Turck BI5-P18-Y1/S100 Data Sheet

Inductive sensor With extended temperature range BI5-P18-Y1/S100
Type designation BI5-P18-Y1/S100
Ident-No. 10245
ATEX category II 2 G. Ex-zone 1
ATEX category II 1 D, Ex-zone 20 for
temperatures up to +70 °C
SIL2 (Low Demand Mode) acc. to IEC
61508, PL c acc. to ISO 13849-1 at HFT0
SIL3 (All Demand Mode) acc. to IEC
61508, PL e acc. to ISO 13849-1 with re­dundant configuration HTF1
Threaded barrel, M18 x 1
Plastic, PA12-GF30-V0
Temperatures up to +100 °C
DC 2-wire, nom. 8.2 VDC
Output acc. to DIN EN 60947-5-6 (NA-
MUR)
Cable connection
Rated switching distance Sn 5 mm
Hysteresis 1…10 % Ambient temperature -25…+100 °C
Output function 2-wire, NAMUR Switching frequency 1 kHz Voltage Nom. 8.2 VDC Non-actuated current consumption Actuated current consumption
Approval acc. to KEMA 02 ATEX 1090X
Design Threaded barrel,M18 × 1
Dimensions 34 mm Housing material Plastic, PA12-GF30 Active area material Plastic, PA12-GF30 End cap Plastic, EPTR Max. tightening torque housing nut 2 Nm Electrical connection Cables Cable quality 5.2mm, LifYY-T105, PVC, 2 Cable cross section
Vibration resistance 55 Hz (1 mm) Shock resistance 30 g (11 ms) MTTF 6198 years acc. to SN 29500 (Ed. 99) 40 °C Packaging unit 1
ð (0,81 x Sn) mm
ð 2 % of full scale ð ± 10 % ð ± 20 %, ï +70 °C
For explosion hazardous areas see instruction leaflet
ï 2.1 mA ð 1.2 mA
2 x 0.5 mm
2
Wiring Diagram
Functional principle
Inductive sensors detect metal objects con­tactless and wear-free. For this purpose they use a high-frequency electromagnetic AC field that interacts with the target. The sensors hosting a ferrite core coil generate the AC field through an LC resonant circuit.
Special versions are available for ambient temperatures between -60°C and +250°C.
Edition • 2018-07-09T17:27:12+02:00
1 / 4 TURCK Inc.
Inductive sensor With extended temperature range BI5-P18-Y1/S100
Distance D 2 x B
Distance W 3 x Sn
Distance T 3 x B
Distance S 1.5 x B
Distance G 6 x Sn
Diameter active area B Ø 18 mm
Edition • 2018-07-09T17:27:12+02:00
2 / 4 TURCK Inc.
Inductive sensor With extended temperature range BI5-P18-Y1/S100
Accessories
Type code Ident-No. Description
QM-18 6945102 Quick-mount bracket with dead-stop; material: Chrome-plat-
ed brass Male thread M24 x 1.5. Note: The switching dis-
tance of proximity switches can be reduced by the use of
quick-mount brackets.
BST-18B 6947214 Fixing clamp for threaded barrel devices, with dead-stop; ma-
terial: PA6
MW-18 6945004 Mounting bracket for threaded barrel devices; material: Stain-
less steel A2 1.4301 (AISI 304)
BSS-18 6901320 Mounting bracket for smooth and threaded barrel devices;
material: Polypropylene
IMX12-DI01-2S-2T-0/
24VDC
7580020 Isolating switching amplifier, 2-channel; SIL2 acc. to IEC
61508; Ex-proof version; 2 transistor outputs; input Namur
signal; ON/OFF switchable monitoring of wire-break and
short-circuit; toggle between NO/NC mode; signal doubling;
removable screw terminals; 12.5 mm wide; 24 VDC power
supply
Edition • 2018-07-09T17:27:12+02:00
3 / 4 TURCK Inc.
Inductive sensor With extended temperature range BI5-P18-Y1/S100
Operating manual
Intended use
This device fulfills the directive 2014/34/EC and is suited for use in explosion hazardous areas according to EN 60079-0:2012 + A11 and EN 60079-11:2012. Further it is suited for use in safety-related systems, including SIL2 as per IEC 61508. In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II 2 G and II 1 D (Group II, Category 2 G, electrical equipment for gaseous atmospheres and category 1 D, electrical equipment for dust atmo­spheres).
Marking (see device or technical data sheet)
É II 2 G and Ex ia IIC T6 Gb acc. to EN60079-0 and -26 and É II 1 D Ex ia IIIC T115°C Da acc. to EN60079-0
Local admissible ambient temperature
-25…+100 °C
Installation/Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas. Please verify that the classification and the marking on the device comply with the actual application conditions.
This device is only suited for connection to approved Exi circuits according to EN 60079-0 and EN 60079-11. Please observe the maximum ad­missible electrical values. After connection to other circuits the sensor may no longer be used in Exi installations. When interconnected to (associated) electrical equip­ment, it is required to perform the "Proof of intrinsic safety" (EN60079-14). Attention! When used in safety systems, all content of the security manual must be observed.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and avoid build-up of dust deposits on the device. If the devices and the cable could be subject to mechanical damage, they must be protected accordingly. They must also be shielded against strong electro-magnetic fields. The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet.
Service/Maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important data from the approval are listed.
Edition • 2018-07-09T17:27:12+02:00
4 / 4 TURCK Inc.
Loading...