T Therm Geo TST-***, TST-024, TST-036, TST-048, TST-060 Installation & Operating Instructions Manual

Two-Stage Split Geothermal Heat Pump
Installation & Operating Instructions
Model: (TST-***)
Application
Retrofit existing forced air installations Dual Heat – combine this geothermal unit and A-coil with standby
gas or oil furnace
LMC (Load management control), LMC/INT ready Tested to UL Standards 1995
Information
The air coil furnished with this product has been tested and certified with this unit. To maintain the specification performance and product
certification, the air coil shipped with this unit must be used.
This unit may not be tax credit eligible when a coil other than the furnished coil is used.
For optimum performance an ECM blower is recommended. The CFM airflow required in the specification table must be matched to the compressor stage by the installed furnace blower/air handler.
Since this product requires line sets and air coil installation, an experienced and licensed refrigeration technician is required.
Domestic Water Heater, Desuperheater
Energy Star promotes the desuperheater and it is offered as an optional item for all TTHERM GEO™ heat pumps. Our exclusive GEO Logic™ control system optimizes the operation of a desuperheater, operating the systems only when there is adequate energy available to provide heat to the domestic hot water. However, to maximize the times the desuperheater aides in providing domestic hot water, a hot water preheat tank is suggested, see Desuperheater section of this manual.
Note – The GEO Logic control board has various required setup adjustments, see Field Setup section.
DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A
SAFE PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
Important information
Model Number:____________________________ Serial Number:_____________________________ Installing Contractor:________________________
12/03/2012 GI301
Table of Contents
Introduction 1
Product Configurator (GC002) 3
Mechanical Specifications 4
Electrical Data 5
Product Dimensions 6
Installation Requirements 7
Mechanical Installation Overview 8
Mechanical Installation Source Water 11
Desuperheater, Domestic Hot Water 16
Duct System/A-Coil Installation 18
Installing the TXV 19
Mechanical Installation Refrigeration 22
Charging Procedure 23
Superheat and Sub-Cooling 24
Unit Operating Conditions Heat & Cool 25
R-410A Pressure/Temperature Conversion Chart 27
Electrical Hookup 28
GEO Logic Controller 29
Accessories/Options 30
Field Setup Overview 32
Duel Fuel/Utility Control 32
Operation Indicators 34
Power On, Start Up 38
Operational Tips 40
Troubleshooting 41
Preventative Maintenance 44
Drawing GH001 – TT-INT-1 Hookup 46
Drawing GR301 – Refrigerant Hookup 47
Drawing UAW555 – Electrical Diagram 49
Warranty Information – GX002 50
12/03/2012 GI301
Introduction
Geothermal heat pumps are able to heat and cool spaces with efficiencies exceeding 350% by taking advantage of solar heat stored in the earth’s crust and the earth’s relatively stable temperatures. In the winter time, heat is moved from the earth into the home and concentrated using a refrigeration system. Since the heat already exists in the soil, the cost of operation of the geothermal heat pump is, in effect transportation cost for the free heat. In the summer, heat is removed from the home by reversing the refrigeration process and sending heat back out into the earth. A geothermal system consists of an earth source (either open loop or earth loop heat exchanger), a geothermal heat pump containing the refrigeration system and a ductwork system for delivering the conditioned air to the individual rooms. To learn more about geothermal heating, please visit our web site at www.tthermgeo.com
This is a pre-wired package for converting a new or existing oil or gas furnace into a dual heat system. This is a complete package for both heating and air conditioning, utility load control, and compatible with DC drive variable speed furnaces. The GEO Logic control uses a standard, multi-wire heat pump room thermostat to initiate and terminate all heat/cool functions. There are various temperature sensors, pressure sensors, water flow switch, etc. which continuously monitor the heat pump system. The interaction of these sensing components, room thermostat requests, and the various heat pump refrigeration components are all controlled by an integrated microprocessor system (GEO Logic). The various setup conditions for this microprocessor based controller determine the application and geo product series. These setups are initially programmed by the factory, but special PC software and cable are available for reprogramming as required for controller replacement and/or other options which may apply to the specific installation. See Additional Equipment Concerns, Field Setup or Programming, Operation Indicators, User Instructions, Control Sequence, and Troubleshooting sections within this manual for further details on the GEO Logic control.
The utility load control receiver interfaces with the T2-TT-INT-1 which properly switches the heating mode and properly controls the air conditioning mode during summer load interrupt. The blower circuit and control is also designed for heating interrupt (blower handled by gas furnace only) and continuous operating blower during cooling peak load interrupt. Typically these controls and design features are only found in this product.
Moving and Storage
Units should be stored in original packaging in a clean dry area. Store and move units in normal upright position. Do not stack units. Transport in vertical position only.
Initial Inspection
Be certain to inspect all cartons and crates as units are received before signing the freight bill. Verify that all items received have no physical damage. Report any damages or shortages on the freight bill. The purchaser is responsible for filing the necessary claims with the carrier. Concealed or hidden damages not discovered until removing packaging must be reported to the carrier within 15 days of receipt.
Unit Location and Mounting
Locate the unit in an indoor area where the ambient temperature will remain above 45°F [8°C]. TTHERM GEO Heat Pump provides 4 removable panels for ease of servicing.. This unit is zero clearance rated; however, allow enough room to remove panels for service and maintenance. Suggest setting unit on a sound vibration pad, see accessories price sheet, part # E2-0122. Water supply should not be hard plumbed directly with copper or PVC pipe as this could transfer any vibration to living space. Consider using Hose Kit part # L3-0015B to minimize transferred vibration.
Please read and understand conditions associated with proper installation, unauthorized changes, and POWER ON procedures.
Warranty Statement
See the last page of this manual for detailed limited warranty coverage explanation.
12/03/2012 1 GI301
WARNING
BEFORE PERFORMING SERVICE OR MAINTENANCE OPERATIONS ON A SYSTEM, TURN OFF MAIN POWER SWITCHES TO THE INDOOR UNIT. IF APPLICABLE, TURN OFF THE ACCESSORY HEATER POWER SWITCH. ELECTRICAL SHOCK COULD CAUSE PERSONAL INJURY.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply, such as the following safety measures:
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations. Have a fire extinguisher available for all brazing operations.
Warnings, Cautions, and Notes
Throughout this manual there are warnings, cautions and notes containing various levels of important information. Read all of these items carefully before performing any installation, servicing or troubleshooting of the system.
Warnings are for any item which MUST be followed and failure to do so could result in serious injury or even
death and/or serious damage to the equipment.
Cautions relate to potentially hazardous situations or important practices which if ignored could cause minor to moderate injury or cause equipment damage or performance problems.
Notes are used to indicate items of high importance but are not related to a hazardous situation.
Safety Considerations
12/03/2012 2 GI301
T V T - 0 4 8 - 1 C L D X 1 - X X
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TTHERM GEO (1)
Unit Style (2)
C = Combo
H = Hydronic
S = Split
V = Vertical
Unit Type (3)
A = Single Stage
T = Two Stage
Nominal Tonnage (4, 5, 6)
Voltage Option (7)
Heat Exchanger Option (8)
M = Copper (Load) & Cupronickel
S = Stainless (THT only)
024 = 2-ton 036 = 3-ton
042 = 3.5-ton
048 = 4-ton 060 = 5-ton 072 = 6-ton
096 = 8-ton 120 = 10-ton 144 = 12-ton
1 = 208/230V, 1 Ph 2 = 208/230V, 3 Ph 3 = 460/480V, 3 Ph
C = Copper
N = Cupronickel
(Source)
TTHERM GEO Heat Pump Configurator
Model Number Digits
TVT-048-1CLDX1-XX
Auxiliary kW Option* (13, 14)
05 = 4.8 kW 10 = 9.6 kW 15 = 14.4 kW 20 = 19.2 kW XX = None
*Can be factory or field installed
Vintage (12)
1
Miscellaneous Kits (11)
A = Soft Start Kit (Installed) X = None
Desuperheater Option (10)
D = Desuperheater w/Factory
Installed Pump
X = None
Configuration Option (9)
L = Left Return (Standard)* R = Right Return C = Split Air Coil X = N/A or No Split Air Coil
*Left return can be field converted to right return
10/12/2012 GC002
Mechanical Specifications – R410A Two-Stage Compressor
MODEL
TST-024
(2 ton) Coax & Piping Water Volume gal .43 .65 1.1 1.1 Source Temperature °F (min/max) 20°/120° 20°/120° 20°/120° 20°/120° Nominal source differential* ° F (H/C) 3/12° 9/11° 6/11° 6/10° Factory Charge R410A 3 lbs. 10 oz. 6 lbs. 1 oz. 7 lbs. 2 oz. 7 lbs. 2 oz. Static Pressure – Nominal 0.3 0.3 0.3 0.3 Static Pressure – Design 0.5 0.5 0.5 0.5 Weight– Base Unit Only (lbs) 240 275 320 320
Model GPM PSID Model GPM PSID Model GPM PSID Model GPM PSID
4 1.2 6 1.8 8 1.3 10 1.9
2-ton
6 2.7 9 2.4 12 2.5 15 3.6 8 3.6 12 4.3 16 4.0 20 5.8
10 5.6
HEAT EXCHANGER PRESSURE DROP TABLE
Water-to-Air (Source Side, Pure Water @ 68° F)
3-ton
15 6.7
PRESSURE DROP MULTIPLIERS
Freeze Point (° F) 20° F 25° F 30° F 35° F 40° F
Pure Water Multiplier 32 1.00 1.00 1.00 1.00 1.00 Methanol 12.5%* Multiplier 16.2 1.25 1.21 1.18 1.15 Propylene Glycol 20%* Multiplier 18.4 1.39 1.35 1.31 1.28 1.24 Ethanol 20%* Multiplier 18.1 1.56 1.47 1.42 1.36 1.31
1. Capacities are based on temperatures shown in heading, source is left group, return air is right group.
2. Stated Btu/h is the ISO 13256-1 formula adjusted, actual HP supply energy delivered is 2% greater.
3. Temp rise is based on sensible only.
4. All ratings based upon operation at lower voltage of dual voltage rated models.
5. Ground Loop Heat Pump ratings based on 15% antifreeze solution.
*By volume Feet of Head = PSI x 2.31
HEATING – ISO 13256-1 SPECIFICATION – ENERGY STAR
Model Stage
TST-024
TST-036
TST-048
TST-060
FL 8 32.9 850 32 4.05 24.8 850 26 3.56 PL 8 21.8 725 29 21.6 18.5 725 26 3.89 FL 10 42.3 1200 31.8 4.01 33.0 1200 26.5 3.62 PL 10 30.1 1000 27.4 4.35 26.9 1000 24.0 3.90 FL 12 56.0 1500 37 4.02 47.7 1500 29 3.57 PL 12 38.5 1200 31 4.33 37.7 1200 29 3.98 FL 15 70.7 1875 36 4.10 55.7 1875 28 3.59 PL 15 51.9 1480 32 4.22 46.3 1480 30 3.86
Source
GPM
COOLING – ISO 13256-1 SPECIFICATION – ENERGY STAR
Model Stage
TST-024
TST-036
TST-048
TST-060
FL 8 32.8 950 22 19.4 30.6 950 20 16.3 PL 8 23.3 825 21 23.8 22.5 825 22 20.9 FL 10 45.1 1250 20.7 19.7 44.1 1250 19.4 15.8 PL 10 32.2 1050 19.4 22.5 30.5 1050 18.2 18.9 FL 12 63.8 1600 22 19.7 57.4 1600 23 15.4 PL 12 46.9 1275 24 23.5 45.1 1275 23 20.8 FL 15 70.2 2000 23 19.2 63.3 2000 23 14.7 PL 15 50.4 1650 21 23.0 51.3 1650 22 19.7
Source
GPM
GWHP – Ground Water GLHP – Ground Loop 50° F 68° F 32° F/41° F 68° F
Capacity
Btu/h
Blower
CFM
GWHP – Ground Water GLHP – Ground Loop 59° F 80.6° F 77° F/68° F 80.6° F
Capacity
Btu/h
Blower
CFM
4-ton
Temp
Rise
Temp
Drop
TST-036
(3 ton)
20 5.8
COP
EER
Capacity
Btu/h
Capacity
Btu/h
TST-048
(4 ton)
5-ton
Blower
CFM
Blower
CFM
TST-060
(5 ton)
25 8.5
Temp
Rise
Temp
Drop
COP
EER
12/03/2012 4 GI301
Electrical Data – Single Phase
Desup.
Pump
Model
Voltage Compressor
(60 Hz) RLA LRA FLA FLA FLA Ampac.
TST-024 208/230-1 13.1 73.0 .15 4.4 17.7 20.9 40 TST-036 208/230-1 17.9 96 .15 4.4 22.5 26.9 50 TST-048 208/230-1 27.1 152.9 .15 4.4 31.6 38.2 60 TST-060 208/230-1 29.7 179.2 .15 4.4 34.3 41.7 70
Loop
Pump
(Ext)
Total Min.
Max. Fuse/
HACR
Electrical Data – Three-Phase
Desup.
Pump
Model
Voltage Compressor
(60 Hz) RLA LRA FLA FLA FLA Ampac.
TST-024 Not Available
TST-036 200/230-3 14.2 88 .15 4.4 18.6 22.1 30 TST-048 200/230-3 16.5 110.0 .15 4.4 20.9 25.0 40
TST-060 Not Available
Loop
Pump
(Ext)
Total Min.
Max. Fuse/
HACR
TST Blower CFM Requirements
Model
G Y *Y2
Heat / Cool Heat / Cool TST-024 Furnace Default 725 / 825 850 / 950 TST-036 Furnace Default 1000 / 1050 1200 / 1250 TST-048 Furnace Default 1200 / 1275 1500 / 1600 TST-060 Furnace Default 1450 / 1650 1875 / 2000
* When the TST unit is installed with a single speed furnace blower, the blower needs to be capable of
delivering the CFM required by Y2
12/03/2012 5 GI301
Product Dimensions
Forced Air Coil – Reference Information
12/03/2012 6 GI301
Installation Requirements
1. All installation work must be performed by trained, qualified contractors or technicians. TTHERM GEO
Heat Pump, sponsors installation and service schools to assist the installer. Contact TTHERM GEO at
sales@tthermgeo.com
WARNING
ALL ELECTRICAL WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND LOCAL ELECTRIC CODES, ORDINANCES, AND REGULATIONS.
WARNING
OBSERVE ELECTRIC POLARITY AND WIRING COLORS. FAILURE TO OBSERVE COULD CAUSE ELECTRIC SHOCK AND/OR DAMAGE TO THE EQUIPMENT.
CAUTION
This unit can only be used for its intended design as described in this manual. Any internal wiring changes, modifications to the circuit board, modifications or bypass of any controls, or installation practices not according to the details of this manual will void the product warranty, the safety certification label, and manufacturer product liability. TTHERM GEO, cannot be held responsible for field modifications, incorrect installations, and conditions which may bypass or compromise the built-in safety features and controls.
2. If this is a Dual Heat system, this product relates only to the addition to the furnace ducting system external
to the gas or oil force air furnace. The owner/installer assumes all responsibility and/or liability associated with any needed installation of the gas/oil furnace, fuel system, flue, chimney, etc. Any instructions or comments made within this manual (or factory phone assistance) relating to the gas/oil furnace are provided as comments of assistance and “helps” only.
for upcoming dealer training events.
CAUTION
This unit shall not be operated (either heating section or blower) until the interior of the structure is completed and cleaned. This also means all duct work must be complete with filter, etc. Manufacturer’s warranty is void if this unit is operated during structure construction.
CAUTION
Hazards or unsafe practices could result in property damage, product damage, severe personal injury and/or death.
3. All removed or discharged refrigerant must be recovered. Local and federal statutes are to be observed.
Should a compressor need replacing, the compressor oil is to remain with the compressor. Refrigerant lines on the compressor must be sealed.
4. Remember, safety is the installer’s responsibility and the installer must know this product well enough to
instruct the end user on its safe use.
At TTHERM GEO, the safety of the installer and the end user is of highest priority. Remember, safety is the installer’s responsibility and the installer must know this product well enough to instruct the end user on its safe use. Professional installers should be trained and experienced in the areas of handling electrical components, sheet metal products, and material handling processes.
12/03/2012 7 GI301
Mechanical Installation Overview
This TTHERM GEO series unit cannot correct airflow problems inherent within the duct work system. The following items should be carefully considered and properly followed for all installations:
Examination of the existing forced air furnace – Prior to starting this installation or furnace modification,
examine the total furnace system and make necessary comments or recommendations to the homeowner. Remember, if a marginal condition exists within the existing forced air system, the installation of a geothermal heat pump will not cure PRE-EXISTING conditions. Consider such items as proper fossil fuel ignition, is the furnace cycling on hi-limit, filter, adequate cold air return, adequate supply duct and room register. Inspect and count supply and return registers for size and number.
Heating capacity – Size the geothermal heat pump according to the normal heating requirements as the building
exists today geothermal heat pump should be sized to the heat loss of the house. Heat loss and heat gain audits should be done to determine proper equipment sizing.
Supply plenum – Carefully examine all sides of the plenum. Installing the coil in the supply plenum of a fossil
fuel furnace is the preferred location. If the coil is installed in the return ductwork, the cool air during cooling could be detrimental to the life of the furnace. Either location would be fine in the case of a fan coil. Verify all transitions have angles less than 30, the coil is centered within the plenum/ductwork, and there are no odd shaped angles or odd shaped transitions within the plenum/ductwork.
Other plenum equipment – Auxiliary equipment such as humidifiers, zone plenum dampers, etc., located
within the plenum which may cause a non-uniform airflow issues may have to be removed if they cause to great reduction to system airflow.
Insufficient cold air return capacity – Installation experience indicates this is a major concern. In fact, it
could represent a problem in as many as 60% of the installations, especially if there is a requirement to increase airflow with the existing blower and the existing cold air return capacity is already undersized or restricted. Check the static pressure within the return cabinet or the suction at the filter cabinet door. Do not assume because there is a register on the wall, the hole behind the register or the passageways are equal to this register. Sharp offsets and transitions in the cold air return system often cause severe restrictions. Expect to add additional registers or a relief register in the main cold air return duct. Best practice would include both high and low return registers.
Blower CFM capacity – The furnace forced air system must have an airflow capacity larger than the minimum requirement on the TTHERM GEO Series specification sheet (see unit nameplate and/or Mechanical Specifications). It is near impossible to correctly measure CFM airflow in an existing residential installation.
Experience and rule of thumb indicators will have to be followed to determine the existing furnace CFM capacity. The following may be helpful:
. Do not necessarily match to the existing furnace nameplate because it may be oversized. The
Comment – zone dampers cause back pressure on the blower and overall reduced airflow. Reduced airflow can cause the geothermal unit to perform poorly or in some cases cause icing or freeze ups in the air coil. If the smallest zone cannot handle the minimum CFM requirements of the heat pump, create a dump zone and/or allow air flow to bypass to other zones.
a. Existing furnace nameplate
the systems static pressure. What changes have been made to the heating system since installation?
b. Blower motor size
- Used only as a minimal guide.
2 ton unit - 1/3 HP or larger 3 ton unit - 1/2 HP or larger 4 ton unit - 3/4 HP or larger 5 ton unit - 1 HP or larger
c. Observe/examine airflow ducting system and design
- Typically represents a high or optimistic rating and is a function of
- Use duct sizing table , or industry
12/03/2012 8 GI301
equivalent duct capacity airflow charts and determine if the system is capable of delivering the CFM required on the nameplate. Especially check the number of registers and the number of “6 inch rounds”. The same would apply to cold air return duct capacity.
d. Calculated CFM
- By measuring the temperature rise across the existing furnace, the CFM can be approximated. The accuracy of this formula will depend upon the estimated or determined Btu output (actual heat energy across the furnace, not nameplate input).
CFM =
Btuh (output)
Temperature Rise x 1.08
Duct Sizing Chart Acceptable Branch Duct Sizes Acceptable Main or Trunk Duct Sizes CFM ROUND Rectangular Round Rectangular
100 6” 4x8, 4x6 150 7” 4x10, 5x8, 6x6 200 8” 5x10, 6/8,4x14,7x7 250 9” 6x10, 8x8, 4x16 300 10” 6x14, 8x10, 7x12 350 10” 6x20, 6x16. 9x10 400 12” 6x18, 10x10, 9x12 10” 4x20, 7x10, 6x12, 8x9 450 12” 6x20, 8x14, 9x12, 10x11 10” 5x20, 6x16, 9x10, 8x12 500 10” 10x10,6x8, 8x12, 7x14 600 12” 6x10, 7x18, 8x16, 10x12 800 12” 8x18, 9x15, 10x14, 12x12 1000 14” 10x18, 12x14, 8x24 1200 16” 10x20, 12x18, 14x15 1400 16” 10x25, 12x20, 14x18, 15x16 1600 18” 10x30, 15x18, 14x20 1800 20” 10x35, 15,20, 16x19, 12x30, 14x25 2000 20” 10x40, 12x30, 15x25, 18x20 2200 22” 10x40, 15x25, 20x20 2400 22” 12x40, 16x25, 20x20
12/03/2012 9 GI301
Closed Loop Applications – Closed loop system re-circulates the same water/antifreeze solution through a
closed system of underground high-density polyethylene pipe. As the solution passes through the pipe it collects heat (in the heating mode) that is being transferred from the relatively warm surrounding soil through the pipe and into the relatively cold solution. The solution is circulated back to the heat pump that extracts its heat and then returns to the ground to absorb more heat from the earth. Earth loops must be sized properly for each particular geographic area and individual capacity requirements.
The TTHERM GEO Series heat pumps are designed to operate
on either vertical or horizontal closed loop applications.
(Figures 1 & 2) Vertical loops are typically installed with a well drilling rig up to 200 feet (61 meters) deep or more. Horizontal systems are typically installed with excavating or trenching equipment approximately six to eight feet (1.8 – 2.4 meters) deep, depending on geographic location and length of pipe used. Horizontal bored loops are typically installed 15 feet deep.
Figure 1 – Horizontal Closed Loop
Lake or Pond Loops – Closed loop systems may also be used
in lakes or rivers to supply a heat source to the heat pump. Typically a loop consisting of geothermal pipe can be designed and placed in an area not much deeper than 12ft (3.7 meters) deep with some water currents present. In any lake or pond, municipal and area codes must be observed in regards to a lake or pond loop. The use of an environmentally friendly loop fluid like Propylene Glycol should be considered should damage ever occur to the loop. Consult an IGSHPA or CGC certified installer for proper lake loop design and installation. State and local codes apply.
Figure 2 – Vertical Closed Loop
12/03/2012 10 GI301
Mechanical Installation Source Water
WARNING
LOOP DESIGN IS EXTREMELY IMPORTANT FOR PROPER HEAT PUMP OPERATION. INCORRECT LOOP DESIGN WILL REDUCE HEAT PUMP EFFICIENCY, CAUSE POOR PERFORMANCE OR MAY RENDER THE SYSTEM UNUSABLE. IF YOU LACK EXPERIENCE DESIGNING LOOP FIELDS, CONTACT AN IGSHPA OR CGC CERTIFIED GEOTHERMAL LOOP CONTRACTOR FOR PROPER INSTALLATIONS.
Water Connections General – The following pages outline typical piping arrangements for the most common
source water connection options, as well as flushing and filling procedures and antifreeze requirements for closed loop systems. TTHERM GEO recommends hose kits for the source water connection points at the heat pump. This will provide a flexible connection to reduce and isolate vibrations transmitting from the compressor into other parts of the system. Hose kits also provide P/T ports for monitoring pressure and temperature (see below).
Note
TTHERM GEO heat pumps are factory set for open loop. J11 must be removed for proper operation on an antifreeze protected closed loop. See figure on page 30 for the location of J11.
Once closed loops are completed, they must be pressure tested to at least 60 PSI to insure integrity. Once pressure is tested, the loop must be purged of all foreign debris and filled with fluid. All air must be removed at this time by flushing the system. (Table 2) shows approximate fluid volumes.
Pressure/Temperature (P/T) plugs – Should be installed in the adaptor elbow on the entering and
leaving water line of the heat pump on a closed system. (Figure 3) A thermometer can be inserted into the P/T ports to check entering and leaving water temperatures. A pressure gauge can also be inserted into these P/T ports to determine the pressure differential between the entering and leaving water. This pressure differential can then be compared to the engineering specifications data to determine the flow rate of the system.
A Flow Meter is an important part of the system. It provides a visual indicator of loop flow in GPM. A flow
meter can be installed on either side of the pump pack, but must be installed per manufacturer recommendations so it reads accurately.
Non Pressurized Loops require an air separator/stand pipe to eliminate air and to hold enough fluid to
compensate for the expansion and contraction of the loop pipe and fluid. Purge and fill valves should be placed between the loop manifold valves and the insulated pump pack.
Pressurized Loops do not require an air separator. They require purge and fill ports between the loop manifold
valves and the insulated pump pack. After purging a pressurized loop, it should maintain 45 to 60 psi static pressure. The Geothermal Loop Pipe stretches under pressure so may need to be pressurized above the desired pressure several times to achieve the recommended static pressure. Pressurized loops must maintain enough static pressure to compensate for the expansion and contraction of the loop pipe and fluid.
Loop Pump Selection – Select a loop circulation pump based upon the GPM required and total system pressure
drop. See specification, page 4. Geo heat pump Btu/h capacity and efficiency are directly related to the GPM
flow though the unit. Vibration pad – suggest setting the unit on a sound vibration pad, available from most distributors or
accessories price sheet – E2-0122.
Water quality – models with standard copper heat exchanger coils require the installer to evaluate water quality
and meet minimum water properties.
pH < 7.5 Calcium hardness < 100 PPM Iron fouling < 0.2 PPM (Ferrous)
< 0.5 PPM of oxygen
Hydrogen sulfide (H Chloride levels < 20 PPM Erosion/clogging 10 PPM, particles Filter, if required 800 micron size Softened water is recommended along with 2 oz of common house chlorine bleach for every 10 gallons of water.
S) < 0.5 PPM
2
P/T Adapter
Figure 3
12/03/2012 11 GI301
Figure 4 – Non-Pressurized Closed Loop with Flow Center – Typical piping arrangement.
Figure 5 – Pressurized Closed Loop with Flow Center – Typical piping diagram.
12/03/2012 12 GI301
Antifreeze
When considering the earth loop solution, water quality is very important. TTHERM GEO recommends a minimum of soft water (not well water) treated with 2 oz. of household chlorine bleach for each 10 gallons of total volume. TTHERM GEO’s recommended antifreeze concentration is 22% which will yield a freeze protection of 18° F. This concentration of glycol requires additional additives to protect the system. TTHERM GEO recommends Enviro-Guard HD propylene glycol for this reason.
Over antifreeze protecting a loop field decreases pumping capacity when the loop gets cold and reduces thermal transfer. Under protecting a loop field will cause the THERM GEO heat pump to take action protecting itself from damage. This action will result in a loss of geothermal capacity, and AUX heat may be required to maintain the temperature in the home.
Table 2 – Approximate Fluid Volume (gal) per 100ft
Pipe Size Volume Pipe Size Volume
Polyethylene
¾” IPS SDR 11 3.02 1” 4.1 1” IPS SDR 11 4.73 1-1/4” IPS SDR 11 7.55 1” 4.5 1-1/2” IPS SDR 11 9.93 1.25” 6.8 2” IPS SDR 11 15.36
Rubber Hose
Copper
Type M
1.25” 6.4
1.5” 9.5
WARNING
PREVENTING FREEZE-UP IS INSTALLER/USER RESPONSIBILITY. DAMAGE CAUSED BY
FREEZE-UP IS NOT COVERED BY WARRANTY.
CAUTION
Softened water is recommended along with 2 oz. of common household chlorine bleach for every 10 gallons of water.
WARNING
NOT ALL GLYCOLS PROVIDE THE SAME LEVEL OF CONCENTRATION. MOST GLYCOLS
DO NOT CONTAIN ENOUGH INHIBITORS FOR THE RECOMMENDED CONCENTRATION
LEVELS.FOR GEOTHERMAL SYSTEMS.
Open Loop – An open system gets its name from the open discharge of water after it has been used by the heat
pump. A well must be available that can supply all of the water requirements of the heat pump along with any other water requirements drawing off that same well. The well must be capable of supplying the heat pump’s required flow rated for up to 24 hours per day for the coldest winter day.
Figure 6 shows the necessary components for water piping of an open system. First a bladder type pressure tank with a “draw down” of at least 1-1/2 to 2 times the well pump capacity must be installed on the supply side of the heat pump to prevent short cycling the well pump. Constant pressure well pumps need to deliver the GPM flow rate of the TTHERM GEO heat pump and other possible consecutive demands. Shut off valves and boiler drains on the entering and leaving water lines are necessary for future maintenance. A screen strainer is placed on the supply line with a mesh size of 40 to 60 and enough surface area to allow for particle buildup between cleanings. Hose kits are installed between the heat pump and ridged plumbing to reduce vibration transfer. Hose kits have pressure temperature (P/T) plugs placed in the supply and discharge hydrant elbows so that thermometers or pressure gauges can be inserted into the water stream. On the well water discharge side of the
12/03/2012 13 GI301
heat pump a flow meter is installed to provide a visual indicator of open loop flow in GPM. The water solenoid valve must be installed to control water flow through the unit. After the water solenoid a flow control valve is installed to limit maximum flow through the heat pump. The ball valve installed in the leaving water line can be used to create a small amount of back pressure to quiet the flow control valve if needed. Discharge water temperature should not drop below 39° at any time during the units operation. Remove handle on the entering and leaving water ball valves to prevent accidental change of flow.
The solenoid valve is then wired to two leads (brown/yellow and gray) provided. This valve will open when the unit is running and close when the unit stops. The visual flow meter will allow visual inspection of the flow requirements, and can be useful in determining when maintenance is required. Schedule 40 PVC piping, copper tubing, polyethylene or rubber hose can be used for supply and discharge water lines. Make sure line sizes are large enough to supply the required flow with a reasonable pressure drop (generally 1.00” diameter). Water discharge is generally made to a drain field, stream, pond, surface discharge, tile line, or storm sewer.
Solenoid Valve Wiring (for Open Loop Systems)
Inside the cabinet, tie-wrapped to the OUT water pipe, are two leads (brn/yel and gray) for direct connection to a 24VAC solenoid.
CAUTION
Using a drain field requires soil conditions and adequate sizing to assure rapid percolation or the required flow rates will not be achieved. Consult local codes and ordinances to assure compliance. Do not discharge water to a septic system. The heat pump should never be operated with flow rates (GPM) less than specified. Discharge water should never be lower than 39° F. Operation of the unit with less than required flow rate or no flow may result in freezing water in the water to refrigerant heat exchanger. This will cause the unit to shut down on low-pressure lockout. If the unit locks out low pressure, verify that the unit has the required flow and reset the unit by shutting off power to the unit for one minute. Do not continually reset the unit; if the unit locks out more than once call your service professional. Continued reset of the unit can freeze water inside the water coil to the point of rupturing the water coil
(no warranty for frozen coils).
12/03/2012 14 GI301
Loading...
+ 37 hidden pages