TTHERM GEO THA-036, THA-048, THA-072, THA-060, THT-096 Installation Instructions Manual

...
Installer
Water to Water Geothermal Heat Pump
3-Phase Models – Both 208 & 480
Installation Instructions
Model: THA-***-2 (208, 3-Phase) THT-***-2 (208, 3-Phase) THA-***-3 (480, 3-Phase) THT-***-3 (480, 3-Phase)
This manual provides the changes in electrical installation and is an addition to the standard GI101 Installation & Operating Instructions.
This additional document only replaces GI101
pages 5, 26 and 45.
All general information, mechanical details
and installation, general operating and troubleshooting, etc. is the same for all models.
DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A
SAFE PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
Important information
Model Number:____________________________ Serial Number:_____________________________ Installing Contractor:________________________
10/12/2012 GI102
THA-*** – Electrical Data – Three-Phase, 208
Model
Voltage Compressor
(60 Hz) RLA LRA FLA FLA FLA FLA Ampac-
Load
Pump
Desup.
Pump
Source
Pump
Total Min.
Max. Fuse/
HACR
THA-036 200/230-3 13.5 88 1.8 .15 4.4 19.9 23.2 30 THA-048 200/230-3 17.6 123 1.8 .15 4.4 24.0 28.4 40 THA-060 200/230-3 20.5 155 1.8 .15 4.4 26.9 32.0 50 THA-072 200/230-3 23.2 164 1.8 .15 4.4 29.6 35.4 50
THT-*** – Electrical Data – Three-Phase, 208
Model
Voltage Compressor
(60 Hz) RLA LRA FLA FLA FLA FLA Ampac.
Load
Pump
Desup.
Pump
Source
Pump
Total Min.
Max. Fuse/
HACR
THT-096 200/230-3 17.6 x 2 123 x 2 1.8 .15 4.4 24.0 x 2 28.4 x 2 40 x 2 THT-120 200/230-3 20.5 x 2 155 x 2 1.8 .15 4.4 26.9 x 2 32.0 x 2 50 x 2 THT-144 200/230-3 23.2 x 2 164 x 2 1.8 .15 4.4 29.6 x 2 35.4 x 2 50 x 2
THA-*** – Electrical Data – Three-Phase, 480
Model
Voltage Compressor
(60 Hz) RLA LRA FLA FLA FLA FLA Ampac.
Load
Pump
Desup.
Pump
Source
Pump
Total Min.
Max. Fuse/
HACR
THA-036 THA-048 THA-060 THA-072
THT-*** – Electrical Data – Three-Phase, 480
Load
Pump
Model
Voltage Compressor
(60 Hz) RLA LRA FLA FLA FLA FLA Ampac.
THT-096 THT-120 THT-144 460/480 15 x 2 75 x 2 20 x 2
Notes:
1. Dual compressor models contain dual power circuits for the compressors, amperages shown are for each
circuit.
2. All 3-phase models have 120V service source for internal control transformer and outputs for pumps.
Thus the only current/power from the 3-phase source is the compressor.
Desup.
Pump
Source
Pump
Total Min.
Max. Fuse/
HACR
10/12/2012 1 GI102
Loading...
+ 3 hidden pages