Turbonics KWM6, KWM11 Installation Instructions Manual

Installation:
13
13 16
351mm
14
5
16
363mm
13
21 32
347mm
13
5
32
334mm
19 32
15mm
4
19 32
117mm
3
15 32
88mm
WIRING INPUT
INLET 1/2" COPPER TUBING
OUTLET 1/2" COPPER TUBING
CAT-09853-TUR
• Kickster Wall-Mount hydronic fan coils are suitable for connection to a hot water supply at any pressure up to 300 psi with a maximum water temperature of 200°F.
• Building codes and plumbing regulations may vary. Check local codes and regulations before determining proper application and installation.
KWMIOM-3
Kickster Wall-Mount Fan Coil
Installation Instructions
Model KWM All Sizes
• Unit is designed to be mounted under sheetrock for proper t of the cover. Install at least 6" - 8" above the oor for best performance. Unit will t between standard 16" studs on center.
• For unit dimensions on the KWM6 refer to Figure 1, 3 & 6. For KWM11 refer to Figure 2, 4 & 7.
• Examine unit for shipping damage.
Figure 1 - KWM6
• Secure unit in proper position. Unit must be level to assure proper drainage and operation.
1
OUTLET
INLET
Figure 2 - K WM11
Piping
• e piping on the unit will usually be copper or any other locally approved piping. Accessible ½” sweat ttings are provided on the unit itself. An optional exible stainless steel connector kit with shut-o valves is available for connecting the unit to any type of piping system and can be used with an optional valve control box.
• All piping systems should be designed by a technician with experience in the various piping arrangements that work with this type of unit.
• As with any system employing circulated water, the pipes passing through unheated spaces should be insulated.
NOTE: When using mono-flo or “venturi” fittings, we suggest placement of a ball valve just after the supply take-off and before the return is connected.
Piping: Hot Water Boiler
• e unit supply line should be taken from the boiler side beyond any o-control valve. If the system being used is a gravity-ow or cast iron hot water system, a separate circuit must be installed.
Piping: Water Heater
• To install correctly, a technician with knowledge of piping arrangements and back-o valves must design the piping system.
Wiring the Unit
• A eld wiring connection is provided on the unit (see gure 5). Connect wires at this point only.
• e unit is manufactured with a built-in factory wired aquastat with a set point of 140°F on and 110°F o. e aquastat may be disabled in the eld if not required (see application manuals).
Loading...
+ 2 hidden pages