Tuncmatik NEWTECH PRO II X9 User Manual

info@tuncmatik.com / www.tuncmatik.com
NEWTECH PRO II X9
1-2-3 KVA ONLINE
USER MANUAL
1
Table of Contents
1. Important Safety Warning ................................................................................................................. 2
1-1 Transportation ............................................................................................................................ 2
1-2 Preparation .................................................................................................................................. 2
1-3 Installation ................................................................................................................................... 2
1-4 Operation ...................................................................................................................................... 3
1-5 Maintenance, service and faults ........................................................................................... 3
1-6 Symbols used in this guide ..................................................................................................... 4
2. Installation and setup .......................................................................................................................... 4
2-1 Unpack checking ........................................................................................................................ 4
2-2 Real panel view .......................................................................................................................... 5
2-3 LCD control panel ...................................................................................................................... 7
2-4 Setup the UPS ............................................................................................................................. 7
3. Operations ................................................................................................................................................ 9
3-1 Button operation ........................................................................................................................ 9
3-2 LCD display ................................................................................................................................. 10
3-3 UPS setting ................................................................................................................................. 13
3-4 Operating Mode Description ................................................................................................ 15
3-5 Operational Status and Mode(s) ................................................................................... ….16
3-6 Alarm or Fault reference code ............................................................................................. 17
4. Troubleshooting ................................................................................................................................... 18
5. Storage and Maintenance ................................................................................................................. 19
6. Specification .......................................................................................................................................... 20
2
1. Important Safety Warning
Important safety instructions – Save these instructions
Please comply with all warnings and operating instructions in this manual strictly. Save
this manual properly and read carefully the following instructions before installing the
unit. Do not operate this unit before reading through all safety information and operating
instructions carefully
There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety instructions and
relative laws, otherwise it will result in personnel injury or equipment damage. Safety
instructions in this manual act as a supplementary for the local safety instructions. Our
company will not assume the liability that caused by disobeying safety instructions.
1-1 Transportation
Please transport the UPS system only in the original package to protect against shock
and impact.
1-2 Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments. Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1-3 Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them. Do not connect domestic appliances such as hair dryers to UPS output sockets. The UPS can be operated by any individuals with no previous experience. Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
3
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS
system.
When installing the equipment, it should ensure that the sum of the leakage current
of the UPS and the connected devices does not exceed 3.5mA.
1-4 Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
1-5 Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary when working with batteries:
remove wristwatches, rings and other metal objects
4
use only tools with insulated grips and handles.
When changing batteries, install the same number and same type of batteries. Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.
1-6 Symbols used in this guide
WARNING!
Risk of electric shock
CAUTION!
Read this information to avoid equipment damage
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. Please keep the original package in a safe place for future use.
2-1 Unpack checking
Don’t lean the UPS when moving it out from the packaging Check the appearance to see if the UPS is damaged or not during the transportation,
do not switch on the UPS if any damage found. Please contact the dealer right away.
Check the accessories according to the packing list and contact the dealer in case of
missing parts.
5
2-2 Real panel view
1kVA standart:
1kVA Ex. Batt:
2kVA Standart:
6
2-3kVA Ex Batt:
3KVA Standart:
1. AC input
2. Network / Fax / Modem Surge Protection(option)
3. Input circuit breaker
4. EPO(option)
5. USB communication port(option)
6. RS-232 communication port
7. SNMP intelligent slot (option)
8. Output receptacles
9. Battery Terminal
10. Output Terminal