL20 modules that can be supplied by the gateway or a separate Bus Refreshing module
via the internal module bus depends on the respective nominal current consumption of the individual
modules on the module bus.
Attention
The sum total of the nominal current consumption of the connected BL20 modules must not
exceed 1.5 A.
The following examples show the calculation for the required number of Bus Refreshing modules:
Example 1:
The BL20 station consists of 20 BL20-1AI-I(0/4...20MA) modules. The number of additional Bus
Refreshing modules required is calculated as follows:
Gateway430 mA
20 BL20-1AI-I(0/4...20MA) 20 x 41 mA820 mA
Total:1250 mA
Maximum permissible current via module bus: 1 500 mA
The calculation shows that no further Bus Refreshing module is required.
D301087 1211 - BL20 CANopen6-4
Page 59
Power Supply
Example 2:
The BL20 station comprises 15 BL20-1AI-U(-10/0...+10VDC) modules, 10 BL20-2AO-U(-10/0...+10VDC)
modules, 10 BL20-2DI-24VDC-P modules and 5 BL20-2DO-24VDC-0.5A-P modules. The required
number of Bus Refreshing modules is calculated as follows:
Gateway430 mA
15 BL20-1AI-U(-10/0...+10VDC)15 x 41 mA615 mA
10 BL20-2AO-U(-10/0...+10VDC)10 x 43 mA430 mA
10 BL20-2DI-24VDC-P10 x 28 mA280 mA
5 BL20-2DO-24VDC-0.5A-P5 x 32 mA160 mA
Total:1 915 mA
Table 6-2:
Nominal current
consumption of
the BL20 modules
on the module bus
Maximum permissible current via module bus:1 500 mA
The calculation shows that an additional/further Bus Refreshing module is required at the latest
following the last BL20-2AO module. This Bus Refreshing module is sufficient to supply the remaining
modules.
Note
The power requirements of the BL20 gateway is to be considered when calculating the
required number of Bus Refreshing modules.
The following table offers an overview of the nominal current consumption of the individual BL20
modules on the module bus:
ModuleSupplyNominal current consumption
Gateway 1 500 mA≤ 430 mA
BL20-PF-24VDC-D28 mA
BL20-PF-120/230VAC-D25 mA
BL20-2DI-24VDC-P28 mA
BL20-2DI-24VDC-N28 mA
BL20-2DI-120/230VAC28 mA
BL20-4DI-24VDC-P29 mA
BL20-4DI-24VDC-N28 mA
BL20-E-8DI-24VDC-P15 mA
BL20-16DI-24VDC-P45 mA
D301087 1211 - BL20 CANopen
6-5
Page 60
Guidelines for Station Planning
Table 6-2:
Nominal current
consumption of
the BL20 modules
on the module bus
ModuleSupplyNominal current consumption
BL20-E-16DI-24VDC-P15 mA
BL20-32DI-24VDC-P30 mA
BL20-1AI-I(0/4...20MA)41 mA
BL20-2AI-I(0/4...20MA)35 mA
BL20-1AI-U(-10/0...+10VDC)41 mA
BL20-2AI-U(-10/0...+10VDC)35 mA
BL20-2AI-PT/NI-2/345 mA
BL20-2AI-THERMO-PI45 mA
BL20-4AI-U/I50 mA
BL20-2DO-24VDC-0.5A-P32 mA
BL20-2DO-24VDC-0.5A-N 32 mA
BL20-2DO-24VDC-2A-P33 mA
BL20-4DO-24VDC-0.5A-P30 mA
BL20-E-8DO-24VDC-P15 mA
BL20-16DO-24VDC-0.5A-P120 mA
BL20-E-16DO-24VDC-P25 mA
BL20-32DO-24VDC-0.5A-P30 mA
BL20-1AO-I(0/4...20MA)39 mA
BL20-2AO-I(0/4...20MA)40 mA
BL20-2AO-U(-10/0...+10VDC)43 mA
BL20-2DO-R-NC28 mA
BL20-2DO-R-NO28 mA
BL20-2DO-R-CO28 mA
BL20-1CNT-24VDC40 mA
BL20-1RS232140 mA
BL20-1RS485/42260 mA
BL20-1SSI50 mA
BL20-2RFID30 mA
BL20-E-1SWIRE60 mA
D301087 1211 - BL20 CANopen6-6
Page 61
Power Supply
23
22
21
13
12
11
2323
2222
2121
1313
1212
1111
24
23
22
21
14
13
12
11
24
23
22
21
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
–+
Field supply
TS
2 DO 2 DI 2 DO 2 DIBR
SBBC-B
2 DIAI1AONO
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
2 DI
Gateway
GND-
CAN_L
Shield
CAN_H
+–
+–
Field supply
System supply
23
22
21
13
12
11
2323
2222
2121
1313
1212
1111
2424
2323
2222
2121
1414
1313
1212
1111
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
+–
+
–+
–
=
Field supply
System supply
Field supply
GatewayTSBR
SBBC
2 DO 2 DI 2 DO 2 DIBR
SBBC-B
2 DIAI1AONO
CANH
SHLD
CANL
GND
CANH
SHLD
CANL
GND
Figure 6-1:
Power supply at
BL20-GWBRCANOPEN
If the power supply from the module bus is not guaranteed, thereby making a further Bus Refreshing
module necessary, the software I/O-ASSISTANT generates an error message when the user activates
the command “Station → Verify“.
Note
Bus Refreshing modules which do not supply the gateway with power are to be combined
with either a BL20-P3T-SBB-B or a BL20-P4T-SBBC-B (tension clamp connection) base module
or with the base modules BL20-P3S-SBB-B or BL20-P4S-SBBC-B (screw connection).
Figure 6-2:
Power supply at
BL20-GWCANOPEN
With the system supply, it must be ensured that the same ground potential and ground connections
are used. Compensating currents flow via the module bus if different ground potentials or ground
connections are used, which can lead to the destruction of the Bus Refreshing module.
All Bus Refreshing modules are connected to one another via the same ground potential.
The power to the module bus is supplied via the connections 11 and 21 on the base module.
D301087 1211 - BL20 CANopen
6-7
Page 62
Guidelines for Station Planning
23
22
21
13
12
11
23 23
22 22
21 21
13 13
12 12
11
24
2323
2222
2121
14
1313
1212
1111
Potential group 2
2L+ 2L-
2 DO 2 DI PF 2 DO2 DI
24
23
22
21
14
13
12
11
Potential group 1
TS
2 DIAINO
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
NO
AI
24
23
22
21
14
13
12
11
Gateway
GND
CAN_L
Shield
CAN_H
+–
+–
System supply
Field supply
6.2.3Creating Potential Groups
Bus Refreshing and Power Feeding modules can be used to create potential groups. The potential
isolation of potential groups to the left of the respective power distribution modules is provided by the
base modules.
Attention
Ensure that the correct base modules are planned for when using Bus Refreshing modules.
Figure 6-3:
Example for
creating potential
groups with
BL20-GWBRCANOPEN
Note
The system can be supplied with power independent of the potential group formation
described above.
When using a digital input module for 120/230 V AC, it should be ensured that a potential group is
created in conjunction with the Power Feeding module BL20-PF-120/230VAC-D.
Attention
It is not permitted to use the modules with 24 V DC and 120/230 V AC field supply in a joint
potential group.
6.2.4Protecting the Service Interface on the Gateway
During operation, the cover protecting the service interface and the rotary coding-switches must
remain closed due to EMC and ESD.
D301087 1211 - BL20 CANopen6-8
Page 63
Power Supply
6.2.5C-Rail (Cross Connection)
The C-rail runs through all base modules. The C-rail of the base modules for power distribution modules
is mechanically separated; thus potentially isolating the adjoining supply groups.
Access to the C-rail is possible with the help of base modules with a C in their designation (for example,
BL20-S4T-SBCS). The corresponding connection level is indicated on these modules by a thick black
line. The black line is continuous on all I/O modules. On power distribution modules, the black line is
only above the connection 24. This makes clear that the C-rail is separated from the adjoining potential
group to its left.
Figure 6-4:
C-rail front view
Figure 6-5:
C-rail side view
Danger
It is permitted to load the C-rail with a maximum of 24 V. Not 230 V!
The C-rail can be used as required by the application, for example, as a protective earth (PE). In this case,
the PE connection of each power distribution module must be connected to the mounting rail via an
additional PE terminal, which is available as an accessory.
Note
For information about introducing a BL20 station into a ground reference system, please read
chapter 7.
D301087 1211 - BL20 CANopen
6-9
Page 64
Guidelines for Station Planning
23
22
21
13
12
11
2323
2222
2121
1313
1212
1111
232323
222222
212121
131313
121212
111111
2424
2323
2222
2121
1414
1313
1212
1111
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
Gateway
TS
BR
SBBC
2 DO
SBC
2 DI
SBBC
2 DO
SBC
2 DI
SBBPFSBBC
2 DI2 DO
SBBCSBC
2 DO
SBC
2 DI
SBB
C-rail (PE)C-rail (PE)
PE
terminal
Gateway
23
22
21
13
12
11
2323
2222
2121
1313
1212
1111
2424
2323
2222
2121
1414
1313
1212
1111
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
yyy
TS
Gateway
PE
terminal
BR
SBBC
2 DO
SBC
2 DI
SBBC
2 DO
SBC
2 DI
SBB
PFNCNO
SBCSSBCS
NO
SBCSNCSBCS
C-rail (24 V DC)C-rail (PE)
SBBC
Figure 6-6:
Using the C-rail as
a protective earth
C-rails can be used for a common voltage supply when relay modules are planned. To accomplish this,
the load voltage is connected to a Power Feeding module with the BL20-P4x-SBBC base module with
tension clamp or screw connection. All the following relay modules are then supplied with power via
the C-rail.
Figure 6-7:
Using the C-rail as
protective earth
and for the power
supply with relay
modules
Attention
When relay modules are planned and the C-rail is used for a common voltage supply, a further
power distribution module must be used for the potential isolation to the following modules.
The C-rail can only again be used as a PE following potential isolation.
Cross-connecting relay module roots is achieved by the use of jumpers. The corresponding wiring
diagram including the jumpers can be found in chapter 4.
6.2.6Direct Wiring of Relay Modules
As well as the options mentioned above, relay modules can be wired directly. In this case, base modules
without C-rail connections should be chosen to guarantee the potential isolation to the adjoining
modules.
D301087 1211 - BL20 CANopen6-10
Page 65
Plugging and Pulling Electronics Modules
6.3Plugging and Pulling Electronics Modules
BL20 enables the pulling and plugging of electronics modules without having to disconnect the field
wiring. The BL20 station remains in operation if an electronics module is pulled. The voltage and current
supplies as well as the protective earth connections are not interrupted.
Attention
If the field and system supplies remain connected when electronics modules are plugged or
pulled, short interruptions to the module bus communications can occur in the BL20 station.
This can lead to undefined statuses of individual inputs and outputs of different modules.
D301087 1211 - BL20 CANopen
6-11
Page 66
Guidelines for Station Planning
6.4Extending an Existing Station
Attention
Please note that extensions to the station (mounting further modules) should be carried out
only when the station is off-circuit.
Once alterations have been made to the order of the modules on the BL20 station, the new
configuration must be saved to the ”actual configuration memory” of the BL20 gateway. This is done
by either pressing the SET button between the two decimal rotary coding switches (see chapter 2) or
by making the appropriate settings in the configuration software (see chapter 3).
D301087 1211 - BL20 CANopen6-12
Page 67
Firmware Download
6.5Firmware Download
Firmware can be downloaded via the service interface on the gateway using the software tool
I/O-ASSISTANT. More information is available in the program’s online help.
Attention
The station should be disconnected from the fieldbus when downloading.
Firmware must be downloaded by authorized personnel only.
Cables should be grouped together, for example: signal cables, data cables, heavy current cables,
power supply cables.
Heavy current cables and signal or data cables should always be routed in separate cable ducts or
bundles. Signal and data cables must always be routed as close as possible to ground potential surfaces
(for example support bars, cabinet sides etc.).
7.1.2Cable Routing
Correct cable routing prevents or suppresses the reciprocal influencing of parallel routed cables.
7.1.3Cable Routing Inside and Outside of Cabinets:
To ensure EMC-compatible cable routing, the cables should be grouped as follows:
Various types of cables within the groups can be routed together in bundles or in cable ducts.
Group 1:
shielded bus and data cables
shielded analog cables
unshielded cables for DC voltage ≤ 60 V
unshielded cables for AC voltage ≤ 25 V
Group 2:
unshielded cables for DC voltage > 60 V and ≤ 400 V
unshielded cables for AC voltage > 25 V and ≤ 400 V
Group 3:
unshielded cables for DC and AC voltages > 400 V
The following group combination can be routed only in separate bundles or separate cable ducts (no
minimum distance apart):
Group 1/Group 2
The group combinations:
Group 1/Group 3 and Group 2/Group 3
must be routed in s eparate cable ducts with a mi nimum dista nce of 10 cm apart. Th is is equ ally val id for
inside buildings as well as for inside and outside of switchgear cabinets.
Cable Routing Outside Buildings
Outside of buildings, cables should be routed in closed (where possible), cage-type cable ducts made
of metal. The cable duct joints must be electrically connected and the cable ducts must be earthed.
Danger
Observe all valid guidelines concerning internal and external lightning protection and
grounding specifications when routing cables outside of buildings.
D301087 1211 - BL20 CANopen7-2
Page 71
General Notes
Station 0
Station 63Station x
terminating
resistor
terminating
resistor
R
t
R
t
7.1.4Lightning Protection
The cables must be routed in double-grounded metal piping or in reinforced concrete cable ducts.
Signal cables must be protected against overvoltage by varistors or inert-gas filled overvoltage
arrestors. Varistors and overvoltage arrestors must be installed at the point where the cables enter the
building.
7.1.5Transmission Cables
The slaves on the bus are connected to one another with fieldbus lines that correspond to the
DeviceNet specification (ODVA Spec. Rel. V2.0).
The bus cables must be terminated at the beginning and end with a bus terminating resistor. This can
be connected via the number 4 DIP switch on the gateway.
Figure 7-1:
Representation of
a bus cable
7.1.6Cable Types
TURCK offers a variety of premoulded bus cables - please refer to the BL20-catalog (TURCK
documentation number: D300418).
D301087 1211 - BL20 CANopen
7-3
Page 72
Guidelines for Electrical Installation
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
24
23
22
21
14
13
12
11
Gateway
Power Feeding
Bus Refreshing
I/O moduleI/O moduleI/O module
Bus Refreshing
LogicLogic
5V
Logic
24 V
2 O2 O4 I
24 V24 VField-
bus
24 V230 V
Logic
DCDC
DCDC
+V -V
7.2Potential Relationships
7.2.1General
The potential relationship of a CANopen system realized with BL20 modules is characterized by the
following:
The system’s power supply to the gateway, I/O modules and the field level is distributed via a Bus
Refreshing module.
All BL20 modules (gateway, Bus Refreshing, Power Feeding and I/O modules), are connected
capacitively via base modules to the mounting rails.
Separate power supplies for the system and the field level allow a potential-free installation.
The block diagram shows the arrangement of a typical BL20 station.
Figure 7-2:
Block diagram of
a BL20 station
7.2.2Potential-Free Installation
In a potential-free installation, the reference potentials of control and load circuitry are galvanically
isolated from each other.
A potential-free installation is necessary with
All AC load circuits (for example, when using the Power Feeding module BL20-PF-120/230VAC-D)
Floating DC load circuits
The potential-free installation does not depend on the method of grounding.
7.2.3Non-isolated Installation
In a non-isolated installation, the reference potentials of the control and load circuitry are galvanically
connected.
D301087 1211 - BL20 CANopen7-4
Page 73
Electromagnetic Compatibility (EMC)
7.3Electromagnetic Compatibility (EMC)
BL20 products comply in full with the requirements pertaining to EMC regulations.
Nevertheless, an EMC plan should be made before installation. Hereby, all potential electromechanical
sources of interference should be considered such as galvanic, inductive and capacitive couplings as
well as radiation couplings.
7.3.1Ensuring Electromagnetic Compatibility
The EMC of BL20 modules is guaranteed when the following basic rules are adhered to:
Correct and large surface grounding of inactive metal components.
Correct shielding of cables and devices.
Proper cable routing – correct wiring.
Creation of a standard reference potential and grounding of all electrically operated devices.
Special EMC measures for special applications.
7.3.2Grounding of Inactive Metal Components
All inactive metal components (for example: switchgear cabinets, switchgear cabinet doors, supporting
bars, mounting plates, tophat rails, etc.) must be connected to one another over a large surface area
and with a low impedance (grounding). This guarantees a standardized reference potential area for all
control elements and reduces the influence of coupled disturbances.
In the areas of screw connections, the painted, anodized or isolated metal components must be
freed of the isolating layer. Protect the points of contact against rust.
Connect all free moving groundable components (cabinet doors, separate mounting plates, etc.) by
using short bonding straps to large surface areas.
Avoid the use of aluminum components, as its quick oxidizing properties make it unsuitable for
grounding.
Danger
The grounding must never – including cases of error – take on a dangerous touch potential.
For this reason, always protect the ground potential with a protective cable.
7.3.3PE Connection
A central connection must be established between ground and PE connection (protective earth).
7.3.4Earth-Free Operation
Observe all relevant safety regulations when operating an earthfree system.
D301087 1211 - BL20 CANopen
7-5
Page 74
Guidelines for Electrical Installation
Protect against high frequency interference signals
Attention
In order to comply with radiation limit values in accordance with EN 55 011/2 000, the supply
lines of the power distribution module BL20-BR-24VDC-D for supplying the gateway with
power are to be fed through a ferrite ring (BL20PS416-ZBX-405). This is to be placed
immediately next to the connection terminals. From there on, it is not permitted to make
connections to further devices.
7.3.5Mounting Rails
All mounting rails must be mounted onto the mounting plate with a low impedance, over a large
surface area, and must be correctly earthed.
Figure 7-3:
Mounting options
A TS 35
B Mounting rail
C Mounting plate
D TS 35
Mount the mounting rails over a large surface area and with a low impedance to the support system
using screws or rivets.
Remove the isolating layer from all painted, anodized or isolated metal components at the connection
point. Protect the connection point against corrosion (for example with grease; caution: use only
suitable grease).
D301087 1211 - BL20 CANopen7-6
Page 75
Electromagnetic Compatibility (EMC)
abcde
A
BCD
E
7.3.6EMC Compliant Cabinet Installation
Figure 7-4:
EMC compliant
cabinet installation
A Bonding straps
Bonding straps connect inactive metal components, if it is not possible to create a large surface area contact. Use
short bonding straps with large surface areas.
B Mounting plates
Mounting plates used to hold control components must have a large surface area contact with the cabinet housing.
C Protective conductor rail
The protective conductor rail must also be connected over a large surface area to the mounting plates and
additionally with an external cable (cross-section at least 10 mm2 / 0,015 inch2) to the protective conductor system to
avoid interference currents.
D Protective conductor terminal block
The protective conductor terminal block must be connected to the protective conductor rail.
E Protective conductor system cable (grounding point)
The cable must be connected over a large surface area with the protective conductor system.
D301087 1211 - BL20 CANopen
7-7
Page 76
Guidelines for Electrical Installation
7.4Shielding of cables
Shielding is used to prevent interference from voltages and the radiation of interference fields by
cables. Therefore, use only shielded cables with shielding braids made from good conducting materials
(copper or aluminum) with a minimum degree of coverage of 80 %.
The cable shield should always be connected to both sides of the respective reference potential (if no
exception is made, for example, such as high-resistant, symmetrical, analog signal cables). Only then
can the cable shield attain the best results possible against electrical and magnetic fields.
A one-sided shield connection merely achieves an isolation against electrical fields.
Attention
When installing, please pay attention to the following...
– the shield should be connected immediately when entering the
–system,
– the shield connection to the shield rail should be of low
–impedance,
– the stripped cable-ends are to be kept as short as possible,
– the cable shield is not to be used as a bonding conductor.
The insulation of the shielded data-cable should be stripped and connected to the shield rail when the
system is not in operation. The connection and securing of the shield should be made using metal
shield clamps. The shield clamps must enclose the shielding braid and in so doing create a large surface
contact area. The shield rail must have a low impedance (for example, fixing points of 10 to 20 cm apart)
and be connected to a reference potential area.
The cable shield should not be severed, but routed further within the system (for example, to the
switchgear cabinet), right up to the interface connection.
Note
Should it not be possible to ground the shield on both sides due to switching arrangements
or device specific reasons, then it is possible to route the second cable shield side to the local
reference potential via a capacitor (short connection distances). If necessary, a varistor or
resistor can be connected parallel to the capacitor, to prevent disruptive discharges when
interference pulses occur.
A further possibility is a double-shielded cable (galvanically separated), whereby the
innermost shield is connected on one side and the outermost shield is connected on both
sides.
D301087 1211 - BL20 CANopen7-8
Page 77
Potential Compensation
Reference potential
Potential compensation cable
Shield
Reference potential
7.5Potential Compensation
Potential differences can occur between installation components that are in separate areas and these
are fed by different supplies,
have double-sided conductor shields which are grounded on different installation components.
A potential-compensation cable must be routed to the potential compensation.
Danger
Never use the shield as a potential compensation.
Connection 1Connection 2
CAN_H0 ---------0CAN_H
CAN_L0 ---------0CAN_L
GND0 ---------0GND
Figure 7-5:
Potential
compensation
A potential compensation cable must have the following characteristics:
Low impedance. In the case of compensation cables that are routed on both sides, the
compensation line impedance must be considerably smaller than that of the shield connection
(max. 10 % of shield connection impedance).
Should the length of the compensation cable be less than 200 m, then its cross-section must be at
least 16 mm
25 mm
2
/ 0.025 inch2. If the cable length is greater than 200 m, then a cross-section of at least
2
/ 0.039 inch2 is required.
The compensation cable must be made of copper or zinc coated steel.
The compensation cable must be connected to the protective conductor over a large surface area
and must be protected against corrosion.
D301087 1211 - BL20 CANopen
7-9
Page 78
Guidelines for Electrical Installation
Potential compensation
Compensation cables and data cables should be routed as close together as possible, meaning the
enclosed area should be kept as small as possible.
Figure 7-6:
Potential
compensation
between switchgear cabinets
7.5.1Switching Inductive Loads
In the case of inductive loads, a protective circuit on the load is recommended.
7.5.2Protection against Electrostatic Discharge (ESD)
Attention
Electronic modules and base modules are at risk from electrostatic discharge when
disassembled. Avoid touching the bus connections with bare fingers as this can lead to ESD
damage.
D301087 1211 - BL20 CANopen7-10
Page 79
Bus Connection
7.6Bus Connection
An Open Style Connector (5-pole) is available for connecting the BL20-GWBR-CANopen to the
CANopen fieldbus.
The shield connection is made via the shielding braid of the cable.
For detailed information about the bus connection of the gateway please refer to chapter 4.6,
Connections of the data cables to BL20-GWBR-CANopen (page 4-12).
D301087 1211 - BL20 CANopen
7-11
Page 80
Guidelines for Electrical Installation
7.7Two-Pole Shield Connection
The 2-pole shield connection can be used to connect signal-cable shielding to the base modules of
analog input and output modules. A special tension-clamp operating tool (BL20-ZBW5-2) is required to
mount the shield connection onto the base module.
Figure 7-7:
Two-pole shield
connection for
analog modules
The following cable diameters are permissible for the shield connection:
Diameter of the shielding braid:max. 4.9 mm / 0.19 inch
Outer diameter of the cable: max. 6.5 mm / 0.26 inch
D301087 1211 - BL20 CANopen7-12
Page 81
8BL20-Approvals for Zone 2/ Division 2
Note
The Zone 2 - approval certificates for BL20 can be found in a separate manual for approvals
D301255 on www.turck.de.
D301087 1211 - BL20 CANopen8-1
Page 82
BL20-Approvals for Zone 2/ Division 2
D301087 1211 - BL20 CANopen8-2
Page 83
D301087 1211 - BL20 CANopen
8-3
Page 84
BL20-Approvals for Zone 2/ Division 2
D301087 1211 - BL20 CANopen8-4
Page 85
D301087 1211 - BL20 CANopen
8-5
Page 86
BL20-Approvals for Zone 2/ Division 2
D301087 1211 - BL20 CANopen8-6
Page 87
9Glossary
A
B
Acknowledge
Acknowledgment of a signal received.
Active metal component
Conductor or conducting component that is electrically live during operation.
Address
Identifier of, e.g. a memory position, a system or a module within a network.
Addressing
Allocation or setting of an address, e. g. for a module in a network.
Analog
Infinitely variable value, e. g. voltage. The value of an analog signal can take on any value, within certain limits.
Attribute
Attributes represent the data that a device makes available via the DeviceNet fieldbus (e. g. status of an object,
serial number of the device, process data).
Automation device
A device connected to a technical process with inputs and outputs for control. Programmable logic controllers
(PLC) are a special group of automation devices.
Baud
Baud is a measure for the transmission speed of data. 1 Baud corresponds to the transmission of one bit per
second (Bit/s).
Baud rate
Unit of measurement for data transmission speeds in Bit/s.
Bidirectional
Working in both directions.
Bit Strobe
A Bit Strobe I/O connection is a connection between a DeviceNet client and an undetermined number of servers,
these being queried by commands sent by the client.
Bonding strap
Flexible conductor, normally braided, that joins inactive components, e. g. the door of a switchgear cabinet to the
cabinet main body.
Bus
Bus system for data exchange, e. g. between CPU, memory and I/O levels. A bus can consist of several parallel
cables for data transmission, addressing, control and power supply.
Bus cycle time
Time required for a master to serve all slaves or stations in a bus system, i. e. reading inputs and writing outputs.
D301087 1211 - BL20 CANopen9-1
Page 88
Glossary
CDE
Bus line
Smallest unit connected to a bus, consisting of a PLC, a coupling element for modules on the bus and a module.
Bus system
All units which communicate with one another via a bus.
Capacitive coupling
Electrical capacitive couplings occur between cables with different potentials. Typical sources of interference are,
e. g. parallel-routed signal cables, contactors and electrostatic discharges.
Class
A group of Objects that all describe the same system components. All Objects of a Class are identical in form and
behavior, they can though contain different attributes.
COB
Communication Object, which is made of one or more CAN frames. Any information transmitted via CANopen has
to be mapped into COBs (Source: CiA
DS 401 V2.1).
COB-ID
COB-Identifier. Identifies a COB uniquely in a CAN network. The identifier determines the priority of that COB in
the data link layer, too (Source: CiA
DS 401 V2.1).
Coding elements
Two-piece element for the unambiguous assignment of electronic and base modules.
Configuration
Systematic arrangement of the I/O modules of a station.
CPU
Central Processing Unit. Central unit for electronic data processing, the processing core of the PC.
Cyclic
Messages are triggered time-controlled in Cyclic I/O connections by means of a time generator.
Digital
A value (e. g. a voltage) which can adopt only certain statuses within a finite set, mostly defined as 0 and 1.
DIN
German acronym for German Industrial Standard.
EDS
Electronic Device Data Sheet which contains standardized DeviceNet station descriptions. They simplify the
planning of the DeviceNet nodes.
EIA
Electronic Industries Association – association of electrical companies in the United States.
D301087 1211 - BL20 CANopen9-2
Page 89
Electrical components
FGH
I
All objects that produce, convert, transmit, distribute or utilize electrical power (e. g. conductors, cable, machines,
control devices).
EMC
Electromagnetic compatibility – the ability of an electrical part to operate in a specific environment without fault
and without exerting a negative influence on its environment.
EN
German acronym for European Standard.
ESD
Electrostatic Discharge.
Field power supply
Voltage supply for devices in the field as well as the signal voltage.
Fieldbus
Data network on sensor/actuator level. A fieldbus connects the equipment on the field level. Characteristics of a
fieldbus are a high transmission security and real-time behavior.
Force Mode
Software mode which enables the user to set his plant to a required state by forcing certain variables on the input
and output modules.
GND
Abbreviation of ground (potential "0").
Ground
Expression used in electrical engineering to describe an area whose electrical potential is equal to zero at any
given point. In neutral grounding devices, the potential is not necessarily zero, and one speaks of the ground
reference.
Ground connection
One or more components that have a good and direct contact to earth.
Ground reference
Potential of ground in a neutral grounding device. Unlike earth whose potential is always zero, it may have a
potential other than zero.
Hexadecimal
System of representing numbers in base 16 with the digits 0... 9, and further with the letters A, B, C, D, E and F.
Hysteresis
A sensor can get caught up at a certain point, and then "waver" at this position. This condition results in the
counter content fluctuating around a given value. Should a reference value be within this fluctuating range, then
the relevant output would be turned on and off in rhythm with the fluctuating signal.
I/O
Input/output.
D301087 1211 - BL20 CANopen
9-3
Page 90
Glossary
LMMOP
Impedance
Total effective resistance that a component or circuit has for an alternating current at a specific frequency.
Inactive metal components
Conductive components that cannot be touched and are electrically isolated from active metal components by
insulation, but can adopt voltage in the event of a fault.
Inductive coupling
Magnetic inductive couplings occur between two cables through which an electrical current is flowing. The
magnetic effect caused by the electrical currents induces an interference voltage. Typical sources of interference
are for example, transformers, motors, parallel-routed network and HF signal cables.
Instance
An Instance is defined as being an Object that is actually set up in a device.
Load value
Predefined value for the counter module with which the count process begins.
Lightning protection
All measures taken to protect a system from damage due to overvoltages caused by lightning strike.
Low impedance connection
Connection with a low AC impedance.
LSB
Least Significant Bit
Mass
All interconnected inactive components that do not take on a dangerous touch potential in the case of a fault.
Module bus
The module bus is the internal bus in a BL20 station. The BL20 modules communicate with the gateway via the
module bus which is independent of the fieldbus.
MSB
Most Significant Bit
NMT
see chapter 3Short description of CANopen (Seite 3-1).
Overhead
System administration time required by the system for each transmission cycle.
PDO
see chapter 3Short description of CANopen (Seite 3-1).
PLC
Programmable Logic Controller.
D301087 1211 - BL20 CANopen9-4
Page 91
Polling
R
S
Establish a Polled I/O Connection, i. e. a conventional Master/Slave relationship between a controller and a
DeviceNet device.
Potential compensation
The alignment of electrical levels of electrical components and external conductive components by means of an
electrical connection.
Potential free
Galvanic isolation of the reference potentials in I/O modules of the control and load circuits.
Potential linked
Electrical connection of the reference potentials in I/O modules of the control and load circuits.
Protective earth
Electrical conductor for protection against dangerous shock currents. Generally represented by PE (protective
earth).
Radiation coupling
A radiation coupling appears when an electromagnetic wave hits a conductive structure. Voltages and currents
are induced by the collision. Typical sources of interference are e. g. sparking gaps (spark plugs, commutators
from electric motors) and transmitters (e. g., radio), that are operated near to conducting structures.
Reaction time
The time required in a bus system between a reading operation being sent and the receipt of an answer. It is the
time required by an input module to change a signal at its input until the signal is sent to the bus system.
SDO
see chapter 3Short description of CANopen (Seite 3-1).
D301087 1211 - BL20 CANopen
9-5
Page 92
Glossary
D301087 1211 - BL20 CANopen9-6
Page 93
10Index
A
addressing
B
BL20 gateway
–function
bus connection ............................................................7-11