TSI Instruments 8691-2 Installation Instructions Manual

MODEL 8691-2
FUME HOOD SENSOR AVERAGING VENTING KIT
INSTALLATION INSTRUCTIONS
This Sensor Averaging Venting Kit can be installed with all TSI Fume Hood Face Velocity Controllers and Face Velocity Monitors.
Installation will be substantially easier if the side wall of the fume hood can be removed prior to Sensor Venting Kit installation. If the side wall cannot be removed, there is usually an access panel inside the fume hood that needs to be removed. This should allow enough room to maneuver the tubing.
Parts List (Figure 1)
One T-fitting Assembly w/sensor housing 20 ft.1½" ID Tubing One extra-long sensor cable Two mounting flanges (black) One bag with:
One O-ring Four screws Four clamps Two brackets Two self-tapping nuts
Step 4: Mount the MOUNTING FLANGE to the
MOUNTING PLATE using 2 #8-32 x 5/8 inch
screws (Figure 3).
WARNING
Both sides of tubing must be of equal length (Figure 4).
Step 5: Cut tubing to fit between the MOUNTING
FLANGE and the T FITTING. Slide 2 hose clamps onto tubing. Remove the T FITTING and insert one end of tubing onto the T FITTING. Push other end of tubing onto mounting flange. Secure tubing by tightening hose clamps.
Step 6: Repeat Step 2 through Step 5 on the other
side of the hood.
Step 7: Loosely push T FITTING onto the SENSOR
ASSEMBLY.
Ins tallation
Step 1: Select location of SENSOR ASSEMBLY,
typically lying on top of the fume hood (Figure 4). SENSOR ASSEMBLY must be located to reference room air, within 15 ft of the controller. If using an existing velocity sensor, make sure to use O-ring to seal the side-wall sensor to the sensor housing and tighten down self-tapping nuts using the two posts on the sensor housing.
Step 2: Determine MOUNTING FLANGE location. Use
Figure 2 as a guide.
Step 3: Drill 1½” hole through the fume hood liner at
this location
Figure 1: Parts
Figure 2: Mounting Flange Location
Figure 3: Finished Assembly
USA Tel: +1 800 874 2811 UK Tel: +44 149 4 459200 France Tel: +33 491 11 87 64 Germany Tel: +49 241 523030
India Tel: +91 80 67877200 China Tel: +86 10 8219 7688 Singapore Tel: +65 6595 6388
Figure 4: Typical Installation
Sen so r Assembly
If the Averaging Fume Hood Vent Kit is added to an existing fume hood controller, then the sensor assembly must be assembled.
Step 1: Open the Sensor Assembly Box, and screw the Sensor in.
Step 2: Close the Sensor Assembly Box. Screw the box together, using the #4-40 screw provided.
This concludes the installation of the Fume Hood Sensor Venting Kit. If you have questions, please call TSI at (651) 490-2811 or 1-800-874-2811.
TSI Incorporated Visit our website www.tsi.com for more information.
P/N 1980334 Rev. F ©2014 TSI Incorporated Printed in U.S.A.
Loading...