TSI Instruments Alnor Model AXD620, AIRFLOW Model PVM620 Operation And Service Manual

Ventilation Testing
Micromanometer
Alnor® Model AXD620
AIRFLOWTM Model PVM620
Operation and Service Manual
Copyright©
TSI Incorporated / 2007-2008 / All rights reserved.

Address

TSI Incorporated / 500 Cardigan Road / Shoreview, MN 55126 / USA
Fax No.
(651) 490-3824
LIMITATION OF WARRANTY AND LIABILITY (effective July 2000)
Seller warrants the goods sold hereunder, under normal use and service as described in the operator's manual, shall be free from defects in workmanship and material for twenty-four (24) months, or the length of time specified in the operator's manual, from the date of shipment to the customer. This warranty period is inclusive of any statutory warranty. This limited warranty is subject to the following exclusions: a. Hot-wire or hot-film sensors used with research anemometers, and certain other components
when indicated in specifications, are warranted for 90 days from the date of shipment.
b. Parts repaired or replaced as a result of repair services are warranted to be free from defects
in workmanship and material, under normal use, for 90 days from the date of shipment.
c. Seller does not provide any warranty on finished goods manufactured by others or on any
fuses, batteries or other consumable materials. Only the original manufacturer's warranty applies.
d. Unless specifically authorized in a separate writing by Seller, Seller makes no warranty with
respect to, and shall have no liability in connection with, goods which are incorporated into other products or equipment, or which are modified by any person other than Seller.
The foregoing is IN LIEU OF all other warranties and is subject to the LIMITATIONS stated herein. NO OTHER EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR PARTICULAR PURPOSE OR MERCHANTABILITY IS MADE.
TO THE EXTENT PERMITTED BY LAW, THE EXCLUSIVE REMEDY OF THE USER OR BUYER, AND THE LIMIT OF SELLER'S LIABILITY FOR ANY AND ALL LOSSES, INJURIES, OR DAMAGES CONCERNING THE GOODS (INCLUDING CLAIMS BASED ON CONTRACT, NEGLIGENCE, TORT, STRICT LIABILITY OR OTHERWISE) SHALL BE THE RETURN OF GOODS TO SELLER AND THE REFUND OF THE PURCHASE PRICE, OR, AT THE OPTION OF SELLER, THE REPAIR OR REPLACEMENT OF THE GOODS. IN NO EVENT SHALL SELLER BE LIABLE FOR ANY SPECIAL, CONSEQUENTIAL OR INCIDENTAL DAMAGES. SELLER SHALL NOT BE RESPONSIBLE FOR INSTALLATION, DISMANTLING OR REINSTALLATION COSTS OR CHARGES. No Action, regardless of form, may be brought against Seller more than 12 months after a cause of action has accrued. The goods returned under warranty to Seller's factory shall be at Buyer's risk of loss, and will be returned, if at all, at Seller's risk of loss.
Buyer and all users are deemed to have accepted this LIMITATION OF WARRANTY AND LIABILITY, which contains the complete and exclusive limited warranty of Seller. This LIMITATION OF WARRANTY AND LIABILITY may not be amended, modified or its terms waived, except by writing signed by an Officer of Seller.

Service Policy

Knowing that inoperative or defective instruments are as detrimental to TSI as they are to our customers, our service policy is designed to give prompt attention to any problems. If any malfunction is discovered, please contact your nearest sales office or representative, or call Customer Service department at +44 (0) 149 4 459200 (UK), (800) 874-2811 (USA), or (1) 651­490-2811 (International).
CONTENTS
CHAPTER 1 UNPACKING AND PARTS IDENTIFICATION ............
CHAPTER 2 SETTING-UP................................................................. 3
Supplying Power to the Alnor Model AXD620/AIRFLOW PVM620 ..3
Installing the Batteries ............................................................... 3
Using the Optional AC Adapter ................................................. 3
Connecting to a Computer.............................................................. 3
CHAPTER 3 OPERATION .................................................................5
Keypad Functions ...........................................................................5
Common Terms .............................................................................. 5
Menus ............................................................................................. 6
DISPLAY SETUP................................................................................. 6
PRESSURE ZERO............................................................................... 6
SETTINGS .........................................................................................6
FLOW SET UP....................................................................................6
ACTUAL/STANDARD SETUP ................................................................7
DATA LOGGING .................................................................................7
Measurements...........................................................................7
Log Mode/Log Settings .............................................................7
Delete Data................................................................................ 7
% Memory .................................................................................7
LogDat2TM Downloading Software.................................................. 7
CHAPTER 4 MAINTENANCE............................................................9
1
Recalibration...................................................................................9
Cases..............................................................................................9
Storage ...........................................................................................9
CHAPTER 5 TROUBLESHOOTING................................................ 11
APPENDIX A SPECIFICATIONS..................................................... 13
iii
Chapter 1
Unpacking and Parts Identification
Carefully unpack the instrument and accessories from the shipping container. Check the individual parts against the list of components below. If anything is missing or damaged, notify TSI immediately.
1. Carrying case
2. Instrument
3. Pressure tubing
4. Static pressure tip
5. USB cable
6. CD-ROM with downloading software
1
Chapter 2
Setting-up

Supplying Power to the Alnor Model AXD620/AIRFLOW PVM620

The Alnor AXD620/A batteries.

Installing the Batteries

Insert four AA batteries as indicated by the diagram located on the inside of the battery compartment. The Alnor AXD620/A PVM620 is designed to operate with either alkaline or NiMH rechargeable batteries, although it will not recharge NiMH batteries. Battery life will be shorter if NiMH batteries are used. Carbon-zinc batteries are not recommended because of the danger of battery acid leakage.

Using the Optional AC Adapter

When using the AC adapter, the batteries (if installed) will be bypassed. Be sure to provide the correct voltage and frequency, which is marked on the back of the AC adapter. The AC adapter will not recharge the batteries.
IRFLOW PVM620 is powered with four size AA
IRFLOW

Connecting to a Computer

Use the Computer Interface USB Cable to connect the instrument to a computer. Connect the end labeled “COMPUTER” to the computer USB port and the other end to the data port of the Alnor AXD620/A PVM620.
For information on how to download stored data see Chapter 3
Downloading Software.
Caution: This symbol is used to indicate that the data port of the Alnor AXD620/A connection to a public telecommunications network. Connect the USB data port only to another USB port.
IRFLOW PVM620 is not intended for
IRFLOW
LogDat2™
3
Chapter 3
Operation

Keypad Functions

ON/OFF Key
Arrow (ST) Keys
(Enter) Key
Arrow (gor h) and Menu Soft Keys

Common Terms

In this manual there are several terms that are used in different places. The following is a brief explanation of the meanings of those terms.
Sample
Test ID
Press to turn the Alnor Model AXD620/A PVM620 on and off. During the power up sequence the display will show the following: Model Number, Serial Number, Software Revision and Last Date Calibrated.
Press to scroll through choices while setting a parameter.
Press to accept a value or condition.
Press arrow keys to change choices while setting a parameter. Press the Menu soft key to select the Menu selections, which are Display Setup, Pressure Zero, Settings, Flow Setup, Actual/Std Set up, Data Logging, and Calibration.
Consists of all of the measurement parameters stored at the same time.
A group of samples. The statistics (average, minimum, maximum, and count) are calculated for each test ID. The maximum number of test IDs is
100.
IRFLOW
5
Time Constant
The time constant is an averaging period. It is used to dampen the display. If you are experiencing fluctuating flows, a longer time constant will slow down those fluctuations. The display will update every second, but the displayed reading will be the average over the last time constant period. For example, if the time constant is 10 seconds, the display will update every second, but the displayed reading will be the average from the last 10 seconds. This is also referred to as a “moving average”.
Log Interval

Menus

DISPLAY SETUP

Display setup menu is where you will setup the desired parameters to be displayed on the running screen. With a parameter highlighted you can then use the ON soft key to have it show up on the running screen or select the OFF soft key to turn off the parameter. Use PRIMARY soft key to have a parameter show up on the running screen in a larger display. Only one parameter can be selected as a primary, and up to 2 secondary parameters can be selected at one time.

PRESSURE ZERO

To zero the pressure reading, select the Pressure Zero menu. The instrument will indicate if the pressure zero was successful.

SETTINGS

Settings menu is where you can set the general settings. These include Language, Beeper, Select Units, Time Constant, Contrast, Set Time, Set Date, Time Format, Date Format, Number Format, Backlight and Auto Off. Use the g use the key to accept settings.
or h soft keys to scroll through the settings for each option and
The logging interval is a frequency period that the instrument will log readings. For example, if the logging interval is set to 30 minutes, each sample will be the average of the last 30 minutes.

FLOW SET UP

In Flow Setup mode, there are four types: Round Duct, Rectangle Duct, Duct Area, and K-Factor. Use the g then press the key to accept the desired type. To change the setting, highlight the Enter Settings option and press the key.
6 Chapter 3
or h soft keys to scroll through the types and
NOTE: K-Factors are intended for use with diffusers with pressure taps and a manufacturer-supplied K factor.

ACTUAL/STANDARD SETUP

Choose Actual/Standard measurements and parameters in the Act/Std Setup menu. Within this menu, the user can also select Standard Temperature, Standard Pressure and a source for the actual temperature. The actual barometric pressure must be entered to convert air velocity and volume measurements to actual conditions.

DATA LOGGING

Measurements

Measurements to be logged are independent of measurements on the display, and must therefore be selected under DATA LOGGING Æ Measurements.

Log Mode/Log Settings

You can set Log Mode to Manual and Auto-save.
Manual mode does not automatically save data, but instead prompts
the user to save a sample.
In Auto-save mode, the user manually takes samples that are
automatically logged.
The Log Interval setting is active during Auto-save mode

Delete Data

Use this to delete all data, delete test or delete sample.

% Memory

This option displays the memory available. Delete All, under Delete Data, will clear memory and reset the memory available.
TM
LogDat2
The Alnor AXD620/A
Downloading Software
IRFLOW PVM620 comes with special software called
LogDat2 Downloading Software, which is designed to provide you with maximum flexibility and power. To install this software on your computer, follow the instructions on the label of the LogDat2 CD-ROM.
To download data from the Alnor AXD620/A supplied computer interface USB cable to the Alnor AXD620/A
IRFLOW PVM620, connect the
IRFLOW
PVM620 and to a computer USB port. Then run the LogDat2 downloading software. Within the LogDat2 software, either select the tests to be downloaded or double-click on a test to open it.
Operation 7
Chapter 4
Maintenance
The Alnor Model AXD620/AIRFLOW PVM620 requires very little maintenance to keep it performing well.

Recalibration

To maintain a high degree of accuracy in your measurements, we recommend that you return your Alnor Model AXD620/A to TSI for annual recalibration. Please contact one of TSI’s offices or your local distributor to make service arrangements and to receive a Return Material Authorization (RMA) number. To fill out an online RMA form, visit TSI’s website at
U.S. & International UK
TSI Incorporated Alnor Products Lancaster Road 500 Cardigan Road Cressex Business Park Shoreview MN 55126-3996 High Wycombe Tel: (800) 874-2811 Buckinghamshire (651) 490-2811 HP12 3QP England Fax: (651) 490-3824 Tel: +44 (0) 149 4 459200 Fax: +44 (0) 149 4 459700
The Alnor Model AXD620/A the field using the CALIBRATION menu. These field adjustments are intended to make minor changes in calibration to match a user's calibration standards. The field adjustment is NOT intended as a complete calibration capability. For complete, multiple-point calibration and certification, the instrument must be returned to the factory.
http://service.tsi.com.
TSI Instruments Ltd.
IRFLOW PVM620 can also be recalibrated in
IRFLOW PVM620

Cases

If the instrument case or storage case needs cleaning, wipe it off with a soft cloth and isopropyl alcohol or a mild detergent. Never immerse the Alnor Model AXD620/A AXD620/A replaced immediately to prevent access to hazardous voltage.

Storage

Remove the batteries when storing the unit for more than one month to prevent damage due to battery leakage.
IRFLOW PVM620. If the enclosure of the Alnor Model
IRFLOW PVM620 or the AC adapter becomes broken, it must be
9
Chapter 5
Troubleshooting
Table 5-1 lists the symptoms, possible causes, and recommended solutions for common problems encountered with the Alnor Model AXD620/A solutions solves your problem, please contact TSI.
Table 5-1: Troubleshooting the Alnor Model AXD620/A PVM620
Symptom Possible Causes Corrective Action
No Display Unit not turned on Switch unit on. Low or dead batteries Replace batteries or plug
Dirty battery contacts Clean the battery
Reading fluctuates / unstable
No response to keypad
Instrument Error message appears
Fault in instrument Factory service required
The pressure sensor is protected from damage up to 7 psi (48 kPa or 360 mmHg). At higher pressure it can burst!
IRFLOW PVM620. If your symptom is not listed, or if none of the
IRFLOW
in AC adapter.
contacts.
Fluctuating flow Reposition probe in
less-turbulent flow or use longer time constant.
Keypad locked out Unlock keypad by
pressing simultaneously.
Memory is full Download data if desired,
then DELETE ALL memory.
on instrument.
ST keys
WARNING!
11
Appendix A
Specifications
Specifications are subject to change without notice.
Static / Differential Pressure:
1
Range
: -15 to +15 in. H2O (-28.0 to +28.0 mm Hg, -3735 to
+3735 Pa) Accuracy: ±1% of reading ±0.005 in. H Resolution: 0.001 in. H
Velocity From a Pitot Tube:
2
Range
: 250 to 15500 ft/min (1.27 to 78.7 m/s)
3
Accuracy
: ±1.5% at 2000 ft/min (10.16 m/s)
O (1 Pa, 0.01 mm Hg)
2
Resolution: 1 ft/min (0.1 m/s)
Duct Size:
Range: 1 to 250 inches in increments of 0.1 in.
(1 to 635 cm in increments of 0.1 cm)
Volumetric Flow Rate:
Range: Actual range is a function of actual velocity, pressure, duct
size, and K factor
Instrument Temperature Range:
Operating : 40 to 113°F (5 to 45°C) Storage: -4 to 140°F (-20 to 60°C)
O (±0.01 mm Hg, ±1 Pa)
2
Instrument Operating Conditions:
Altitude up to 4000 meters Relative humidity up to 80% RH, non-condensing Pollution degree 1 in accordance with IEC 664 Transient over voltage category II
Data Storage Capabilities:
Range: 12,700+ samples and 100 test IDs (one sample can contain
fourteen measurement types)
Logging Interval:
Intervals: 1 second to 1 hour
Time Constant:
Intervals: User selectable
External Meter Dimensions:
3.3 in. × 7.0 in. × 1.8 in. (8.4 cm × 17.8 cm × 4.4 cm)
Meter Weight:
Weight with batteries: 0.6 lbs (0.27 kg)
13
Power Requirements:
Four AA-size batteries (included) or AC adapter (optional) 9 VDC, 300 mA, 4-18 watts (input voltage and frequency vary depending on which adapter is used)
1
Overpressure range = 7 psi (190 in. H2O, 360 mmHg, 48 kPa).
2
Pressure velocity measurements are not recommended below 1,000 ft/min (5 m/s) and are best
suited to velocities over 2000 ft/min. Range can vary depending on barometric pressure.
3
Accuracy is a function of converting pressure to velocity. Conversion accuracy improves when
actual pressure values increase.
14 Appendix A
TSI Incorporated 500 Cardigan Road Shoreview, MN 55126 USA Toll Free (800) 874-2811 Telephone (651) 490-2811 Fax: (651) 490-3824
E-mail: customerservice@alnor.com Web: www.alnor.com
France Tel: +33 491 95 21 90 E-mail: tsifrance@tsi.com Germany Tel: +49 241 523030 E-mail: tsigmbh@tsi.com Sweden Tel: +46 8 595 13230 E-mail: tsiab@tsi.com
Part No. 1980588 Rev. B Copyright © 2008 by TSI Incorporated