TSI Instruments 8636-N2 Manual Supplement

Manual Supplement
Product/System Title: Room Pressure Controller with Reheat
Control and N2 Communications Protocol
Contents of this manual supplement include:
1) Sequence of Operation
2) Menu configuration
3) Software items deleted
4) Variable Map
5) Description of variables
6) Wiring Diagram
N2 communications are installed on the Model 8636-N2 room pressure controllers. This document provides the technical information needed for the host DDC system to communicate with 8636 units. This document assumes the programmer is familiar with the N2 protocol. Further technical assistance is available from TSI if your question is related to TSI interfacing to a DDC system. If you need further information regarding N2 programming in general, please contact Johnson Controls.
Project: Date: Page 1 of 9 Released 10/03/01
Manual Supplement
Sequence of Operation
The Model 8636-N2 measures the room pressure differential and receives temperature information from the temperature sensor. The 8636-N2 control algorithm modulates the supply and general exhaust air to provide adequate supply air while maintaining the room pressure differential and temperature control.
In occupied mode, the Model 8636-N2 has two supply flow set points: ventilation and temperature. The ventilation setpoint is the minimum supply flow for the space, used when the heating and cooling loads are met. The temperature supply set point is a higher flow, required to meet an increased cooling load in the lab.
Laboratory temperature is continuously transmitted to the Model 8636-N2. When the laboratory temperature is satisfied, the ventilation set point is maintained, unless additional supply air is required for the room pressure balance. When the space temperature is more than 1°F above the temperature setpoint, the 8636-N2 slowly will increase the supply air volume, to a maximum of the temperature minimum supply flow, until the space temperature returns to setpoint. When the space temperature is more than 1°F below the temperature setpoint, the 8636-N2 slowly will decrease the supply air volume, to a minimum of the ventilation minimum supply flow, until the space temperature returns to setpoint. If the supply volume is at the ventilation minimum supply flow, the Model 8636-N2 will modulate the reheat valve to provide the necessary heating.
In unoccupied mode, the supply flow will remain at the unoccupied supply flow rate.
Supply air volumes will rise above the minimum setpoints, under all conditions, as required to maintain space pressurization. Temperature control and occupied/unoccupied modes will only affect the minimum supply flows, which are used, for example, when fume hood sashes are lowered.
NOTE: The 8636-N2 will not allow the temperature minimum supply volume to be less than the ventilation minimum supply volume.
Project: Date: Page 2 of 9 Released 10/03/01
Manual Supplement
Menu Configuration
SETPOINTS ALARM CONFIGURE CALIBRATION SETPOINT REM SETPOINT UNOCC SETP VENT MIN SET TEMP MIN SET TEMP SETP
CONTROL SUPPLY FLOW SPEED SENSITIVITY CONTROL SIG Kc VALUE Ti VALUE TEMP OUTPUT TEMP CONTROL TEMP Kc VAL
LOW ALARM HIGH ALARM REM LOW ALM REM HIGH ALM MIN SUP ALM ALARM RESET AUDIBLE ALM ALARM DELAY DOOR DELAY MUTE TIMEOUT
SP1 DCT REA SP2 DCT REA SP1 FLO ZERO SP2 FLO ZERO FLO STA TYPE TOP VELOCITY SP LOW SETP SP HIGH SETP SP1 LOW CAL SP1 HIGH CAL SP2 LOW CAL SP2 HIGH CAL RESET CAL
UNITS NET ADDRESS ACCESS CODES
SENSOR SPAN ELEVATION TEMP CAL
DIAGNOSTICS
CONTROL SUP
CONTROL EXH CONTROL TEMP SENSOR INPUT SENSOR STAT DOOR SWITCH UNOCC SWITCH SUP1 FLOW IN SUP2 FLOW IN TEMP INPUT ALARM RELAY
Software Item Deleted
The following software item has been deleted from the 8636-N2:
Menu Item
SETPOINTS MIN SUP DAMP MAX SUP DAMP MIN EXH DAMP MAX EXH DAMP CONFIGURE NET PROTOCOL
Project: Date: Page 3 of 9 Released 10/03/01
Manual Supplement
Variable Map
NPT NPA UNITS1 DESCRIPTION
AI 1 ft/min, m/s,
in. H2O, Pa,
mm H2O AI 2 CFM, l/s Total Supply Flow Rate AI 3
°F, °C AI 4 ft/min, m/s,
in. H2O, Pa,
mm H2O AI 5 CFM, l/s Minimum Supply Setpoint AI 6 # Supply Control Output AI 7 # Exhaust Control Output AI 8 # Temperature Control Output BI 1 Low Room Pressure Alarm 0=Normal
BI 2 High Room Pressure Alarm 0=Normal
BI 3 Min. Flow Alarm 0=Normal
BI 4 Emergency Mode 0=Normal
BI 5 Room Mode 0=Main
BI 6 Occupied/Unoccupied Mode 0=Occupied
BI 7 Data Error 0=Normal
AO 1 ft/min, m/s,
in. H2O, Pa,
mm H2O AO 2 ft/min, m/s,
in. H2O, Pa,
mm H2O AO 3 ft/min, m/s,
in. H2O, Pa,
mm H2O AO 4 ft/min, m/s,
in. H2O, Pa,
mm H2O AO 5 CFM, l/s Min. Supply Flow Alarm Setpoint
Room Pressure Value
Temperature Control Setpoint
1=Low Alarm
1=High Alarm
1=Low Flow Alarm
1=Emergency Mode
1=Remote
1=Unoccupied
1=Data Error Low Alarm Setpoint
High Alarm Setpoint
Remote Low Alarm Setpoint
Remote High Alarm Setpoint
Project: Date: Page 4 of 9 Released 10/03/01
Manual Supplement
NPT NPA UNITS1 DESCRIPTION
AO 6 ft/min, m/s,
Main Pressure Setpoint in. H2O, Pa, mm H2O
AO 7 CFM, l/s Remote Pressure Setpoint AO 8 CFM, l/s Minimum Ventilation Rate Supply Flow Setpoint AO 9 CFM, l/s Minimum Temperature Supply Flow Setpoint AO 10 CFM, l/s Unoccupied Mode Minimum Supply Flow Setpoint AO 11
°F, °C
Temperature Setpoint
AO 12 # Units 0=Feet per minute
1=Meters per second
2=Inches of H2O
3=Pascals
1
Units will correspond with choice in UNITS variable (AO #12). Flow rates will either be CFM or l/s, based on
whether UNITS variable is set for an english or metric unit type.
Project: Date: Page 5 of 9 Released 10/03/01
Manual Supplement
Description of Variables
NPT - Network Point Type
Variables are defined as analog inputs, binary inputs, and analog outputs. Analog inputs are current control parameters and items that the controller is measuring. Binary inputs represent controller states. Analog outputs are the programmable setpoints for the isolation room pressure controller and monitor. These setpoints can be changed through the keypad or by overriding the current setpoint.
NPA - Network Point Address
Address of the desired point.
Change of Status (COS) - Room Pressure Analog Input
The 8636-N2 has the ability to change control setpoints locally. The alarm setpoints need to be based on the controller’s control setpoint (AI #4). For example the setpoint could go from -0.002 “H2O to +0.001 “H2O. If the COS alarm setpoints are not changed to accommodate you could get low alarm or low warning messages when the unit is working correctly. If these alarm points are set outside of the negative and positive setpoint values, incorrect alarm messages can be prevented.
Override Analog Input Command Analog Input values can be set using the override command. These values will be reset to the correct items when the Override is released. There is not a time-out on the override command.
Override Binary Input Command Overriding a 1 to Emergency binary inputs enables that mode. To release the controller from emergency state, override a 0 to the Emergency input or press either the emergency or reset key. Releasing the override will return the controller to the Normal state. If the 8636-N2 had been put into Emergency mode from the keypad, then it cannot be cleared remotely.
Overriding a 1 to Room Mode binary inputs enables Remote mode. To release the controller from remote state, override a 0 to the Room Mode. Releasing the override will return the controller to the Normal state.
Overriding a 1 to the Occupied/Unoccupied Mode binary inputs enables the unoccupied mode. To release the controller from the unoccupied state, override a 0 to the Occupied/Unoccupied Mode. The Occupied/Unoccupied Mode can only be accessed through N2 communications.
The alarm and data error variables can be overridden, but this will not affect the controller. Overriding the low alarm variable will result in a change of status, but will not put the controller into low alarm mode. The local alarm modes can only be controlled locally. Only override these variables for diagnostic purposes, and release them for normal operation.
Project: Date: Page 6 of 9 Released 10/03/01
Manual Supplement
Binary Input Data Error Data Error binary inputs are used to indicate if something has gone wrong with the controller. Data Error indicates when some of the data stored on the device has been corrupted. The calibration and setpoint values should be checked on the controller.
Override Analog Output Command The analog output variables can be overridden to change their values. The overridden value will be checked for validity. If invalid, the override command will be ignored, and the value will not change. The override flag will not be set when the value is ignored. The override command will be cleared when the variable is reset in the menus. The variable will not reset with the release command.
Supported Commands
Command Response
Request Device ID Returns 0x10 Synchronize Time Command Acknowledged. There Is No Internal Clock To
Synchronize. Poll Without/With Ack Message Any Change Of Status Is Returned Read Analog Input Command Variable Value Read Binary Input Command Variable Value Read Analog Output Command Variable Value Write Analog Input Acknowledge Write Binary Input Acknowledge Write Analog Output Acknowledge Override Analog Input Command Acknowledge Override Binary Input Command Acknowledge Override Analog Output Command Acknowledge Override Release Request Acknowledge Identify Device Type Command Returns 0x10h
Note: Poll Without/With Ack Message will need to be sent twice in order to receive all of the possible change of status variables.
Project: Date: Page 7 of 9 Released 10/03/01
Manual Supplement
Wiring Diagrams
MODEL 8636-N2 PRESSUR E CONTROLLER
MODEL 8636-N2
WIRING DIAGRAM - ELECTRIC
WIRING DIAG RAM - ELEC TRIC
28
27
26
25
24
23
22
21
Project: Date: Page 8 of 9 Released 10/03/01
Manual Supplement
MODEL 8636-N2 PRESSURE CONTROLLER
MODEL 8636-N2
WIRING DIAGRAM - PNEUMATIC
Project: Date: Page 9 of 9 Released 10/03/01
Loading...