TURCK BI1.5-EG08K-Y1 User guide

BI1.5-EG08K-Y1 Inductive Sensor
Features
Threaded barrel, M8 x 1
Stainless steel, 1.4427 SO
DC 2-wire, nom. 8.2 VDC
Output acc. to DIN EN 60947-5-6 (NAMUR)
Cable connection
ATEX category II 1 G, Ex zone 0
ATEX category II 1 D, Ex zone 20
SIL2 (Low Demand Mode) acc. to IEC 61508,
PL c acc. to ISO 13849-1 at HFT0 SIL3 (All Demand Mode) acc. to IEC 61508,
PL e acc. to ISO 13849-1 with redundant configuration HFT1
Technical data
Type
Rated switching distance 1.5mm
Mounting conditions Flush
Secured operating distance ≤(0.81×Sn)mm
Correction factors St37 = 1; Al = 0.3; stainless steel = 0.7; Ms
Repeat accuracy ≤2% of full scale
Temperature drift ≤ ± 10 %
Hysteresis 1…10%
Ambient temperature -25…+70°C
Output function 2-wire, NAMUR
Switching frequency 5kHz
Voltage Nom.8.2VDC
Non-actuated current consumption ≥2.1mA
Actuated current consumption ≤1.2mA
Approval acc. to KEMA 02 ATEX 1090X
Internal capacitance (Ci)/inductance (Li) 150 nF/150 µH
Device marking
Design
Dimensions 23.6mm
Housing material Stainless steel, 1.4427 SO
Active area material Plastic, PA12-GF20
BI1.5-EG08K-Y1
= 0.4
É II 1 G Ex ia IIC T6 Ga/II 1 D Ex ia IIIC T95 °C Da
(max. Ui = 20 V, Ii = 60 mA, Pi = 130 mW)
Threaded barrel,M8 × 1
Wiring diagram
Functional principle
Inductive sensors detect metal objects contactless and wear-free. For this, they use a high-frequency electromagnetic AC field that interacts with the target. Inductive sensors generate this field via an RLC circuit with a ferrite coil.
BI1.5-EG08K-Y1 | 12/03/2020 03-05 | technical changes reserved
TURCK Inc. | 3000 Campus Drive Minneapolis, MN 55441-2656 | Phone: 763-553-7300 | Application Support: 1-800-544-7769 | Fax 763-553-0708 | www.turck.com
1|4
Technical data
End cap Plastic, PP
Max. tightening torque of housing nut 5Nm
Electrical connection Cable
Cable quality Ø4mm, Blue, Lif9YYW, PVC, 2m
Core cross-section
2x0.25mm
2
Vibration resistance 55Hz (1 mm)
Shock resistance 30g (11 ms)
Protection class IP67
MTTF 6198years acc. to SN 29500 (Ed. 99) 40
°C
Mounting instructions
Mounting instructions/Description
Distance D 2 x B
Distance W 3 x Sn
Distance T 3 x B
Distance S 1.5 x B
Distance G 6 x Sn
Diameter active
Ø8mm
area B
TURCK Inc. | 3000 Campus Drive Minneapolis, MN 55441-2656 | Phone: 763-553-7300 | Application Support: 1-800-544-7769 | Fax 763-553-0708 | www.turck.com
BI1.5-EG08K-Y1 | 12/03/2020 03-05 | technical changes reserved
2|4
Accessories
BST-08B 6947210
Mounting clamp for threaded barrel sensors, with dead-stop; material: PA6
MW-08 6945008
Mounting bracket for threaded barrel sensors; material: Stainless steel A2
1.4301 (AISI 304)
MBS80 69479
Mounting clamp for smooth barrel sensors; mounting block material: Anodized aluminum
QM-08 6945100
Quick-mount bracket with dead­stop, chrome-plated brass, male thread M12 x 1. Note: The switching distance of proximity switches may be reduced through the use of quick­mount brackets.
BSS-08 6901322
Mounting clamp for smooth and threaded barrel sensors; material: Polypropylene
TURCK Inc. | 3000 Campus Drive Minneapolis, MN 55441-2656 | Phone: 763-553-7300 | Application Support: 1-800-544-7769 | Fax 763-553-0708 | www.turck.com
BI1.5-EG08K-Y1 | 12/03/2020 03-05 | technical changes reserved
3|4
Operating Instructions
Intended use
This device fulfills the directive 2014/34/EC and is suited for use in explosion hazardous areas according to EN 60079-0:2012 + A11 and EN 60079-11:2012.Further it is suited for use in safety-related systems, including SIL2 as per IEC
61508.In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II 1 G and II 1 D (Group II, Category 1 G, electrical equipment for gaseous atmospheres and category 1 D, electrical equipment for dust atmospheres).
Marking (see device or technical data sheet)
É II 1 G and Ex ia IIC T6 Ga and É II 1 D Ex ia IIIC T95 °C Da acc. to EN 60079-0, -11
Local admissible ambient temperature
-25…+70 °C
Installation/Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas.Please verify that the classification and the marking on the device comply with the actual application conditions.
This device is only suited for connection to approved Exi circuits according to EN 60079-0 and EN 60079-11. Please observe the maximum admissible electrical values.After connection to other circuits the sensor may no longer be used in Exi installations. When interconnected to (associated) electrical equipment, it is required to perform the "Proof of intrinsic safety" (EN60079-14).Attention! When used in safety systems, all content of the security manual must be observed.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and avoid build-up of dust deposits on the device.If the devices and the cable could be subject to mechanical damage, they must be protected accordingly. They must also be shielded against strong electro-magnetic fields.The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet.
Service/Maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important data from the approval are listed.
BI1.5-EG08K-Y1 | 12/03/2020 03-05 | technical changes reserved
TURCK Inc. | 3000 Campus Drive Minneapolis, MN 55441-2656 | Phone: 763-553-7300 | Application Support: 1-800-544-7769 | Fax 763-553-0708 | www.turck.com
4|4