Turck BI50-Q80-Y1X Data Sheet

Inductive sensor With switching distance BI50-Q80-Y1X
Type designation BI50-Q80-Y1X
Ident-No. 1008701
ATEX category II 2 G, Ex zone 1
ATEX category II 1 D, Ex zone 20
SIL2 (Low Demand Mode) acc. to IEC
61508, PL c acc. to ISO 13849-1 at HFT0
SIL3 (All Demand Mode) acc. to IEC
61508, PL e acc. to ISO 13849-1 with re­dundant configuration HFT1
Rectangular, height 40 mm
Active face on top
Plastic, PBT-GF30-V0
Large coverage
DC 2-wire, nom. 8.2 VDC
Output acc. to DIN EN 60947-5-6 (NA-
MUR)
Cable connection
Rated switching distance Sn 50 mm
Output function 2-wire, NAMUR Switching frequency 0.1 kHz Voltage Nom. 8.2 VDC Non-actuated current consumption Actuated current consumption
Approval acc. to KEMA 02 ATEX 1090X
Design Rectangular,Q80
Dimensions 92 x 80 x 40 mm Housing material Plastic, PBT-GF30-V0 Tightening torque fixing screw 4 Nm Electrical connection Cable Cable quality 5.2mm, Blue, LifYY, PVC, 2 Cable cross section
Vibration resistance 55 Hz (1 mm) Shock resistance 30 g (11 ms) Protection class IP67 MTTF 6198 years acc. to SN 29500 (Ed. 99) 40 °C Packaging unit 1
ð (0,81 x Sn) mm
ð 2 % of full scale ð ± 10 %
ï 2.1 mA ð 1.2 mA
2 x 0.34 mm
2
Wiring Diagram
Functional principle
Inductive sensors detect metal objects con­tactless and wear-free. For this, they use a high-frequency electromagnetic AC field that interacts with the target. Inductive sensors generate this field via an RLC circuit with a ferrite coil.
Switching state LED,Yellow
Edition • 2018-04-20T18:26:13+02:00
1 / 4 TURCK Inc.
Inductive sensor With switching distance BI50-Q80-Y1X
Distance D 2 x B
Distance W 3 x Sn
Distance S 1 x B
Distance G 6 x Sn
Width active area B 80 mm
Edition • 2018-04-20T18:26:13+02:00
2 / 4 TURCK Inc.
Inductive sensor With switching distance BI50-Q80-Y1X
Accessories
Type code Ident-No. Description
IMX12-DI01-2S-2T-0/
24VDC
7580020 Isolating switching amplifier, 2-channel; SIL2 acc. to IEC
61508; Ex-proof version; 2 transistor outputs; input Namur
signal; ON/OFF switchable monitoring of wire-break and
short-circuit; toggle between NO/NC mode; signal doubling;
removable screw terminals; 12.5 mm wide; 24 VDC power
supply
Edition • 2018-04-20T18:26:13+02:00
3 / 4 TURCK Inc.
Inductive sensor With switching distance BI50-Q80-Y1X
Operating manual
Intended use
This device fulfills the directive 2014/34/EC and is suited for use in explosion hazardous areas according to EN 60079-0:2012 + A11 and EN 60079-11:2012. Further it is suited for use in safety-related systems, including SIL2 as per IEC 61508. In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II 2 G and II 1 D (Group II, Category 2 G, electrical equipment for gaseous atmospheres and category 1 D, electrical equipment for dust atmo­spheres).
Marking (see device or technical data sheet)
É II 2 G and Ex ia IIC T6 Gb and É II 1 D Ex ia IIIC T95 °C Da acc. to EN 60079-0, -11
Local admissible ambient temperature
-25…+70 °C
Installation/Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas. Please verify that the classification and the marking on the device comply with the actual application conditions.
This device is only suited for connection to approved Exi circuits according to EN 60079-0 and EN 60079-11. Please observe the maximum ad­missible electrical values. After connection to other circuits the sensor may no longer be used in Exi installations. When interconnected to (associated) electrical equip­ment, it is required to perform the "Proof of intrinsic safety" (EN60079-14). Attention! When used in safety systems, all content of the security manual must be observed.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and avoid build-up of dust deposits on the device. If the devices and the cable could be subject to mechanical damage, they must be protected accordingly. They must also be shielded against strong electro-magnetic fields. The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet.
Special conditions for safe operation
avoid static charging
Service/Maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important data from the approval are listed.
Edition • 2018-04-20T18:26:13+02:00
4 / 4 TURCK Inc.