Inductive sensor BI2-M12-Y1X-H1141
Type code BI2-M12-Y1X-H1141
Ident no. 40102
Rated switching distance Sn 2 mm Mounting conditions flush Assured switching distance Correction factors St37 = 1; Al = 0.3; stainless steel = 0.7; Ms = 0.4 Repeatability Temperature drift Hysteresis 1…10 %
Output function 2-wire, NAMUR Switching frequency 5 kHz Voltage Nom. 8.2 VDC Non-actuated current consumption Actuated current consumption
ð (0,81 x Sn) mm
ð 2 % of full scale ð ± 10 %
ï 2.1 mA ð 1.2 mA
ATEX category II 1 G, Ex zone 0
ATEX category II 1 D, Ex zone 20
SIL2 as per IEC 61508
Threaded barrel, M12 x 1
Chrome-plated brass
DC 2-wire, nom. 8.2 VDC
Output acc. to DIN EN 60947-5-6 (NA-
MUR)
M12 x 1 male connector
Wiring Diagram
Functional principle
Inductive sensors detect metal objects con­tactless and wear-free. For this, they use a high-frequency electromagnetic AC field that interacts with the target. Inductive sensors generate this field via an RLC circuit with a ferrite coil.
Approval acc. to KEMA 02 ATEX 1090X Internal capacitance (Ci) / inductance (Li) 150 nF / 150 µH Device designation
Construction threaded barrel, M12 x 1 Dimensions 52 mm Housing material Metal, CuZn, chrome-plated Active area material Plastic, PA Max. tightening torque housing nut 10 Nm Connection flange connector, M12 x 1 Vibration resistance 55 Hz (1 mm) Shock resistance 30 g (11 ms) Protection class IP67 MTTF 6198 years acc. to SN 29500 (Ed. 99) 40 °C
Switching state LED yellow
É II 1 G Ex ia IIC T6 Ga/II 1 D Ex ia IIIC T115 °C Da (max. Ui = 20 V, Ii = 20 mA, Pi = 200 mW)
Edition • 2016-02-12T18:26:30+01:00
1 / 5 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
Page 2
Inductive sensor BI2-M12-Y1X-H1141
Distance D 24 mm
Distance W 3 x Sn
Distance T 3 x B
Distance S 1.5 x B
Distance G 6 x Sn
Diameter of the active area B Ø 12 mm
Edition • 2016-02-12T18:26:30+01:00
2 / 5 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
Page 3
Inductive sensor BI2-M12-Y1X-H1141
Accessories
Type code Ident no. Description Design
IMC-Di-22Ex-PNO/24VDC 7560003 2-channel isolating switching amplifier with M12x1 males,
for peripheral use, IP67, zones 2/22, input circuits II(1) Ex ia,
PNP transistor output NO
IM1-22EX-R 7541231 Isolating switching amplifier, 2-channel; 2 relay outputs; in-
put NAMUR signal; selectable ON/OFF mode for wire-break
and short-circuit monitoring; adjustable output mode (NO /
NC mode); removable terminal blocks; width 18 mm; univer-
sal power supply unit
QM-12 6945101 Quick-mount bracket with dead-stop; material: Chrome-plat-
ed brass Male thread M16 x 1. Note: The switching distance
of proximity switches can be reduced by the use of quick-
mount brackets.
BST-12B 6947212 Fixing clamp for threaded barrel devices, with dead-stop; ma-
terial: PA6
MW-12 6945003 Mounting bracket for threaded barrel devices; material: Stain-
less steel A2 1.4301 (AISI 304)
Edition • 2016-02-12T18:26:30+01:00
3 / 5 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
Page 4
Inductive sensor BI2-M12-Y1X-H1141
Accessories
Type code Ident no. Description Design
BSS-12 6901321 Mounting bracket for smooth and threaded barrel devices;
material: Polypropylene
Wiring accessories
Type code Ident no. Description Design
RKC4.221T-2/TEB 6628420 Connection cable, female M12, straight, 2-pin, cable length: 2
m, sheath material: PVC, black; cULus approval; other cable
lengths and qualities available, see www.turck.com
Edition • 2016-02-12T18:26:30+01:00
4 / 5 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
Page 5
Inductive sensor BI2-M12-Y1X-H1141
Operating manual
Intended use
This device fulfills the directive 94/9/EC and is suited for use in explosion hazardous areas according to EN60079-0:2012, -11:2012, -26:2007. Further it is suited for use in safety-related systems, including SIL2 as per IEC 61508. In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II 1 G and II 1 D (Group II, Category 1 G, electrical equipment for gaseous atmospheres and category 1 D, electrical equipment for dust atmo­spheres).
Marking (see device or technical data sheet)
É II 1 G and Ex ia IIC T6 Ga acc. to EN60079-0 and -26 and É II 1 D Ex ia IIIC T115°C Da acc. to EN60079-0
Local admissible ambient temperature
ATEX category II 2 G electrical equipment -40…+70°C, category II 1 D -25…+70 °C. The corresponding temperature classes are provided in the ATEX type-examination certificate.
Installation / Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas. Please verify that the classification and the marking on the device comply with the actual application conditions.
This device is only suited for connection to approved Exi circuits compliant to EN60079-0 and -11. Please observe the maximum admissible electrical values. After connection to other circuits the sensor may no longer be used in Exi installations. When interconnected to (associated) electrical equip­ment, it is required to perform the "Proof of intrinsic safety" (EN60079-14). When employed in safety systems to IEC 51408 it is required to assess the failure probability (PFD) of the complete circuitry.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and avoid build-up of dust deposits on the device. If the devices and the cable could be subject to mechanical damage, they must be protected accordingly. They must also be shielded against strong electro-magnetic fields. The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet.
service / maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important data from the approval are listed.
Edition • 2016-02-12T18:26:30+01:00