BI0.8-EG05-Y1/S100
Inductive Sensor – With Increased Temperature Range
Features
Threaded barrel, M5 x 0.5
■
Stainless steel, 1.4427 SO
■
Temperatures up to +100 °C
■
DC 2-wire, nom. 8.2 VDC
■
Output acc. to DIN EN 60947-5-6 (NAMUR)
■
Cable connection
■
ATEX category II 1 G, Ex-zone 0 for
■
temperatures up to +80 °C
ATEX category II 2 G. Ex-zone 1
■
ATEX category II 1 D, Ex-zone 20 for
■
temperatures up to +70 °C
SIL2 (Low Demand Mode) acc. to IEC 61508,
■
PL c acc. to ISO 13849-1 at HFT0
SIL3 (All Demand Mode) acc. to IEC 61508,
■
Technical data
PL e acc. to ISO 13849-1 with redundant
configuration HTF1
Type
Ident. no. 1003201
Rated switching distance 0.8mm
Mounting conditions Flush
Secured operating distance ≤(0.81×Sn)mm
Correction factors St37 = 1; Al = 0.3; stainless steel = 0.7; Ms
Repeat accuracy ≤2% of full scale
Temperature drift ≤ ± 10 %
Hysteresis 1…10%
Ambient temperature -25…+100°C
Output function 2-wire, NAMUR
Switching frequency 5kHz
Voltage Nom.8.2VDC
Non-actuated current consumption ≥2.1mA
Actuated current consumption ≤1.2mA
Approval acc. to KEMA 02 ATEX 1090X
Internal capacitance (Ci)/inductance (Li) 150 nF/150 µH
Device marking
BI0.8-EG05-Y1/S100
= 0.4
≤ ± 20 %, ≥ +70 °C
For explosion hazardous areas see
instruction leaflet
É II 1 G Ex ia IIC T6 Ga/II 1 D Ex ia IIIC
T115 °C Da
(max. Ui = 20 V, Ii = 60 mA, Pi = 80 mW)
Wiring diagram
Functional principle
Inductive sensors detect metal objects
contactless and wear-free. For this purpose
they use a high-frequency electromagnetic AC
field that interacts with the target. The sensors
hosting a ferrite core coil generate the AC field
through an LC resonant circuit.
Special versions are available for ambient
temperatures between ‐60°C and +250°C.
TURCK Inc. | 3000 Campus Drive Minneapolis, MN 55441-2656 | Phone: 763-553-7300 | Application Support: 1-800-544-7769 | Fax 763-553-0708 | www.turck.com
BI0.8-EG05-Y1/S100 | 12/03/2020 04-26 | technical changes reserved
1|3

Technical data
Design
Threaded barrel,M5 × 0.5
Dimensions 30mm
Housing material Stainless steel, 1.4427 SO
Max. tightening torque of housing nut 5Nm
Electrical connection Cable
Cable quality Ø3mm, Blue, Lif9YYW, PVC, 2m
Core cross-section
2x0.14mm
2
Vibration resistance 55Hz (1 mm)
Shock resistance 30g (11 ms)
Protection class IP67
MTTF 6198years acc. to SN 29500 (Ed. 99) 40
°C
Mounting instructions
Mounting instructions/Description
Distance D 2 x B
Distance W 3 x Sn
Distance T 3 x B
Distance S 1.5 x B
Distance G 6 x Sn
Diameter active
Ø5mm
area B
TURCK Inc. | 3000 Campus Drive Minneapolis, MN 55441-2656 | Phone: 763-553-7300 | Application Support: 1-800-544-7769 | Fax 763-553-0708 | www.turck.com
BI0.8-EG05-Y1/S100 | 12/03/2020 04-26 | technical changes reserved
2|3

Operating Instructions
Intended use
This device fulfills the directive 2014/34/EC and is suited for use in explosion hazardous areas according to EN
60079-0:2012 + A11 and EN 60079-11:2012.Further it is suited for use in safety-related systems, including SIL2 as per IEC
61508.In order to ensure correct operation to the intended purpose it is required to observe the national regulations and
directives.
For use in explosion hazardous areas conform to classification
II 1 G and II 1 D (Group II, Category 1 G, electrical equipment for gaseous atmospheres and category 1 D, electrical equipment for
dust atmospheres).
Marking (see device or technical data sheet)
É II 1 G and Ex ia IIC T6 Ga acc. to EN60079-0 and -26 and É II 1 D Ex ia IIIC T115°C Da acc. to EN60079-0
Local admissible ambient temperature
ATEX category II 2 G electrical equipment -25…+100 °C, category II 1 G -25…+70 °C and category II 1 D -25…+70 °C. The
corresponding temperature classes are provided in the ATEX type-examination certificate.
Installation/Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have
knowledge of protection classes, directives and regulations concerning electrical equipment designed for use in
explosion hazardous areas.Please verify that the classification and the marking on the device comply with the actual
application conditions.
This device is only suited for connection to approved Exi circuits according to EN 60079-0 and EN 60079-11. Please
observe the maximum admissible electrical values.After connection to other circuits the sensor may no longer be
used in Exi installations. When interconnected to (associated) electrical equipment, it is required to perform the "Proof
of intrinsic safety" (EN60079-14).Attention! When used in safety systems, all content of the security manual must be
observed.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the
device in a dust flow and avoid build-up of dust deposits on the device.If the devices and the cable could be subject to
mechanical damage, they must be protected accordingly. They must also be shielded against strong electro-magnetic
fields.The pin configuration and the electrical specifications can be taken from the device marking or the technical data
sheet.
Service/Maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the
manufacturer. The most important data from the approval are listed.