Tucker SW10, SW19 Installation Manual

Page 1
!
920.1020.15
1
!
!
!
! !
!
!
!
!
!
!
SW10 (Full Power) & SW19 (Low Energy)
INSTALLATION GUIDE
Surface Mounted Applications
!
!
Page 2
!
920.1020.15
2
PAGE
CONTENTS
3
Important Notices
4
Product Description & Specifications
5-10
Header Installation
11-14
Mounting The Operator & Control Assembly
15-17
Push Arm Installation
17-18
Pull Arm Installation 19
120 Volt AC Connection
20
Power On & Indications
21-24
Set-Up Procedures
25
Wiring Connections
26
Adjusting The Mechanical Door Stop
27
Troubleshooting
28
Job Documentation & Closeout / Accessories / Company Contact
29-31
Appendix - Wiring Diagrams
32-33
Appendix - Fire Rated Door Application
25 (KP EVO 1-25)
Appendix - Tap Programming Device - KP evo
!
TABLE OF CONTENT
S:
!
!
Page 3
!
920.1020.15
3
!
IMPORTANT
READ THIS SECTION BEFORE PROCEEDING WITH INSTALLATION
Tucker Auto-Mation, LLC (hereafter referred to as “Tucker”) recommends that all of its automated pedestrian door products be installed by a trained automatic door technician and that the resulting performance of the product be in full compliance with the most current version of the American National Standards Institute document A156.10 or A156.19 (whichever is applicable) as well as any applicable building codes and/or fire codes. Tucker further recommends that a full inspection of the operating system be performed in accordance with the guidelines of the American Association of Automatic Door manufacturers (AAADM). This inspection must be performed by a certified AAADM trained inspector. Tucker recommends this documented inspection be performed upon completion of the installation as well as, following the completion of every service call thereafter. If service is not performed within one year of the previous service action, a routine AAADM inspection should be performed and documented. Under no circumstance should the product operate for more than one year without an AAADM inspection. Tucker does NOT recommend installation or service, on any of their automated pedestrian door products, by any individual who is not certified as an AAADM inspector.
Following the installation or service of any Tucker automated pedestrian door product, if it is deemed unsafe, or is operating in an unsatisfactory manner according to national performance standards or recommended performance guidelines as defined by Tucker, repairs should be made immediately. If an immediate repair cannot be made, the product should be disabled, and appropriate measures should be taken to secure the door in a safe position or to enable the door to safely be used manually. During this situation, every effort should be made to notify the owner (or person responsible) of the condition and to advise on corrective actions that must be taken to return the product to safe operation.
LOW ENERGY APPLICATION NOTE
When using the SW10/19 for a low energy application, Tucker Auto-Mation recommends the use of a door­mounted presence sensor on the approach side of the door to be used as a secondary activation device. This type of sensor can be installed at time of installation or can also be retrofitted. This device serves to re-activate the door to the open position should a person enter into the closing path at the approach side of the door, as it is closing. Once the door is fully closed, a "knowing act" device must then be used for initial activation. Tucker Auto-Mation considers this device to be essential in reducing the possibility of doors "timing out" and closing before all pedestrians have passed though the doorway. Check with your Tucker sales representative to find out about special incentives that may be available for the Torpedo 1 door-mounted presence sensor.
!
!
!
Page 4
!
920.1020.15
4
Power Supply
115
VAC (+6%, -10%)
60Hz
Power Consumpti
on
100W
C
urrent Consumpti
on
1A
Mot
or
24
VDC
Permanent Magnet
With Belt Driven Encoder
Header Dimensions
20 3/4” x 4 1/8” x 4 3/4”
(l
x w x d)
Fused Protection
3.5A Fuse (F1 locate
d on I/O Board)
Weight
22
lbs
Per Operator Assembly
Ambient Operating Temperature
-4 to 131º F
Ingress Protection
IP23 (protection from spray water up to 60º from th
e
vertical – ie. Rainst
orm)
Maximum
Door Weight
PUSH ARM
PULL ARM
36” Door: 438
lbs
342 lbs
42” Door: 328
lbs
256 lbs
44” Door: 299
lbs
234 lbs
48” Door: 254
lbs
198 lbs
24
VDC Accessories Power Supply
24
VDC
/
I A. Max
24
VDC Electric Lock
Power Supply
24
VDC
/
I A. Max
Adjustable Speeds & Timers
Opening Speed Closing Speed Hold
Open Tim
e
Closing Speed with power off
Standa
rd Select
or Switch Functions
Automati
c
Hold O
pen
Manual
(Off)
Standa
rd Control Outputs
Malfunction
Alarm Signal
Electric Lock
Relay
24
VDC Accessories Power Supply
Door
Status
Standa
rd Control Inputs
Interior Activati
on
Exterior Activati
on
Emergency Shutdow
n
Alarm Output “Stop” Safety Device (door-mounted) Safety Device Inpu
t
Secondary Activation
Quick Disconnects
TAP-Controller (optional)
!
PRODUCT DESCRIPTION & SPECIFICATIONS
The Tucker Auto-Mation SW10 & drives. The unique design offers; non-including sensors, push plates, fire alarm, and electric locks. Troubleshooting when needed. Both units can be configured concealed application. The Tucker Advanced Programmer (TAP) is provided as an option to access additional programming features.
! !
!
!
!
!
Page 5
!
920.1020.15
5
PUSH ARM APPLICATIONS:
Bottom of header is flush with bottom of top frame.
PULL ARM APPLICATION: STANDARD PULL ARM & DOUBLE EGRESS APPLICATIONS
Double egress applications require the use of an 80mm spindle adaptor for the side using the push arm.
NOTE:
Tucker Auto-Mation is now using a 35mm spindle adaptor for all standard push arm applications – this requires that the header assembly be mounted as shown at left, flush with bottom of top frame.
!
!
!
HEADER INSTALLATION
Mount the pre-drilled back-plate to the top door frame using appropriate fasteners for the type of frame. (Refer to Door Prep drawings on pgs. 6-10.)
Push side mounting: Pre-drilled back-plate is flush with bottom of door frame.
Pull side mounting: Pre-drilled back-plate is mounted 1.5” up from bottom door frame.
Back-plate should overlap each jamb tube by 1.5”.
Refer to the APPENDIX for fire rated door applications.
! !
!
!
!
! !
!
!
!
! !
!
!
!
! !
!
!
!
!
!
!
!
Page 6
!
920.1020.15
6
Opening Width
Operator Width
X Dim
36"
39"
6.25"
42"
45"
12.25" 44"
47"
14.25"
48"
51"
18.25"
!
Door Prep drawings:
PUSH SIDE INSTALLATION SINGLE
!
!
Page 7
!
920.1020.15
7
Opening Width
Operator Width
A Dim
C Dim
72" 75"
12-7/16"
N/A
84" 87"
N/A
10-7/8"
88" 91"
N/A
14-7/8"
96" 99"
24-7/16"
22-7/8"
!
PUSH SIDE INSTALLATION DOUBLE
!
!
Page 8
!
920.1020.15
8
Opening Width
Operator Width
Y Dim 36"
39"
6.25"
42"
45"
12.25" 44"
47"
14.25" 48"
51"
18.25"
!
PULL SIDE INSTALLATION SINGLE
!
!
Page 9
!
920.1020.15
9
Opening Width
Operator Width
A Dim
C Dim 72" 75"
12-7/16"
N/A
84" 87"
N/A
10-7/8"
88" 91"
N/A
14-7/8"
96" 99"
24-7/16"
22-7/8"
!
PULL SIDE INSTALLATION DOUBLE
!
!
Page 10
!
920.1020.15
10
Opening Width
Operator Width
A Dim
C Dim 72" 75"
12-7/16"
N/A
84" 87"
N/A
10-7/8" 88" 91"
N/A
14-7/8"
96" 99"
24-7/16"
22-7/8"
!
DOUBLE EGRESS INSTALLATION
!
!
Page 11
!
920.1020.15
11
!
MOUNT THE OPERATOR(S)!!
!
Operator is non-handed – same operator for all hands of doors
Handing is determined by how the operator is mounted inside the header
The operator is mounted to a short aluminum “drive” plate that is held into the header by 5 mounting screws.
Four (4) of the screws secure the drive plate. One (1) screw is used to locate the drive plate using a ‘keyhole’ configuration. The keyhole allows for easy removal of the drive plate without the need to loosen to screw. Removing the four (4) screws allows the drive plate & operator to be removed from the header and rotated 180 degrees to change from a push to a pull or vice versa.
!
Drive Plate mounted in standard position using four (4) screws to secure. Loosen the screws using an 5 mm allen wrench and slide each one off of the drive plate.
!
Drive plate removed by shifting to the left and lifting the drive plate off of the locating screw.
!
!
! !
!
!
!
!
!
Page 12
!
920.1020.15
12
!
!
!
!
Drive plate rotated 180 degrees to reverse the operator handing. Re-align locating screw to key slot, insert drive plate and shift to the right into position. Re-position the four (4) screws to secure the drive plate.
!
Key slot configuration & location screw mounted in backplate
!
!
! !
!
!
!
! !
!
!
!
!
!
!
Page 13
!
920.1020.15
13
PUSH = I/O BOARD IS TOWARDS THE HINGE JAMB
!
!
!
! !
!
!
!
! !
!
!
!
! !
!
!
! !
!
!
!
! !
!
!
!
! !
!
!
!
! !
!
!
!
! !
!
!
!
! !
!
!
! !
!
!
Page 14
!
920.1020.15
14
!
!
!
! !
!
!
!
! !
!
!
!
! !
!
!
! !
!
!
!
! !
!
!
!
!
Mount the header to the doorframe with the screws provided.
The header will overlap the doorframe by 1-1/2" at each side.!
!
!
!
!
Page 15
!
920.1020.15
15
!
!
!
PUSH ARM INSTALLATION
All push arms come standard with 35mm spindle. 50mm and 80mm available as an accessory.
Attach the primary door arm approx. 20 degrees past perpendicular and towards the closing direction as shown.
If more spring tension is desired, simply increase the mounting angle to greater than 20 degrees so it results in increased preload.
!
!
Page 16
!
920.1020.15
16
Reveal
Hinge Hung X Dim.
Center Pivot X Dim.
0
" 13
" 16
"
1
" 14
" 17
"
2
" 15
" 18
"
3
" 16
" 19
"
4
" 17
" 20
"
5
" 18
" 21
"
6
" 19
"
7
" 20
"
8
" 21
"
DEEPER REVEAL
REQUIRES ARM EXTENSION
!
Adjust the secondary telescopic arm to the prescribed length according to chart:
Before installing
insert the secondary and primary arm into the sleeve as it will
Slide
o o o
o Mark a
Attach the secondary arm mounting bracket to the door. The centerline of the bracket should be at 13-1/2” in
from the inside face of the hinge jamb when using butt hinges on the door, and 16” when using a center pivoted door.
the short arms within the sleeve to obtain the prescribed Tighten the screws on the short arm that Double-check
r shoe and the center of the hole
doo
imary
pr
any porti
the
pencil line
arm.
This will
on of the door arm assembly, it is easiest to
be when installed on the door:
is
connected to the door shoe.
"X" dimension of the arm - this is
at the pivot
at the edge of the sleeve where it overlaps
make it easie
r when positioning
the distance between the center of the hole
point of the primary arm (as shown).
the primary arm for
lay
the arm out on a flat
"X" dimension.
the short arm that
final installation.
is
connected to the
surface and
at the
!
!
Page 17
!
920.1020.15
17
Standard Pull Arm For 0-degree reveal Use 20mm spindle
Offset (double egress) Pull Arm For reveal greater than 0 degrees Use 20mm Spindle
Slide Track
!
Rotate the primary arm in the opening direction as to reach the pivot point of the secondary. Attach the arms
together with the hardware provided.
PULL ARM INSTALLATION
!
!
Page 18
!
920.1020.15
18
!
Install the slide track assembly at the pull side of the door at the proper location from the hinge end of the door
as shown below:
To install the pull arm, the operator must be powered to the full open position, as it is not possible to install the
arm in the closed position as to allow proper preload.
Power the door to the open position through the use of the hold-open switch on the side of the header. It may
be necessary to first execute a “setup” on the operator prior to doing this. Refer to the applicable section within this User’s Guide for proper instruction.
Once the operator is rotated to the full open position, manually move the door to the desired full open position
and insert the slide track guide block into the track. When completed, the end caps to the track can be installed.
!
!
Page 19
!
920.1020.15
19
BLACK: 115 VAC Power WHITE: Neutral GREEN: Ground
WARNING:
Ensure all incoming electrical power is shut off before proceeding with any wiring to
SW10/19. Use only with wire harness provided; failure to do so may result in damage to
equipment or personal harm as well as voiding the warranty.
!
120 VOLT AC ELECTRICAL CONNECTION
!
Connect the main power to the Black / White / Green connector on the back-plate.
o Main power supply: 120 VAC, 15A, Single Phase, 60 Hz. circuit o Attach the incoming 120 volt AC line wires to the wiring provided in the header – as
shown below.
DO NOT TURN POWER ON until all remaining wiring has been completed.
!
! !
! ! ! !
! ! ! !
!
!
!
!
!
Page 20
!
920.1020.15
20
DL1 : GREEN USB CONNECTION DL2: FLASHING RED LED DL3: BLUE 5V POWER SUPPLY DL4: BOARD VALUES DIFFER FROM DIP SWITCHES (PRESS SW1 MOMENTARILY TO EXTINGUISH YELLOW LED)
!
!
!
POWER ON & INDICATIONS
! ! !
! ! ! ! !
! ! ! ! !
! ! !
Upon applying power, observe the above LED’s. NORMAL OPERATION: DL3 will come on steady and then begin flashing after a few seconds. FAULTY OPERATION; DL2 will be flashing red. This indicates…
An error condition exists – correct as necessary
Operator requires setup – launch a setup and proceed accordingly
NOTE: DL4 will illuminate yellow anytime a change has been made to the control, such as a speed or time adjustment. Momentarily press on SW1 to acknowledge the change and extinguish the yellow LED.
HELPFUL NOTES:
Speed and time adjustment changes will not take effect until the door closes fully after the adjustment has
been made.
Hold Open time affects the delay following activation from input 10, 11, and 13.
When Dip Switch 5 is ON, the blue speed and time potentiometers are disabled and will have no effect.
!
!
!
Page 21
!
920.1020.15
21
!
SET-UP PROCEDURES
Perform a setup at the control as follows:
o Ensure main power is on o At the I/O control board, depress the SW1 button for approximately 5 seconds.
When the red LED (LD2) at the Adjustment Board begins flashing rapidly, release the button. The blue LED will continue flashing.
o Door will slowly go open, recycle partially, close and then re-open. o Do not interrupt the process and do not move the door manually during this
time.
o If the door does not open and the red LED (DL2) is flashing slowly, check to make
sure the motor is plugged in properly at the control board. Correct as necessary.
o Once the setup process is complete, the door will close and the LED will go out. o Setup is complete.
IMPORTANT NOTE: If the operator stroke is altered in any way, a re-learn must be accomplished.
Upon completion of the Setup, activate the door to open and ensure all performance is
acceptable.
Adjust opening and closing speed as necessary. If speeds are changed, a re-learn is not
required.
A re-learn is not required following a main power recovery.
Adjust hold-open time as required.
Additional adjustments are available through the TAP.
!
!
Page 22
!
920.1020.15
22
SETUP BUTTON
!
B1 – Battery – use CR1216 battery – required to maintain timer settings and date programmed by the TAP TR1 – Opening speed adjustment TR2 – Closing speed adjustment TR3 – Hold-open time adjustment TR4 – Closing speed adjustment when power is OFF TR4 will only be enabled when jumper J6 is moved to the correct
pins. (it is enabled by default).
J2 – USB port J4 – Ribbon cable connector between boards J5 – Motor Connector J7 – Power supply connector between boards SW1 – “Parameter Changed” button SW2 – 10 Position “Functions” Dip Switch
For adjustments beyond those mentioned herein, use the TAP. See TAP Users Guide for additional information.
!
!
Page 23
!
920.1020.15
23
DS1 NOT USED
DS2
SW2
!
SET THE DIP SWITCHES ON THE I/O BOARD
!
Set the dip switches according to the application.
Dip switches are used to apply specific functions to the control.
There are 3 sets of dip switches. TWO 2 - POSITION on the I/O board (DS1 & DS2), and a 10-
position at the adjustment board (SW2).
!
!
! ! ! !!!!
! ! ! !
SET THE DIP SWITCHES ON THE ADJUSTMENT BOARD
!
!
!
Set the dip switches according to the application.
!
Page 24
!
920.1020.15
24
Description
ON
OFF
1
Closed Door Force
Additional force applied while door is in closed position. Be sure to maintain ANSI compliance if using on low energy application. Cannot exceed 30 lbf to get door moving from jamb.
Disabled (Default)
2
Push / Pull Arm
Slide Arm Application. Operator stroke at 90° degrees or less. Visible change in performance may not always be noticeable.
Push Arm Application. Operator stroke 90° or greater. (Default)
3
Night Function (Exit Only)
Allows activation at input 10 when On-Off switch is in OFF (night function) position.
Disabled. The On/Off switch, when OFF, requires manual operation of the door. (Default)
4
Push and Go
Enabled
Disabled (Default)
5
Full Power / Low Energy
Low Energy performance enabled. 5 seconds to open, 7 seconds hold open, 5 seconds to close. Speed & time potentiometers are disabled. Settings are fixed.
Disabled. Control can be adjusted for full power or low energy operation via potentiometers. (Default)
6
Lockout Function
Overhead presence sensor input (17) is inhibited during closing cycle unless input 14 is triggered. Connect COM and Input 14 to NC output of lockout safety beam.
Disabled. Overhead presence sensor input (17) is inhibited during closing cycle. Otherwise, if commanded, it keeps an open door open and a closed door closed. A command at Input 14 will stall the door. (Default).
7
Inhibit at 30 Degrees Before Door Fully Open
Input is disabled at 30 degrees prior to full open door position. Eliminates need for external inhibiting switch.
Stall function remains un­inhibited for full door stroke. (Default)
8
Power Close
Additional closing force applied for final 10 degrees of closing.
Disabled (Default)
9
Assisted Manual Closing***
Enabled assisted closing following a manual opening
Disabled assisted closing following a manual opening
10
FACTORY USE ONLY
!
! ! !
!
*** Tucker Auto-Mation recommends the use of a door-mounted secondary activation device
when dip switch 9 is ON - Enabled.
!
!
Page 25
!
920.1020.15
25
Position
Function
Description
TERMINAL STRIP J5
1
Electric Lock Relay
Common
2
Electric Lock Relay
N.O. Dry contact – Contact closes upon activation. May be used for fail-secure locks by routing 1 leg of power though the relay. Relay is triggered by activation inputs 10, 11, or
16. Relay remains energized until door is fully closed again.
3
Electric Lock Relay
N.C. Dry Contact - Contact opens upon activation. May be used for fail-safe locks by routing 1 leg of power though the relay. Relay is triggered by activation inputs 10, 11, or
16. Relay remains energized until door is fully closed again.
4
Door Status ­Closed
N.O. Contact is closed when door is closed. The contact opens as soon as the door opens.
5
Door Status – Common
Common contact for door status
6
Door Status ­Open
N.C. – Contact is closed when door is open. The contact opens as soon as the door starts to close. This input can be used for motor connection at lockout relay when power is looped through, thus switching power on when door is open.
TERMINAL
STRIP J4
7
GND
Common GND
8
GND
Common GND
9
+ 24 VDC
I A. Max Current
10
Internal Activation
Requires N.O. Contact between input 10 & COM. Remains capable to activate when dip switch 3 is ON AND On-Off switch is OFF.
11
External Activation
Requires N.O. Contact between input 11 & COM.
12
Emergency Closing
Requires N.C. contact between 12 & COM. Upon open contact, door closes and overrides all other inputs. Remains jumpered if input is not used.
13
Secondary Activation
Requires N.C. contact between 13 & COM. Disabled in full closed position.
14
“Stall” Safety
Requires N.C. contact between 14 & COM. Upon open contact, (Dip 6 OFF) during opening, door stops, then resumes at reduced speed when input is released.
15
KEY
KEY IMPUT
16
Alarm Input
N.O. contact, when closed causes door closing. All inputs inhibited during closed contact (not available on all software versions)
17
Overhead Presence Sensor Input
Requires N.O. contact between 14 & +24 VDC (input 9). When input is closed it causes an open door to stay open and a closed door to stay closed. Works in conjunction with dip switch #6.
18
GND
Common GND
19
GND
Common GND
20
Aux Relay
Auxiliary Relay NOTE: Relay is triggered by input 14
21
Aux Relay
Auxiliary Relay N.O.
22
Aux Relay
Auxiliary Relay N.C.
23
Alarm Output ­Common
Common 24
Alarm Output
N.O. output is closed upon closed contact from fire alarm. LED 2 also illuminates.
25
+ 24 VDC
I A. Max Current
26
GND
Common GND
Inputs 27 & 28 not used
!
WIRING CONNECTIONS
!
I/O BOARD CONNECTIONS
(wiring diagrams are located in the Appendix)
!
!
Page 26
!
920.1020.15
26
!
ADJUSTING THE MECHANICAL DOOR STOP
CAUTION – DO NOT REMOVE THE STOPS
IMPORTANT - This step may be optional depending on your application
The mechanical stops are located on the top or bottom of the operator, depending on the
hand of the door.
Apply 120 VAC Main power to the control o Place the On-Off-Hold switch to the Hold Open position
!
!
Page 27
!
920.1020.15
27
Door will not open
Check On-Off switch for proper position
Check LED status for LD 5, 6, and 7. If any of these LED’s are OFF, the
door will not open. They require a normally closed circuit.
Launch a new setup – see page 26
Check status of emergency input 12
Door has traveled close past the 0 degree position
Door will not close
Check status of LEDs” LD2, 3, 4, 8 on the I/O board.
If any of the LED’s are ON, check the associated input
Door will not reach its full open or closed position
Check the mechanical stops on the operator for proper adjustment
Slow flashing red LED (LD2) at the Adjustment Control Board
Indicates a possible fault in the control. o Check LED status for the other inputs. This will identify if any
inputs are currently active.
Indicates a potential faulty setup.
o Loose or incorrect motor connection o Possible loose chain tensioner - refer to Appendix for chain
tensioner adjustment procedures.
o Launch a new setup. If problem repeats and there are no
other discrepancies noted, replace the operator/control sub­assembly.
Door closes too fast at last 5 to 10 degrees of closing
Ensure dip switch 8 is OFF.
Ensure there is no binding of the door as it is closing through the last
few degrees of closing. If binding exists (from a tight bottom sweep, for example), correct the condition and then re-launch a new setup.
!
TROUBLESHOOTING
!
!
Page 28
!
920.1020.15
28
!
JOB DOCUMENTATION & CLOSEOUT
Upon completion of the installation, provide the following to the Owner or their assigned
agent:
o Completed & signed work ticket. Be certain to record any serial numbers for items
that were replaced.
o Completed and signed copy of the AAADM inspection form o AAADM Owner’s Manual
Additionally, advise the Owner of the work that was performed and ask if there are any
other doors that may require service.
ACCESSORIES
Tucker BAT Microwave Motion Sensor - PN: 200.1068
Tucker TORPEDO ONE door-mounted presence sensor - PN: 200.1087
Spindle Adaptors 20, 50, 80 mm
TAP Controller – KP EVO
COMPANY CONTACT
Tucker Auto-Mation Supply, LLC
Toll Free: 1-855-8 TUCKER (1-855-888-2537) – Service: Tel. 412-823-2537 Email: sales@tuckerauto-mation.com
WWW.TUCKERAUTO-MATION.COM
!
!
Page 29
!
920.1020.15
29
!
APPENDIX - WIRING DIAGRAMS
LOW ENERGY APPLICATION: PUSH PLATES WITH APPROACH SIDE DOOR-MOUNTED SENSOR
!
! ! ! ! !
Non-Swing Side (approach) door-mounted sensor is wired into the secondary activation input (13)
at the SW19 I/O board. It is a normally closed circuit.
Door-mounted sensor will cause re-activation when in detection during the closing cycle.
Secondary activation input is disabled at the full closed door position.
Jumpers must be installed between terminal 8 and 12 & 14 if those inputs are not required for the
application. If they are used for the application, they must be connected to a N.C. circuit.
!
!
Page 30
!
920.1020.15
30
!
SIMULTANEOUS PAIRS
!
! !
!
!
Page 31
!
920.1020.15
31
!
When wiring controls for use as a simultaneous pair, all required inputs need to be
sync’d (connected) between Door #1 and Door #2 (shown as dotted lines in above diagram).
Example shown above: Push plates are connected to inputs 8, 10 and 11 at door #1
and are connected via sync line to Door #2.
When using pairs of controls, N.C. inputs 12, 13 and 14 may be sync’d to each other,
OR each control may have it’s own jumpers installed. If any of these inputs are required for the application, the jumper will be removed for the respective input – in place of the jumper, a N.C. switching circuit will connected to Door #1, and a sync line will be connected to Door #2.
For simultaneous pairs, Tucker Auto-Mation provides a dual harness for the On-Off-
Hold switch. Each plug-in connector for the control is wired in parallel to the On-Off­Hold switch located in the header end-cap. One switch will control both doors.
All control adjustments (speed & time delay) must be made independantly at each
control.
All dipswitches at each control must be set independantly and must match between
controls.
When using the TAP programmer, settings must be made independantly at each
control and must match between controls.
!
!
!
!
!
!
!
!
! !
!
!
!
!
!
!
Page 32
!
920.1020.15
32
!
!!!!!!!!!!!!!
APPENDIX - FIRE RATED DOOR APPLICATION
Perform the installation according to the instructions outlined in this manual.
Additionally, ensure the following conditions have been met:
o When attaching the door arm to the door,
use steel binding posts (Sex Bolts) to attach. Do NOT use sheet metal screws into the face of the door. The door arm bracket must be through-bolted.
o When attaching the header to
the hollow metal door frame, ensure there are 5 attaching screws spaced equally apart. They should be #12 sheet metal type screws.
!
!
Page 33
!
920.1020.15
33
!
o Fire rated power operated doors must close and latch during a fire alarm condition.
Ensure proper procedures have been followed to allow a main power disconnect during a fire alarm condition. Always check to ensure compliance to local building codes.
§ Upon job completion, always perform a functional test to ensure that the
door(s) close and latch following a power loss.
o Other hardware may be required to complete the installation. For example, for pairs
of doors, if an Astragal is installed, a mechanical door coordinator may be required to ensure a proper coordinated closing during a power loss.
o Only fire rated hardware shall be used on a fire rated door & frame assembly.
o Ensure the Tucker SW10/19 that is being installed has the proper fire rated label
applied to the header.
!
!
Page 34
!
920.1020.15
34
!
!
APPENDIX - TAP PROGRAMMING DEVICE
Please note, some functions of the SW10/19 controller require the use of a hand-held “TAP” programming device. The following functions require use of this device for programming:
ü Logic Assignment For Inputs ü Logic Assignment For Outputs ü Opening & Closing Acceleration ü Opening & Closing Deceleration ü Opening & Closing Strength (obstruction force) ü Opening & Closing Strength Duration (time duration for obstruction force) ü Night-Time Hold Open Time ü Delay On Activation (up to 4 seconds) ü Electric Lock Interfacing ü Master/Slave Configuration ü Cycle Count – Maintenance Reset ü 7-Day Programmable Timer (With Daylight Savings Time) ü Troubleshooting & Data
!
!
Page 35
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
TUCKER AUTOMATION
KP evo - TAP CONTROLLER
WWW.TUCKERAUTO-MATION.COM
Page 36
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
IMPORTANT
READ THIS SECTION BEFORE PROCEEDING WITH INSTALLATION
Tucker Auto-Mation, LLC (hereafter referred to as “Tucker”) recommends that all of its automated pedestrian door products beinstalled by a trained automatic door technician and that the resulting performance of the product be in full compliance with themost current version of the American National Standards Institute document A156.10 or A156.19 (whichever is applicable) as well as any applicable building codes and/or re codes. Tucker further recommends that a full inspection of the operating system be performed in accordance with the guidelines of the American Association of Automatic Door manufacturers (AAADM). This inspection must be performed by a certied AAADM trained inspector. Tucker recommends this documented inspection be performed upon completion of the installation as well as, following the completion of every service call thereafter. If service is not performed within one year of the previous service action, a routine AAADM inspection should be performed and documented. Under no circumstance should the product operate for more than one year without an AAADM inspection. Tucker does NOT recommend installation or service, on any of their automated pedestrian door products, by any individual who is not certied as an AAADM inspector. Following the installation or service of any Tucker automated pedestrian door product, if it is deemed unsafe, or is operating in an unsatisfactory manner according to national performance standards or recommended performance guidelines as dened by Tucker, repairs should be made immediately. If an immediate repair cannot be made, the product should be disabled, and appropriate measures should be taken to secure the door in a safe position or to enable the door to safely be used manually. During this situation, every eort should be made to notify the owner (or person responsible) of the condition and to advise on corrective actions that must be taken to return the product to safe operation.
TUCKER AUTOMATION
KP evo - TAP CONTROLLER
920.1003.02 | 01
WWW.TUCKERAUTO-MATION.COM
Page 37
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
TABLE OF CONTENTS
1. KP EVO ........................................ 3
1.1 Installation and connections .................. 3
1.2 Switching on and the home screen ............ 4
1.3 SELECTION menu ............................. 5
1.4 FUNCTIONS menu ............................ 6
2. DIAGNOSTICS ................................. 44
2.1 LEDs check ................................... 44
I/O board LEDs ................................. 44
Logic board LEDs .................................................................................................14
2.2 Inputs and outputs status check .................................................................................14
2.3 Automation status check ........................................................................................ 14
2.4 Warnings ......................................................................................................15
2.5 Errors ..........................................................................................................16
2.6 Other board data ...............................................................................................17
2.7 Firmware versions ..............................................................................................17
2.8 Log Data ....................................................................................................... 17
KP evo TABLES
A P EVO menu ................................................................. 07
 B Access permissions and passwords ............................... 13
 C I/O board LEDs .............................................................. 14
 D Logic board LEDs .......................................................... 14
 E Status ........................................................................... 14
 F Warnings ...................................................................... 15
G Errors ............................................................................ 16
 H Selecting theupload/download function ...................... 18
 I Scheduled maintenance ............................................... 21
3. UPLOAD / DOWNLOAD ........................................................................................ 18
4. PUT TING INTO SERVICE ....................................................................................... 19
4.1 Final checks ...................................................................................................19
4.2 Final operations ............................................................................................... 19
Installing a plastic cover ..........................................................................................19
Installing an aluminium cover ................................................................................... 20
5. MAINTENANCE ................................................................................................ 20
5.1 Inserting / replacing the battery ............................................................................... 20
5.2 Replacing the fuse ........................................................................................... 20
5.3 Routine maintenance ......................................................................................... 21
6. INTERCOM .................................................................................................... 22
6.1 Intermode ................................................................................................... 23
6.2 Interlock ..................................................................................................... 23
Interlock with no memory ....................................................................................... 24
Interlock with memory .......................................................................................... 24
6.3 2 Leaves ..................................................................................................... 24
6.4 2 Leav
es + Interlock .......................................................................................... 24
COMPANY ADDRESS............................................................................................
7.
WWW.TUCKERAUTO-MATION.COM
25
920.1003.02 | 02
Page 38
KP evo - TAP CONTROLLER
1. KP evo
1.1 INSTALLATION AND CONNECTIONS
CARRY OUT THE FOLLOWING OPERATIONS WITH THE ELECTRICITY SUPPLY DISCONNECTED
1. Disassemble the parts (01 ).
2. Break the cable passage insert.
With reference to 02, the KP EVO is designed
for the cables to enter from the back (1) or from underneath (2).
3. Decide where to position the support and x it
using suitable screws (01 -1).
4. Connect the KP EVO to the 950N2 using a 4 pair twisted U/UTP AWG24 cable with a maximum length of 50m (03).
INSTALLATION GUIDE
1
2
02
An optional key device can be connected between ter-
minals G and K in order to enable/disable the KP EVO.
5. Reassemble the parts indicated in (01 ).
1
1
1
max 50 m
U/UTP CAT.5
4x2xAWG24
J3 950N2
03
01
920.1003.02 | 03
WWW.TUCKERAUTO-MATION.COM
Page 39
KP evo - TAP CONTROLLER
1.2 SWITCHING ON AND THE HOME SCREEN
1. Turn power on to the 950N2
2. The display will show the following in sequence:
KP EVO
BOOTLOADER X.X
in which the Bootloader version appears, then
KP EVO
VERSION X.X
in which the rmware version appears, and lastly
A951
xxx dd/mm/yy
xxxxxx
hh:mm
INSTALLATION GUIDE
3. The 4 buttons are used to select controls that, depending on the screen, appear on the display above them.
4. By pressing the relative button on the home screen (04) you can:
- = set the NIGHT mode
-  = set the MANUAL mode - = switch to the FUNCTIONS menu that includes
all the 950N2 conguration parameters.
- = switch to the SELECTION menu that includes
additional operating modes.
By pressing the button to set the NIGHT or MANUAL
mode, the relative icon is highlighted and the descrip­tion of the operating mode is updated on the display. Once MANUAL mode has been set by pressing the relative button, press it again to return to the pre­vious mode.
The content of this home screen, including the xed icons and those that may appear under certain circum­stances, is explained in 04.
current warnings
A951
xxx dd/mm/yy
xxxxxx
timer active
set / deselect NIGHT mode
hh:mm
KP EVO locked
- product name
- day and date or error
- operating mode
- time
switch to the SELECTION menu
switch to the FUNCTIONS menuset / deselect MANUAL mode
04
920.1003.02 | 04
WWW.TUCKERAUTO-MATION.COM
Page 40
KP evo - TAP CONTROLLER
1.3 SELECTION MENU
To access the SELECTION menu from the home screen, press the button (05). 4 New icons appear on the display that dene the operating modes that can be set. The possible combinations can be obtained by press­ing the corresponding buttons (05). After having set the operating mode, press the OK button to conrm and return to the home screen.
The description of the operating mode on the display
is updated with the description of the one that has been set.
description of the current operating mode
INSTALLATION GUIDE

AUTOMATIC
ALWAYS OPEN
INTERLOCK (press for 5 s)
%
xxxxxx
BI-DIRECTIONAL

EXIT ONLY
ENTRY ONLY
OK
conrm and return to the home screen
TOTALLY
100%
OPEN
PARTIAL
%
OPEN
05
920.1003.02 | 05
WWW.TUCKERAUTO-MATION.COM
Page 41
KP evo - TAP CONTROLLER
1.4 FUNCTIONS MENU
To access the FUNCTIONS menu from the home screen, press the button (06). The display prompts for a 4-digit password to be entered.
INSTALLATION GUIDE
1 LANGUAGE
2 PROGRAMMING
The factory-set password is: 0000
- Set the rst digit using the and buttons.
- Conrm using the OK button to move to the next
digit.
- When all 4 digits have been entered, if the pass-
word is correct, access the FUNCTIONS menu as a
USER or a TECHNICIAN.
- Select the item from the menu using the and buttons.
- Conrm using the OK button to enter.
Press ESC at any time to return to the home screen.
menu items
3 ERRORS
4 WARNINGS
5 CYCLES COUNT
6 DATE/TIME
7 TIMER
8 PASSWORD
8 INFO
menu name
return to the home screen
ENTER PASSWORD
****
sets the value
conrms the
value
quits without
saving and
returns to the
previous menu
>1 xxxxxxxx 2 xxxxxxxx 3 xxxxxxxx 4 xxxxxxxx
selects an item
from those listed
in the menu
MENU
conrms the
selection
06
920.1003.02 | 06
WWW.TUCKERAUTO-MATION.COM
Page 42
KP evo - TAP CONTROLLER
 A KP EVO menu
1 LANGUAGE
1 ITALIANO 2 ENGLISH 3 FRANCAIS 4 DEUTSCH 5 ESPANOL 6 NEDERLANDS
2 PROGRAMMING
1 INPUTS / OUTPUTS
1 INPUTS I1-I8
I1…I8
0 DISABLED 1 EXTERNAL OPEN 4 INTERNAL OPEN 7 AUTOMATIC OPEN 8 SEMIAUTOM. OPEN 10 KEY 11 PARTIAL OPEN 20 CLOSING SAFETY 21 OPENING SAFETY 22 OVERHEAD PRES. SENS 30 EMERGENCY OPEN 31 EMERGENCY OPEN WITH MEM 34 EMERGENCY CLOSE 35 EMERGENCY CLOSE WITH MEM
36 FIRE ALARM
40 ALWAYS OPEN 41 EXIT ONLY 42 ONLY IN 43 NIGHT 44 MANUAL 45 PARTIAL 46 INTERBLOCK ON
2 OUTPUTS O1/O2
60 TIMER
01…O2
0 DISABLED 1 GONG 2 ERROR 4 EMERGENCY ACTIVATE 5 TEST 6 DOOR NOT CLOSED 7 DOOR OPENED 8 DOOR OPENING 9 LIGHT 10 INTRUSION ACTIVE 11 CLOSING SAFETY 12 SAFETIES
NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED
NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED TIME 1...90 S NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED NORMALLY OPENED / NORMALLY CLOSED
INSTALLATION GUIDE
ENABLED / DISABLED
TEST
ENABLED / DISABLED
TEST
NORMALLY OPENED / NORMALLY CLOSED
3 OP/CLRELAY
NORMALLY OPENED / NORMALLY CLOSED
4 EXTERNAL SELECTOR
POSITION 1…POSITION 2
0 DISABLED 1 NIGHT 2 OPENED 3 EXIT ONLY 4 MANUAL
920.1003.02 | 07
WWW.TUCKERAUTO-MATION.COM
Page 43
KP evo - TAP CONTROLLER
2 MOTION
1 OPENING...2 CLOSING
1...10
SLOWDOWN SPACE 0°...90°
0...10
0.1...3.0 s
1...10
1...10
0...30 s
0...30 s
0...90 s
0...90 s
WITH MEMORY / WITHOUT MEMORY
WITH MEMORY / WITHOUT MEMORY
3 TIMING
4 MOTOR LOCK KIT
ENGLISH
5 INSTALLATION
6 INTERCOM
1 SPEED 2 SLOWDOWN 3 STRENGTH 4 STRENGTH DURATION 5 ACCELERATION 6 DECELERATION
1 PAUSE TIME 2 PAUSE TIME 3 NIGHT PAUSE TIME 4 NIGHT SENSOR NIGHT
1 FUNCTION
2 LOCK DELAY 0...60 tenths of a second 3 RELEASE TYPE
1 ARM TYPE
2 SENSOR TYPE
3 START SETUP ARE YOU SURE ? 4 PUSH AND GO
5 PARTIAL STOP SEC.
6 LEAF DELAY 0°...90° 7 SCP
8 REVERSE STROKE
10 INOUT STATE IN1...IN8 01...02 11 DOOR STATUS 12 OTHER BOARD DATA V_MAIN V_ACC POS I_MOT
1 FUNCTION
2 MASTER/SLAVE NR. 3 INTERCOM REG. 4 NODE LIST
]
DISABLED NIGHT EXIT ONLY NIGHT + MONODIR ALWAYS
WHEN OPENING CLOSED
SKID ARTICULATE
DOOR MOUNTED SYSTEM OPS AND BEAM
0 DISABLED 1 ENABLED 2 FAST FOOD
DISABLED ENABLED
DISABLED ENABLED
DISABLED ENABLED
DISABLED INTERMODE INTERLOCK 2 LEAVES 2 LEAVES + INTERBLOCK
INSTALLATION GUIDE
SLOWDOWN SPEED 1...3
920.1003.02 | 08
WWW.TUCKERAUTO-MATION.COM
Page 44
KP evo - TAP CONTROLLER
7 MISCELLANEOUS
1 DEFAULT DEFAULT
2 BOARD'S DISPLAY
3 INTRUSION
4 KPEVO KEY
5 CONSECUTIVE OBST.
6 TEST ERROR
3 ERRORS
The display shows any current errors
4 WARNINGS
the display shows any current warnings
5 CYCLES COUNT
1 CYCLES NUMBER
ABSOLUTE RELATIVE
2 MAINTENANCE
MAINTENANCE DATE MAINTENANCE CYCLES
3 CYCLES RESET ARE YOU SURE ? resets the number of cycles
ACTIVATE NO
STOPPED NOT BLOCKED
DISABLED ENABLED
WITHOUT USER PSW BLOCK
CLOSING OPENING
DISABLED ENABLED
DO YOU WANT TO LOAD
0...10
0...10
INSTALLATION GUIDE
DEFAULT CONFIG ?
ENGLISH
6 DATE/TIME
1 SET DATE 2 SET TIME 3 DAYLIGHT SAV TIME
DISABLED
7 TIMER
ENABLED
1 TIMER STATE
DISABLED ENABLED
2 MONDAY 3 TUESDAY 4 WEDNESDAY 5 THURSDAY 6 FRIDAY 7 SATURDAY 8 SUNDAY 9 MON - SUN 10 MON - FRI 11 JOLLY 12 JOLLY SLOTS
SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 APPLY (appears only if selected LUN - SUN or LUN - FRI)
920.1003.02 | 09
WWW.TUCKERAUTO-MATION.COM
Page 45
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
FUNCTION: 0 FUNCTION: 1 FUNCTION: 2 FUNCTION: 3 FUNCTION: 4 FUNCTION: 5 FUNCTION: 6 FUNCTION: 7 FUNCTION: 8 FUNCTION: 9 FUNCTION: 10
8 PASSWORD
1 TECHNICIAN PSW
CHANGE TEC PSW REINSERT TEC PSW NEW PSW INSERTED
2 USER PSW
CHANGE USER PSW REINSERT USER PSW NEW PSW INSERTED
9 INFO
E950E E950E KP EVO
■ PROGRAMMING INPUTS/OUTPUTS
BOOT APP APP
VER *.* VER *.* VER *.*
NO FUNCTION AUTO BIDIR TOTAL AUTO OUT TOTAL AUTO BIDIR PARTIAL AUTO OUT PARTIAL TOTALLY OPEN PARTIAL OPEN AUTO IN TOTAL AUTO IN PARTIAL NIGHT PARTIAL
NIGHT
INPUTS
The inputs on terminal board J5 of the I/O board can be congured with the following functions
Each input can be set to NC or NO according to the
device connected to it.
Disabled
No associated function.
External open
When activated, the door opens and remains open as long as the input is active. When released, the door waits for the pause time to elapse and then closes. This has no eect in the EXIT ONLY or NIGHT modes.
Internal open
When activated, the door opens and remains open as long as the input is active. When released, the door waits for the pause time to elapse and then closes. This has no eect in the ONLY IN or NIGHT modes.
Automatic open
When activated, the door opens and remains open as long as the input is active. When released, the door waits for the pause time to elapse and then closes. Active in the BI-DIRECTIONAL, EXIT ONLY and ONLY IN modes. This has no eect in the NIGHT mode.
Semiautom. open
When activated:
- if the door is not already open, it opens and remains open
- if the door is already open, it closes e in the BI-DIRECTIONAL, EXIT ONLY and ONLY IN
Activ
modes.
This has no eect in the NIGHT mode.
BEGINNING END
hh:mm hh:mm
Key
When activated, the door opens and remains open as long as the input is active. When released, the door waits for the night pause
time to elapse and then closes.
Active in the BI-DIRECTIONAL, EXIT ONLY, IN ONLY and NIGHT modes.
Partial open
Only opens the master door when activated in the “2 leaves” mode.
Closing safety
When activated:
- If the door is closing, it reopens
- If the door is already open, it prevents it from closing
- If the door is opening, it has no eect
Opening safety
When activated:
- If the door is opening, it stops until it is released
- If the door is already closed, it prevents it from opening
- If the door is closing, it has no eect
Emergency open
When activated, the door opens (always total) and remains open as long as the input is active. When released, the door waits for the night pause time to elapse and then closes. Also active in NIGHT mode.
Emergency open with memory
When activated, the door opens (always total) and remains open as long as the input is active. When released, the open until it is Reset
Emergency close
ctivated, the door closes and remains closed as long as the in-
When a put is active. When released, the door returns to normal operation.
door remains
920.1003.02 | 10
WWW.TUCKERAUTO-MATION.COM
Page 46
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
Emergency close with memory
When activated, the door closes and remains closed as long as the input is active. When released, the door remains closed until it is Reset
Fire alarm
When activated, the door closes, regardless of the operating mode that has been set, with the lock kept in the released position. It has priority over any commands that may be active.
Always open
When activated, the ALWAYS OPEN mode is set.
Exit only
When activated, the EXIT ONLY mode is set.
Entry only
When activated, the ONLY IN operating mode is set.
Night
When activated, the NIGHT mode is set.
Manual
When activated, the MANUAL mode is set.
Partial
When activated, the PARTIAL mode is set.
Interblock ON
When activated, the INTERLOCK mode is set.
Timer
When activated, the TIMER mode is set.
OUTPUTS
The outputs on terminal board J5 of the I/O board can be congured with the following functions
Closing safety
The output is activated when a closing safety device is active.
Safeties
The output is activated when a closing or opening safety device is engaged.
OP/CL RELAY
Species the logic of the door status relay (NC/NO).
EXTERNAL SELECTOR
Species the operating mode associated with positions 1 and 2 of the selector on the side of the unit.
■ PROGRAMMING MOTION
OPENING/CLOSING Speed
Sets the speed of movement.
Deceleration
Species the space (in degrees of rotation of the 950N2 shaft) and the deceleration speed (on 3 levels) of the door before reaching the nal open / closed positions.
Strength
Species the maximum crushing force.
Strength duration
Species the maximum thrust time before an obstacle is recognised.
Acceleration
Species how quickly the door reaches the set opening speed when starting from stop.
Deceleration
Species how quickly the door stops.
Each input can be set to NC or NO according to the
device connected to it.
Disabled
No associated function
Gong
The output is activated and deactivated at 1-second intervals when the safety devices are engaged.
Error
The output is activated if there is an error.
Emrg. active
The output is activated when an Emergency is triggered.
Test
The output commands a FAILSAFE test on the inputs that are cong- ured as safety devices on which the option of running a TEST before movement has been enabled.
Door not closed
The output remains active until the door is closed.
Door open
The output remains active as long as the door is open.
Door opening
The output remains active as long as the door is moving.
Light
The output is activated, fo door is open in NIGHT mode.
Intrusion active
The output is activated when an intrusion is in progress (i.e. when an unexpected movement of the door from its closed position is detected).
.
r a programmable length of
time, when the
■ PROGRAMMING TIMING
PAUSE TIME
Denes the pause time of the door when opened by a command, before closing automatically.
PAUSE TIME P&G
Sets the door pause time when opened by a Push & Go command, before closing automatically.
Night PAUSE TIME
Sets the door pause time when opened by a command in NIGHT mode, before closing automatically.
NIGHT SENSOR DELAY
When NIGHTmode is set, the internal detector remains active for the amount of time set in this parameter, to allow it to be opened only once. The internal detector is disabled immediately after opening
and in any case upon expiry of the set delay.
■ PROGRAMMING MOTOR BLOCK KIT
FUNCTION
Species the operating mode in which the lock is activated.
LOCK DELAY
Species the opening delay time of the door to allow the lock to be released, particularly motorised locks.
RELEASE TYPE
Species when power is disconnected from the lock after it has been mechanically released:
Opening = during the opening phase Closed = when the door is closed again
920.1003.02 | 11
WWW.TUCKERAUTO-MATION.COM
Page 47
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
■ PROGRAMMING INSTALLATION
ARM TYPE
Species the type of transmission arm installed (shoe or articulated)
START SETUP
Carries out a Setup cycle after conrmation.
PUSH AND GO
Sets the function that commands the automatic opening of the door after an initial manual push:
Disabled = Push & Go not enabled Enabled = Push & Go enabled Fast food = Push & Go enabled in “FAST FOOD“mode (manual
opening, motorised closing)
PARTIAL STOP SEC.
Species the detection area of the safety in opening:
Disabled= obstacle detection active over the entire opening stroke Enabled= obstacle detection NOT active in proximity to the
opening stop
LEAF DELAY
Species the opening delay between the doors of 2 leaf models.
SCP
Species the function that pushes the door with a greater force in the nal section of the closure. It is useful to activate this function if there is high friction, if the seals are particularly rigid or if locks have a sti latch.
■ PROGRAMMING MISCELLANEOUS
CONFIG. DEFAULT
Shows whether the parameters have been modied, and if so, resets the factory defaults after conrmation.
BOARD'S DISPLAY
Not active.
INTRUSION
Sets the function in which the door resists attempts to open it manually.
KPEVO KEY
You can choose between:
Block = the user must enter the user password in order to access
the menus that he is authorised to use.
Without user psw = the user doesn’t need to enter the user
password in order to access the menus that he is authorised to use.
CONSECUTIVE OBST.
Species the maximum number of consecutive obstacle detections in the same direction of movement, before stopping in an error condition.
TEST ERROR
Species the eect that the TEST will have when it detects a safety device fault:
Disabled = the door will remain stationary in an error condition Enabled= the door will continue to operate at minimum speed
Because activating the SCP function also reduces the sensitivity of the electronic anti-crushing system the nal section of closing, DO NOT activate theSCP function in "low energy" mode.
REVERSE STROKE
Sets the function that makes the door carry out a short reverse stroke before opening to make it easier to the release the lock.
2 EASY REG.
Registration of BUS 2easy devices.
INOUT STATE
The display indicates the status (on / o) of inputs I1-I8 and outputs O1-O2 in real-time.
DOOR STATUS
The display indicates the status of the automation in real-time.
OTHER BOARD DATA
The display indicates useful diagnostics information in real-time.
■ PROGRAMMING INTERCOM
FUNCTION
Sets the operating mode.
MASTER/SLAVE NR.
Sets the network ID of the unit.
INTERCOM REG.
Registers the units of the network (to be performed only on the 950N2 with ID1).
NODE LIST
Shows the ID of the units registered (on the master).
in
■ ERRORS
In this menu, the display indicates any current errors that there may be in real time.
■ WARNINGS
In this menu, the display indicates any current alerts that there may be in real time.
■ CYCLE COUNTER
The 950N2 has two counters:
- total, non-resettable
- partial, resettable This menu allows you to view the cycles performed by the automa­tion and reset the partial counter. It is also possible to set a deadline for scheduled maintenance according to:
- date (optional)
- number of cycles (from 1000 to 1000000) Alert 60 will be displayed as soon as one of the two settings (date or number of cycles) is reached.
Logging in with the user password only allows data
to be viewed.
■ DATE/TIME
This menu allows you to set or modify the date, time and turn European summer time on / o.
920.1003.02 | 12
WWW.TUCKERAUTO-MATION.COM
Page 48
KP evo - TAP CONTROLLER
To keep the settings even if there is no mains power,
which is necessary for the TIMER to work correctly, a battery must be installed on the Logic board.
■ TIMER
This menu includes all the parameters for conguring the TIMER function. When the TIMER is enabled, the operating mode of the door during the programmed time bands is set automatically. A maximum of 6 daily time bands can be dened, and an operating mode, selected from those available, assigned to each one. Each time band has a start time and an end time. The time bands must not overlap.
When the TIMER is enabled, the T icon appears on
the home screen. To manually change the operating mode set by the
TIMER, it rst has to be disabled.
In order for the TIMER to work correctly, a battery must be installed on the Logic board.
INSTALLATION GUIDE
■ PASSWORD
This menu allows passwords to be set or modied. To access the FUNCTIONS menu you are prompted to enter a 4-digit
password.
The 950N2 has two passwords available, with dierent access rights (B)
In order to quickly program groups of days time bands, it is possible to simultaneously select all the days of the week (MON - SUN) and all weekdays (MON - FRI). Once the time bands that have been dened here have been conrmed using the
APPLY option, they will overwrite any time bands that have already
been programmed for individual days. If it is necessary to program specic days or periods (e.g. recurring holidays), you may use the JOLLY function. A maximum of 6 JOLLY time bands can be specied and an operating mode, selected from those available, assigned to each one. Each time band has a start time and an end time. The time bands must not overlap. The JOLLY time bands are then assigned to a maximum of 6 INTER- VALS. An interval can be a single day or a series of days.
If a single day is dened, the start and end date of
the interval must be the same. The interval must refer to same calendar year ple: for the period from 25/12 to 06/01, 2 intervals must be created, from 25/12 to 31/12 and from 01/01 to 06/01).
of the week with the
same
(exam-
B sdrowssap dna snoissimrep sseccA
LANGUAGE
PROGRAMMING
ERRORS
WARNINGS
CYCLES COUNT
DATE/TIME
TIMER
PASSWORD
INFO
TECHNICIAN PSW
 
    (*)     (*)
USER PSW
* with restrictions
The user is only allowed to modify the user password.
920.1003.02 | 13
WWW.TUCKERAUTO-MATION.COM
Page 49
KP evo - TAP CONTROLLER
2. DIAGNOSTICS
2.1 LEDS CHECK
I/O BOARD LEDS
Each input on the I/O board, has a LED that indicates the physical state of the contact:
C I/O board LEDs
LED
DL 1 accessories power on accessories power o DL 2 - DL9 open contact closed contact
LOGIC BOARD LEDS
There are 4 LEDs on the Logic board:
D Logic board LEDs
INSTALLATION GUIDE
E sutatS
CLOSED OPENING OPEN PAUSE NIGHT PAUSE CLOSING EMERGENCY ACTIVATE MANUAL NIGHT STOP SECURITIES TEST ERROR SETUP in progress
LED
DL 1 green
DL 2 red
DL 3 blue
DL 4 yellow
oonashingfast ashing
2.2 INPUTS AND OUTPUTS STATUS
The status of each input and output can be checked via the KP EVO. Go to menu 2.5.9. The display indicates the status of the logic as shown in 07. Example:
IN1
= input active
IN1
= input not active

no USB
normal con­dition
no power or board failure
boar d pa­rameters the same as trim­mer and DIP switch values
USB connect­ed
error
/
boar d pa­r amet ers dierent to trimmer and DIP swit ch values
S etup r e -
quested normal con-
dition
Button pressed
§
Setup in pro-
gress
/
/
CHECK
AMOTUA 3.2 TION STATUS CHECK
The current status of the automation system can be checked via the KP EVO. Go to menu 2.5.10. The display shows information regarding the status of the automation.
IN1 IN4
IN5
O1
IN2
IN6
O2
IN3
IN7
IN8
07
920.1003.02 | 14
WWW.TUCKERAUTO-MATION.COM
Page 50
KP evo - TAP CONTROLLER
2. 4 SGNINRAW
Alerts provide information regarding the status or current phase of the automation and errors that do not prevent it from operating. It is possible to check any current alerts via the KP EVO. Go to menu 4 to view the list of current alerts. If there is at least one alert, an icon appears on the home screen.
INSTALLATION GUIDE
F sgninraW
Date and time missing
41
- Reset date/time via the KP EVO Clock battery discharged or missing
42
Emergency active (including command memory)
44
Timer active
45
Timer function in progress
46
Night mode operation
48
Manual mode operation
49
Partial mode operation
50
Obstacle detected during closure
51
Obstacle detected during opening
52
Number of maintenance cycles on E
53
- Carry out a Reset.
- If the alarm persists, replace the Logic board Searching for strike on closing
58
Maintenance requested
60
KP EVO fault
61
- Check that the correct device is connected and check the connections.
- If the alarm persists, update the rmware
- If the alarm persists, replace the Logic board Intrusion in progress
63
Set-up in progress
65
TEST alarm (only if the “test error” parameter is enabled)
68
- Check the operation of the connected devices
- If the alarm persists, replace the device
- If the alarm persists, replace the Logic board In this condition, the door moves at a slower speed.
Door opened by a semi-automatic command
69
Slave Intercom mode
71
Intercom alarm
72
- Check the connections
- Check the ID
- If the alarm persists, replace the Logic board
Slave Error / Alarm
73
Interlock alarm
74
- Check the connections
- Check the ID
- If the alarm persists, replace the Logic boar Non-standard programming
80
2
prom corrupted
d
920.1003.02 | 15
WWW.TUCKERAUTO-MATION.COM
Page 51
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
2.5 SRORRE
Errors are malfunctions that prevent the automation system from working. They are indicated by a steady red LED on the Logic board. After every 5 minutes in which a fault condition persists and for a maximum of 20 consecutive times, the 950N2 will perform a Reset to attempt to restore normal operation so as not to require any action if the condition that caused the error was temporary. If the fault persists, remove the cause in order to restore
G srorrE
When an error occurs:
1. Check all the electrical connections
2. Carry out a reset.
3. If the problem persists, carry out the operations described in the table one at a time until the problem is resolved.
Board failure - Replace the Logic board
01
E2
02 03
04
05
07
09
11
12
15
16 18 19
22
prom failure - Replace the Logic board
Motor driver failure - Replace the Logic board
- Replace the motor
Accessories power supply fault - Check that the accessories power supply is not short circuited
- Check that maximum load of the accessories has not been exceeded
- Replace the Logic board
- Replace the I/O board
Microcontroller error - Reload/update the Logic board rmware
- Replace the Logic board
Motor failure - Replace the motor
- Replace the Logic board
Board voltage anomaly - Replace the Logic board
- Replace the I/O board
Closing safety TEST failed - Check the connections of the safety device
- Check that the safety device is working
- Replace the Logic board
Opening safety TEST failed - Check the connections of the safety device
- Check that the safety device is working
- Replace the Logic board
Setup inhibited - Make sure that Night or Manual mode has not been set.
- Make sure that an Emergency command has not been activated Encoder fault - Replace the Logic board Firmware not compatible - Update with the correct rmware High mechanical friction - Make sure that the leaf has been mounted correctly
remove any fric
- Replace the Logic board
- Replace the gearmotor Programming data corrupted - Reprogram the board or upload the program les that were saved to the USB
storage device.
- Replace the Logic board
normal operation. The type of error can be identied via the KP EVO The error code appears on the home page. Go to menu 5; the display provides information regarding the current error.
deriuqer noitcArorrE
and that it moves smoothly,
tion
920.1003.02 | 16
WWW.TUCKERAUTO-MATION.COM
Page 52
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
24
26
27 31
39
Consecutive obstacles in closing - Remove the obstacle in closing.
- Make sure that the leaf has been mounted correctly and that it moves smoothly, remove any friction
Lock failure - Check the wiring of the lock
- Check that the maximum load of the lock has not been exceeded
- Replace the lock
- Replace the Logic board
Motor rotation fault - Check the polarity of the motor cable Consecutive obstacles in opening - Remove the obstacle in opening
- Make sure that the leaf has been mounted correctly and that it moves smoothly, remove any friction
Setup data missing or corrupted - Perform Setup
- Replace the Logic board
O 6.2 THER BOARD DATA
Go to menu 2.5.11 of the KP EVO. The display provides information on the following parameters:
- V MAIN : input voltage to the Logic board (Volts)
- V ACC : output voltage for accessories (Volts)
- POS : position of the rotating shaft (degrees)
- I MOT : current drawn by motor (Amperes)
2.7 FIRMWARE VERSIONS
Go to menu 9 of the KP EVO to view the rmware versions of the bootloader, the Logic board and the KP EVO.
2.8 LOG DATA
The 950N2 records the last 512 system events. A battery must be installed on the Logic board in order to save the list of events in memory even if the system is switched o. To download the data as a text le, see § .
920.1003.02 | 17
WWW.TUCKERAUTO-MATION.COM
Page 53
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
3. UPLOAD / DOWNLOAD
There is a USB port on the Logic board via which the following operations can be carried out:
- Load data from a USB pen drive (UPLOAD).
- Save data to a USB pen drive (DOWNLOAD).
For both operations, the USB pen drive must be formatted with the FAT or FAT 32 le system.
The NTFS format is not recognised.
In order to upload, the les required, the names of which are indicated in H must be present in the root directory
of the USB pen drive.
1. Turn power o to the 950N2.
2. Insert the USB pen drive in the USB port (J2) on the Logic board.
3. Turn power on to the 950N2.
4. If the device is detected correctly, the green LED DL1 of the Logic (08) board lights up steadily.
5. The available functions are selected by briey pressing button SW1 on the Logic board (08). The
operation to be carried out is indicated by the number of ashes of the green LED. Each time the button is pressed, the operations selected ar
6. Press and quickly while the procedure is being carried out. When nished, the result is signalled by the status of the following LEDs:
- yllufsseccus detelpmoc = ylidaets no )1LD( DEL neerg
- red LED (DL2) on steadily = error
7. Turn power o to the 950N2 and remove the USB pen drive.
hold the SW1 button for at least 3 seconds to use the function. The green LED ashes more
e indicated in H .
J2
H eht gnitceleS upload/download function
Green LED DL1 Function
1 ash
2 ashes
3 ashes
4 ashes
950N2 rmware update le required: 950N2.hex
KP EVO rmware update, including menu translations les required: KP EVO.hex e KP EVO_L.bin
950N2 and timer conguration upload les required:
950N2, timer and LOG data conguration download les written: 950N2.prg , 950N2.tmr , 950N2.log
110
SW1
DL2
DL1
08
920.1003.02 | 18
WWW.TUCKERAUTO-MATION.COM
Page 54
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
TUP .4 TING INTO SERVICE
4.1 FINAL CHECKS
1. For doors in “low energy” mode, make sure that the forces generated by the leaf are within the limits permitted by the regulations. Use an impact force tester in accordance with standards EN 12453: 2002 and EN 12445: 2002. For non-EU countries, of there are no specic local regulations, the force must be less than 67 N.
2. For doors that are not in “low energy” mode, make sure that the test object is detected in all areas covered by the leaf movement.
4.2 FINAL OPERATIONS
1. Connect the cable of the functions selector at the side of the unit to the I/O board (connector J2).
2. Install the front cover.
3. Highlight all areas with adequate warning signs in which there are still residual risks, even if all possible safety measures having been adopted. In particular, for doors less than 2 meters high, apply the hazard warning pictograms in correspondenc
4. Place a “DANGER, AUTOMATICALLY CONTROLLED” sign in a prominent position on the door.
5. Attach the CE marking on the door.
6. Fill out the EC declaration of conformity and the system register.
7. Give the EC Declaration, the system register with the maintenance plan and the instructions for use of the automation to the system owner/operator.
e with the arm movement area.
INSTALLING A PLASTIC COVER
1. Install the cover xing plates with screws 09-1 on both sides.
2. Partially tighten the screws 09-2.
3. Insert the cover so that the screws t into the slots, then tighten them.
4. As an alternative to xing it from the side, use the template to fasten the cover with screws from the top or bottom (10
5. Press the top and bottom slot covers on (11 ).
1
2
09
10 11
920.1003.02 | 19
WWW.TUCKERAUTO-MATION.COM
Page 55
KP evo - TAP CONTROLLER
INSTALLING AN ALUMINIUM COVER
1. Install the side proles using the screws 12-1
on both sides.
2. Press the aluminium cover on, aligning the slot with the side on which the transmission arm has been installed.
5. MAINTENANCE
RISKS
PERSONAL PROTECTIVE EQUIPMENT
INSTALLATION GUIDE
1
1
12
5.1 INSERTING / REPLACING THE BATTERY
CARRY OUT THE FOLLOWING OPERATIONS WITH THE ELECTRICITY SUPPLY DISCONNECTED
1. Remove the cover.
2. Install or replace the CR1216 battery on the Logic
board, as shown in 13 .
3. Reinstall the cover.
Always shut o the power supply before performing any maintenance operations. If the disconnect switch is not in view, apply a warning sign stating “WARNING - Maintenance in Progress”. Restore the power supply only after nishing any maintenance work and restoring the area to normal.
Maintenance must be performed by the installer or a maintenance technician. Follow all safety recommendations and instructions given in this manual. Mark o the work site and prohibit access/transit. Do not leave the work site unattended. The work area must be kept tidy and cleared after maintenance has been completed. Before starting work, wait for any hot components to cool down. Do not make any modications to the original components. FAAC S.p.A. shall injury due to components that have been modied or otherwise tampered with.
bear no liability for damage
or
5.2 REPLACING THE FUSE
CARRY OUT THE FOLLOWING OPERATIONS WITH THE ELECTRICITY SUPPLY DISCONNECTED
There is a power supply protection fuse on the I/O board. To replace it:
1. Remove the cover:
2. Replace the following fuses
- F 4A for the 230 V version
- T 3.15A for the 115 V version
3. Reinstall the cover.
The warranty shall be forfeited in the event of
tampering with components. Only use original FAAC spare parts.
CR1216
WWW.TUCKERAUTO-MATION.COM
13
920.1003.02 | 20
Page 56
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
5.3 ROUTINE MAINTENANCE
elbaT I lists the operations which must be
performed on a regular basis in order to keep the au­tomation working reliably and safely; these are given purely as a guideline and should not be considered exhaustive. The installer/machine manufacturer is responsible for drawing up the maintenance plan for the automation, supplementing this list or modifying the maintenance operations on the basis of the ma­chine characteristics.
I ecnanetniam deludehcS
Operations Frequency/months Structures
Check the structures and the parts of the building to which the door and the automation is xed: make sure there is no damage, cracking, breaks or subsidence.
Frame
Check the frame: make sure that it is xed correctly, that it is integral and that there is no deformation or damage. Tighten screws and bolts where necessary.
Check the hinges: make sure that they are xed correctly, that they are integral, correctly positioned in their seats and that there is no deformation or damage.
Check the presence them.
Operator
Check that the cover/casing and all the movable guards are integral and that they are fastened correctly. Tighten screws and bolts where necessary.
Check the condition of the power cables, the sensor and accessory connection cables and the relative cable glands. 12 General cleaning. 12
Function set-up selector and keyboard
Sensors, protective devices and control devices
If applicable, check that the pictograms that identify the cont
The door
Check that the opening and closing speed is correct. For doors in “low energy” mode, make sure that the opening and closing times are within the limits permitted by the regulations.
For doors in “low energy”, mode, make sure that it is possible to stop the movement of the door without excessive force (Max. 67N) at any point along its travel.
Check that the safet open position when there is an obstacle in the area of movement etc.)
Check the presence, integrity and legibility of the EC marking on the door and the DANGER AUTOMATIC MOVEMENT warning sign. 12
and condition of pictograms that highlight the glass part of the door. If they are missing or damaged, replace
rol devices for disabled persons are present and intact. 12
atsni secived eht lla htiw snoitcerid htob ni ylreporp setarepo rood eht taht kcehC
setarepo rood eht taht kcehC
y system is working correctly (door reverses or stops when an obstacle is detected, that the door stops in the
12
12
21.egamad ro noitamrofed on si ereht taht dna largetni si ti taht :fael eht kcehC
12
21.yrassecen fi ,skcol ro segnih etacirbuL
21.rood eht fo tnemevom fo aera eht fo naelc yllareneG
12
12
21.yltcerroc gnitarepo dna tcatni era yeht taht kcehC
21.yltcerroc gnitarepo dna tcatni era yeht taht kcehC
21.dell 21 .sesion lausunu yna gnikam tuohtiw ylmrofinu dna ylhtooms sevom rood eht taht kcehC
6
6
21.edom gnitarepo yreve ni yltcerroc
6.tneserp fi ,ylreporp gnikrow si kcol eht taht kcehC
6
920.1003.02 | 21
WWW.TUCKERAUTO-MATION.COM
Page 57
KP evo - TAP CONTROLLER
6. INTERCOM
INSTALLATION GUIDE
■ DESCRIPTION
The 950N2 is capable of communicating with other 950N2 units via an Intercom network connec­tion. This enables the following modes of operation to be used (KP EVO menu 2.6.1):
- INTERMODE: a master door from which to set the
operating mode for all the other doors that are connected to the network.
- INTERLOCK: two single doors, where the opening
of one is subject to the closing of the other and vice versa.
- 2 LEAVES: access consisting of a double leaf.
- 2 LEAVES + INTERLOCK: two interlocked accesses,
each consisting of a double leaf.
Ever y network connected 950N2 should be pro­grammed for the same Intercom mode.
■ CONNECTION
The units in the network are connected via 3 cascade connected-wires between the J8 connectors of the
I/O boards (14).
The sequence in which the units are wired is unim­portant, but it is essential that a CASCADE connection is used.
The 2 DIP switches on the I/O board must be set as follows:
- On the rst and last units of the cascade connec-
tion: both ON.
- On intermediate units (if any): both OFF.
■ ADDRESSING
A unique ID (KP EVO menu 2.6.2) must be assigned to each 950N2 in the network as indicated below.
Do not assign the same ID to more than one unit in the network.
ON
1
■ REGISTRATION
After having wired up and assigned an address to each unit, registration (KP EVO menu 2.6.3), must only be carried out on the 950N2 that has been assigned ID1.
J8
DS2
2
J8
DS2
1
ON
J8
DS2
2
1
ON
CHGCHGCHG
CLCLCL
2
14
920.1003.02 | 22
WWW.TUCKERAUTO-MATION.COM
Page 58
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
6.1 INTERMODE
15 shows the ID to assign to the 950N2 units in the network. The system consists of a Master unit and a maximum of 14 Slave units. The 950N2 Master unit is the only one on which the operating mode should be set, which is then also applied immediately to all the Slave units.
With INTERMODE, it is not possible to change the
operating mode of an individual unit.
950N2 The Master must be assigned ID1 and the Slave units with ID from 2 to 14.
6.2 INTERLOCK
16 shows the ID to assign to the 950N2 units in the network. Either of the two units can be designated as the Master and the other as the Slave. In INTERLOCK mode, one door can open only if the other is closed. The available variations are shown below. If the PARTIAL mode is associated with INTERLOCK, only the Master leaf opens.
Connect the devices and carry out the programming
and Setup of the individual 950N2 units before conguring the INTERLOCK using KP EVO.
Select
INTERLOCK.
on the Master unit to activate the
950N2
MASTER
ID=1
950N2
SLAVE
ID=2
950N2
SLAVE
ID=3
950N2
SLAVE
ID=15
15
950N2
Master interlock
ID=1
950N2
Slave interlock
ID=3
16
920.1003.02 | 23
WWW.TUCKERAUTO-MATION.COM
Page 59
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
INTERLOCK WITH NO MEMORY
With 4 sensors: the second opening is not automatic. In order to open the door, the internal/external sensor must be sensor is activated while the door is not yet closed, it has no eect.
A1 closed A2 closed
A1 NOT closed A2 closed
A1 closed A2 NOT closed
INTERLOCK WITH MEMORY
With 2 sensors or buttons: the second opening is automatic.
triggered when the other door is closed. If the
EXTERNAL
OPENING
A1
INTERNAL
OPENING
INTERNAL
OPENING
S1 S2 S3 S4 A1 opens A1 opens A2 opens A2 opens
A1 opens A1 opens request
request opening A1
request opening A1
A2
S3S2
opening of A2
A2 opens A2 opens
EXTERNAL
OPENING
4S1S
request opening of A2
6.3 2 LEAVES
17 shows the ID to assign to the 950N2 units in the network. If the two doors overlap, the one that opens rst is designated as the Master. If there is no overlap, either of the two units can be designated as the Master and the other as the Slave. The movement of the leaves 2 is synchronised.
The internal / external door sensors and safety devices
must be connected to their own unit; all other devices are connected only to the Master. Connect the devices and carry out the programming and Setup of the individual 950N2 units before
activating the 2 LEAF function.
Only use the Master 950N2 to change the oper­ating mode.
The leaf opening / closing delay can be set in menu
2.5.5 of the KP EVO.
2A1A
17
950N2 2 leaves MASTER ID=1
S2
S1
S3
S4
950N2 2 leaves SLAVE ID=2
A1
S1 S2
EXTERNAL
OPENING
S1 S2
A1 closed A2 closed A1 opens, then A2A2 opens, then
A1 NOT closed, A2 closed A1 opens and
request opening of A2
A1 closed, A2 NOT closed request
opening of A1
A2
EXTERNAL
OPENING
A1 request
opening of A2
A2 opens and request opening of A1
6.4 2 LEAVES + INTERLOCK
18 shows the ID to assign to the 950N2 units in the network. This conguration integrates the 2 LEAVES function (on two double-leaf accesses) with the interlock function. Refer to the operating modes described above.
950N2
Master interlock
2 leaves MASTER ID=1
950N2 2 leaves SLAVE ID=2
950N2
Slave interlock
2 leaves MASTER ID=3
950N2 2 leaves SLAVE ID=4
18
920.1003.02 | 24
WWW.TUCKERAUTO-MATION.COM
Page 60
KP evo - TAP CONTROLLER
INSTALLATION GUIDE
Tucker Auto-Mation, LLC 11075 Parker Dr, Irwin, PA 15642
Toll Free: 1-855-8 TUCKER Tel: 412-823-2537 Fax: 412-842-0260 Email: sales@tuckerauto-mation.com
920.1003.02 | 25
WWW.TUCKERAUTO-MATION.COM
Loading...