Installation:
13
13
16
351mm
14
5
16
363mm
13
21
32
347mm
13
5
32
334mm
19
32
15mm
4
19
32
117mm
3
15
32
88mm
WIRING INPUT
INLET
1/2" COPPER TUBING
OUTLET
1/2" COPPER TUBING
CAT-09853-TUR
• Kickster Wall-Mount hydronic fan coils are suitable for
connection to a hot water supply at any pressure up to 300
psi with a maximum water temperature of 200°F.
• Building codes and plumbing regulations may vary.
Check local codes and regulations before determining
proper application and installation.
KWMIOM-3
Kickster Wall-Mount Fan Coil
Installation Instructions
Model KWM All Sizes
• Unit is designed to be mounted under sheetrock for proper
t of the cover. Install at least 6" - 8" above the oor for
best performance. Unit will t between standard 16" studs
on center.
• For unit dimensions on the KWM6 refer to Figure 1, 3 & 6.
For KWM11 refer to Figure 2, 4 & 7.
• Examine unit for shipping damage.
Figure 1 - KWM6
• Secure unit in proper position. Unit must be level to assure
proper drainage and operation.
1
![](/html/bc/bc43/bc43c37123b5009a27daed0539ee7edbd869cc6bb9595c94696a665de86a4412/bg2.png)
Figure 2 - K WM11
Piping
• e piping on the unit will usually be copper or any other
locally approved piping. Accessible ½” sweat ttings are
provided on the unit itself. An optional exible stainless
steel connector kit with shut-o valves is available for
connecting the unit to any type of piping system and can
be used with an optional valve control box.
• All piping systems should be designed by a technician
with experience in the various piping arrangements that
work with this type of unit.
• As with any system employing circulated water, the pipes
passing through unheated spaces should be insulated.
NOTE: When using mono-flo or “venturi” fittings, we
suggest placement of a ball valve just after the supply
take-off and before the return is connected.
Piping: Hot Water Boiler
• e unit supply line should be taken from the boiler side
beyond any o-control valve. If the system being used is
a gravity-ow or cast iron hot water system, a separate
circuit must be installed.
Piping: Water Heater
• To install correctly, a technician with knowledge of piping
arrangements and back-o valves must design the piping
system.
Wiring the Unit
• A eld wiring connection is provided on the unit (see
gure 5). Connect wires at this point only.
• e unit is manufactured with a built-in factory wired
aquastat with a set point of 140°F on and 110°F o. e
aquastat may be disabled in the eld if not required (see
application manuals).