TSURUGA ELECTRIC NRP-60 Instruction Manual

Instruction Manual
Meter Relay Model NRP-60
I-01899-1/2
We thank you for your purchase of our model NRP-60 series meter relay. For safety use of this product, please observe the following caution. For proper operation of it, please also read the instructions to follow before the initial operation.
CAUTION
To prevent electric shock, observe the following cautions:
Never make power line connections with active lines.
Ensure firm and tight connections to the terminals.
Do not touch the power source terminals while the
instrument is powered on.
Check at Delivery When the product is delivered to you, please check that its specifications conform to your requirement and that there is no damage in transit. This instrument is carefully inspected before delivery from factory under our strict quality control program, but if you find any defect or inconvenience, please inform us of the model name and serial number of the product, etc.
Cautions for Use
① This product is a precision instrument, so please take utmost care for transportation, installation or any other handling of it. ② No power on-off switch is provided on this product, so it immediately starts to operate when connected to the power source. ③ In case of fear that the external noise of surge may cause malfunction or breakdown of this instrument, it is necessary to take proper protective solution against noise. ④ In case of fear that this instrument suffers the surge voltage, ground one side of the measuring input terminals. ⑤ Use this product within the range or conditions conforming to its specifications and standard.
Name of Parts
Low limit setting index High limit setting index
Low limit setting knob
Measuring
pointer
High limit setting knob
Zero adjuster
Note: In case that the model name is NRP-60H, no low limit setting lever, set point
index bar ,low limit display or contact output terminal is provided.
Panel Cut-Out Dimensions
24 24
4-φ4
To avoid electric shock, failure or abnormal heat-up of the instrument, do not use the instruments in such places where:
exposed to rain, water drops or direct sunlight.
high temperature or humidity, much dust or corrosive gas.
affected by external noise, radio waves or static electricity.
where there is constant vibration shock.
Measuring
input terminal
Output terminal
high limit contact
Auxiliary supply terminals
[Note]
Output terminal
low limit contact
Installation
2424
Insert the instrument from the front of the panel to install. And fasten them with the mounting screw to the pane
Optimum fastening torque : 0.36~0.48N・m
TSURUGA ELECTRIC CORPORATION
Model NRP-60
I-01899- 2/2
Connections Measuring input terminals of the instrument and, the contact output and auxiliary supply terminals M3.
Measuring input terminal
S
O
M
U
R
C
E
Auxiliary supply terminals
Make firm and correct connections with crimp type terminal. Optimum torque of the terminal screws: 0.36~0.48Nm
Note : In case that the model name is NRP-60H, no contact output terminals for the low limit is provided.
Measuring Input Terminals
Output terminal high limit contact
H
I
W
G
O
H
L
a
c
b
b
c
a
Output terminal low limit contact
[Note]
Arrange a cabling of measuring input line and power source line as distant as possible from each other. Close and parallel wiring of these two lines may cause unstable reading of the instrument.
DC Volt Meter DC Current Meter Receiving Meter
Connect the measuring input with correct polarity. Use the particular accessory when it is designated.
(+) (-)
(+
(-)
)
Auxiliary supply Terminals
AC Volt Meter AC Current Meter
Connect the measuring input. Use the particular accessory when it is designated.
AC INPUT
C
A
PUT
IN
AC power source model DC power source model Connect the AC voltage to the respective terminals of Connect the DV24V to the auxiliary supply auxiliary supply terminals (SOURCE). terminals (SOURCE) with correct polarity. AC100V power source voltage: Terminals ± and 100/110V AC200V power source voltage: Terminals ± and 200/220V
S
O
U
R
C
E
± 100V(110V)±10% 200V(220V)±10%
S
O
U
R
C
E
DC24V±10%
High Limit (HIGH) and Low Limit (LOW) Contact Output Terminals
The contact capacity of high and low limit contact output is, with resistive load: AC250V, 125VA or DC30V, 60W Make the connections with the cable conforming to these capacities. In case that the relay controls with the capacity higher than these, provide the auxiliary relay externally.
Operation
Prior to the operation of instrument, check that the input rate, auxiliary supply voltage and connections are correct. Before starting the measurement, check if the measuring pointer is accurately at zero (which is the point when the DC4mA
or DC1V generated by a standard voltage/current generator is input to the input terminals, respectively when the rated input is DC4~20mA or DC1~5V). If there is a discrepancy at zero, adjust the pointer to indicate zero with the adjuster provided on the front of the instrument. Turning the high (or low) limit setting knob, set the setting index at a desired point where the relay acts.
The setting index stops at slightly beyond the scaled range. If the setting knob is forcedly turned more, it causes a breakage, so take care with it.
Note)
When the input impedance at the input rating DC1 ~ 5V with the specification of 7331 accessory having more than 1 MΩ is inserted the auxiliary power with opened condition of input terminal of 7331, the measuring pointer indicates more than the upper limit of the scale.
While the instrument is powered on and when the measuring pointer exceeds the setting index (set point), the relay is actuated and, a-c turns ON (close) and c-b turns OFF (open).
Contact Information
Name : Tsuruga Electric Corporation Address : 1-3-23 Minami-Sumiyoshi, Sumiyoshi-ku, Osaka-shi 558-0041 Japan
TSURUGA ELECTRIC CORPORATION
Instruction Manual
Meter Relay Model NRP-83
I-01972 1/3
We thank you for your purchase of our model NRP-83 series meter relay. For safety use of this product, please observe the following caution. For proper operation of it, please also read the instructions to follow before the initial operation.
CAUTION
To prevent electric shock, observe the following cautions:
Never make power line connections with active lines.
Ensure firm and tight connections to the terminals.
Do not touch the power source terminals while the
instrument is powered on.
Check at Delivery When the product is delivered to you, please check that its specifications conform to your requirement and that there is no damage in transit. This instrument is carefully inspected before delivery from factory under our strict quality control program, but if you find any defect or inconvenience, please inform us of the model name and serial number of the product, etc.
Cautions for Use
① This product is a precision instrument, so please take utmost care for transportation, installation or any other handling of it. ② No power on-off switch is provided on this product, so it immediately starts to operate when connected to the power source. ③ In case of fear that the external noise of surge may cause malfunction or breakdown of this instrument, it is necessary to take proper protective solution against noise. ④ In case of fear that this instrument suffers the surge voltage, ground one side of the measuring input terminals. ⑤ Use this product within the range or conditions conforming to its specifications and standard.
Name of Parts
Low limit setting index
Low limit LED display
High limit setting index
High limit LED display
Measuring pointer
Low limit setting knob
High limit setting knob
Zero adjuster
Note: In case that the model name is NRP-83H, no low limit setting lever, set point
index bar ,low limit display or contact output terminal is provided.
Panel Cut-Out Dimensions
34 34
4-φ4
To avoid electric shock, failure or abnormal heat-up of the instrument, do not use the instruments in such places where:
exposed to rain, water drops or direct sunlight.
high temperature or humidity, much dust or corrosive gas.
affected by external noise, radio waves or static electricity.
where there is constant vibration shock.
Measuring input terminal
Output terminal high limit contact
Auxiliary supply terminals
Variable resister for span adjustment
(option)
[Note]
Output terminal low limit contact
Installation
3434
Insert the instrument from the front of the panel to install. And fasten them with the mounting screw to the pane
Optimum fastening torque : 0.36~0.48N・m
TSURUGA ELECTRIC CORPORATION
Model NRP-83
I-01972 2/3
Connections
Measuring input terminals of the instrument and,
Measuring input terminal
the contact output and auxiliary supply terminals M3. Make firm and correct connections with crimp type terminal. Optimum torque of the terminal screws: 0.36~0.48Nm
S
O
U
M
Note : In case that the model name is NRP-83H, no contact output terminals for the low limit is provided.
Measuring Input Terminals
Output terminal high limit contact
H
I
G
H
a
c
b
Arrange a cabling of measuring input line and power source line as distant as possible from each other. Close and parallel wiring of these two lines may cause unstable reading of the instrument.
DC Volt Meter DC Current Meter Receiving Meter
Connect the measuring input with correct polarity. Use the particular accessory when it is designated.
(+) (-)
(+
(-)
)
Auxiliary supply Terminals
AC Volt Meter AC Current Meter
Connect the measuring input. Use the particular accessory when it is designated.
AC INPUT
AC power source model DC power source model Connect the AC voltage to the respective terminals of Connect the DV24V to the auxiliary supply auxiliary supply terminals (SOURCE). terminals (SOURCE) with correct polarity. AC100V power source voltage: Terminals ± and 100/110V AC200V power source voltage: Terminals ± and 200/220V
High Limit (HIGH) and Low Limit (LOW) Contact Output Terminals
S
O
U
R
C
E
± 100V(110V)±10% 200V(220V)±10%
S
O
UR
C
E
The contact capacity of high and low limit contact output is, with resistive load: AC250V, 3A or DC30V, 3A Make the connections with the cable conforming to these capacities. In case that the relay controls with the capacity higher than these, provide the auxiliary relay externally.
Auxiliary supply terminals
R
C
E
W
O
L
b
c
a
Output terminal low limit contact
C
T
U
A
P
N
I
DC24V±10%
[Note]