Turck BI3-M18-AP6X/S903 Data Sheet

Inductive sensor BI3-M18-AP6X/S903
Type designation BI3-M18-AP6X/S903
Ident-No. 4607140
Rated switching distance Sn 3 mm Mounting conditions Flush Secured operating distance Correction factors St37 = 1; Al = 0.3; stainless steel = 0.7; Ms = 0.4 Repeat accuracy Temperature drift Hysteresis 1…3 % Ambient temperature -30…+70 °C
ð (0,81 x Sn) mm
ð 2 % of full scale ð ± 10 %
Threaded barrel, M18 x 1
Chrome-plated brass
Hysteresis always below 0.1 mm
DC 3-wire, 10…30 VDC
NO contact, PNP output
Cable connection
Wiring Diagram
Functional principle
Inductive sensors detect metal objects con­tactless and wear-free. For this, they use a high-frequency electromagnetic AC field that interacts with the target. Inductive sensors generate this field via an RLC circuit with a ferrite coil.
Operating voltage 10…30 VDC Residual ripple DC rated operational current No-load current I Residual current Isolation test voltage Short-circuit protection yes/ Cyclic Voltage drop at I Wire breakage/Reverse polarity protection yes/ Complete Output function 3-wire, NO contact, PNP Switching frequency 0.5 kHz
Design Threaded barrel,M18 × 1 Dimensions 54 mm Housing material Metal, CuZn, Chrome-plated Active area material Plastic, PA12-GF30 End cap Plastic, EPTR Max. tightening torque housing nut 25 Nm Electrical connection Cable Cable quality 5.2mm, LifYY, PVC, 2 Cable cross section
Vibration resistance 55 Hz (1 mm) Shock resistance 30 g (11 ms) Protection class IP67
Switching state LED,Yellow
0
e
ð 10 % U
ss
ð 200 mA ð 15 mA ð 0.1 mA ð 0.5 kV
ð 1.8 V
3 x 0.34 mm
2
Edition • 2018-04-23T16:01:32+02:00
1 / 3 TURCK Inc.
Inductive sensor BI3-M18-AP6X/S903
Distance D 2 x B
Distance W 3 x Sn
Distance T 3 x B
Distance S 1.5 x B
Distance G 6 x Sn
Diameter active area B Ø 18 mm
Edition • 2018-04-23T16:01:32+02:00
2 / 3 TURCK Inc.
Loading...