TSL MDU12-PMi User Manual

MAINS DISTRIBUTION UNIT
MDU12-PMi
Television Systems Limited.
Vanwall Road, Maidenhead, Berkshire, SL6 4UB
MDU12-PMi Manual 2 Issue 4
This Page is Blank
MDU12-PMi Manual 3 Issue 4
Contents
1.0 Installation.
2.0 Description
3.0 Introduction
4.0 Operation
4.1 The Home Screen
4.2 The Output Screen
4.3 The System Screen
4.4 The SNMP Screen
4.4.1 SNMP Alarms
4.4.2 Email Alerts
5.0 Initial Configuration
6.0 Pin-outs
7.0 Response Times
8.0 Temperature Indications
9.0 Specifications.
Appendix 1
MIB File information
MDU12-PMi Manual 4 Issue 4
This Page is Blank
MDU12-PMi Manual 5 Issue 4
SAFETY
1.0 Installation.
Unless otherwise stated TSL equipment may be installed at any angle or position within an operating temperature range of 5° ~ 30° C .
The RJ45 connector is for use only with an Ethernet 10/100 system. All TSL equipment conforms to the EC Low Voltage Directive:
EC Low Voltage Directive (73/23/EEC)(OJ L76 26.3.73)(LVD). Amendment: (93/68/EEC) (OJ L220 30.8.93).
CAUTION: Always disconnect equipment connected to a powered MDU before performing any maintenance. Potentially hazardous voltages are present even after the operation or removal of a fuse, unless the front panel circuit breaker is set to OFF.
Earthing/Grounding In all cases, the frame of the equipment must be earthed on installation. Connection to an earthed strip running the length of the frame is ideal. The earth pin on the mains inlet connector is connected to the metal frame of the equipment, to 0 volts on the internal DC PSU and to signal ground, unless otherwise stated. All metal panels are bonded together. Rack mounted equipment must be earthed (grounded).
Mounting Careful consideration of the equipment location and mounting in racks must be made. In particular, consideration must be given to the stability of free-standing racks by mounting heavy equipment low in the rack. The rear of the unit should be supported in the rack.
Power This equipment is designed for installation in any position in a rack. Consideration must be given to the supply circuit loading and switch on/fault surges that will affect overcurrent
protection trips and switches etc. Check that the fuse rating is correct for the local power (mains) supply. Replacement fuses must be of the
same rating and type for continued protection against fire risk. The equipment rating is shown on the rear panel. No power supply cord is provided with this equipment but the inlet connector is.
Do not switch on until all connections are made.
Ventilation Due consideration for cooling requirements must be given when mounting the equipment. The equipment contains an internal temperature sensor.
General If equipment is installed in a closed unit, consideration must be given to providing forced air cooling in order that the maximum recommended temperature is not exceeded.
MDU12-PMi Manual 6 Issue 4
WARRANTY, MAINTENANCE AND REPAIR
All TSL equipment is guaranteed for one year from the date of delivery to the customer’s premises. If the equipment is to be stored for a significant period, please contact TSL concerning a possible extended warranty period.
Failure during warranty
If any TSL product should fail or become faulty within the warranty period, first please check the PSU fuses. All maintenance work must be carried out by trained and competent personnel. If equipment has to be returned to TSL for repair or re-alignment, please observe the following overleaf:
Technical support information
E-Mail address: support@televisionsystems.ltd.uk Telephone Support Number for the UK and Europe: +44 (0) 1628 670000 Telephone Support Number for the USA only: 1 877 591 2108
MDU12-PMi Manual 7 Issue 4
TSL Returns Procedure Please telephone +44 (0)1628 676200 (Fax: +44 (0)1682 676299) and ask for Sales who will provide a
Returns Number. This will enable us to track the unit effectively and will provide some information prior to the unit arriving.
For each item, this unique Returns Number must be included with the Fault Report sent with the unit. A contact name and telephone number are also required with the Fault Report sent with the unit.
Fault report details required.
Company:
Name:
Address:
Contact Name:
Telephone No:
Returns Number:
Symptoms of the fault (to include switch setting positions, input signals etc):
Packing
Please ensure that the unit is well packed as all mechanical damage is chargeable. TSL recommends that you insure your equipment for transit damage.
The original packaging, when available, should always be used when returning equipment..
If returned equipment is received in a damaged condition, the damage should be reported both to TSL and the carrier immediately.
YEAR 2000 CONFORMITY REQUIREMENTS
This product conforms to the following rules: Rule 1 No value for the current date will cause any interruption in operation.
Rule 2 Date based functionality will behave consistently for dates prior to, during and after the Year
2000.
Rule 3 In all interfaces and data storage, the century in any date is specified either explicitly or by
unambiguous algorithms or by inferencing rules.
Rule 4 The Year 2000 is recognised as a leap year.
MDU12-PMi Manual 8 Issue 4
EC DECLARATION OF CONFORMITY
Application of Council Directives Nos: EC Low Voltage Directive (73/23/EEC)(OJ L76 26.3.73)(LVD). Amendment: (93/68/EEC) (OJ L220 30.8.93). Conformity Standards Declared: EN 60950
EMC Directive: 89/336/EEC, Amended 92/31/EEC. Conformity Standards Declared: EN 50081-1, EN 50082-1
Manufacturer’s Name: Television Systems Ltd Manufacturer’s Address: Vanwall Road Maidenhead SL6 4UB England United Kingdom
Type of Equipment: Mains Distribution Unit Model No: MDU12-PMi Part Number: TSLP- MDU12-PMi Date CE Mark Affixed: 04 I, the undersigned, declare that the equipment specified above conforms to the quoted Directives and
Standards. Place: Maidenhead, England Signature: Date: TBA Print: A J Mackinder Position: PRODUCT MANAGER
MDU12-PMi Manual 9 Issue 4
Power Manager Mains Distribution Unit MDU12-PMi
0
I
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
2.0 Description
Features:
19" 1RU.
16 Amp Double Pole Breaker / Switch.
12 Fused IEC outlets.
LED Indication
o Power - Blue - Power applied to the unit. o LAN - Flashing Amber LAN connected & active o Output LEDs 1-12 o Green - Circuit on and fuse OK o Amber – Circuit off and fuse OK. o Red – Circuit off and fuse failed. o Off – Circuit on but fuse has failed
Serial D9 & RJ11 set up ports.
Cable tie bar.
Ethernet SNMP status reporting and Email alerts for:
o Each mains circuit. o 16 Opto-isolated GPI inputs via D37 connector. o Input mains failure. o Access to unit configuration and SNMP data via secure web browser interface.
Relay controlled outputs with delayed power up.
Latching relays are fitted to reduce internal heat dissipation as they draw no current once set.
Outputs can be controlled via SNMP, or the secure web browser interface (which also provides
SNMP control lockout per output if required).
Start up can be immediate, sequential, or individual delay.
This 1RU unit is designed to fit into a rack in any position. The inlet is via a Neutrik Powercon NAC3FCA connector. A free cable mounted connector is supplied with each unit.
A 16 A TCB (Thermal Over current Circuit Breaker) is fitted to the input and the rear 12 IEC outlets are via 10A fuses located on the front panel.
The MDU12-PM can accept up to 16 opto isolated GPI alarms on a D37F connector. There is a rear D9F and front RJ11 port for TCP/IP programming requirements and a standard CAT5 RJ45 Ethernet socket for network connection.