TSI Alnor VOC Specifications

VOLATILE ORGANIC
COMPOUNDS (VOC)
INDOOR AIR QUALITY PROBES MODELS 984, 985, 986 & 987
TSI VOC probes are pre-calibrated, plug-and-play accessory probes for multi-purpose meters including, Q-Trak™ Monitor 7575, VelociCalc® meter 9565 and Airow™ Instruments TA465 meter. When combined with these meters, long-term data analysis can be performed and reported, which is useful for monitoring or investigating the indoor environment.
Applications
+ IAQ investigations
+ Building commissioning
+ Track down emissions to their source
Data Collection and Reporting
Expanded data logging capacity and the inclusion of TrakPro™ Data
Analysis Software provides the capabilities to work more eectively
and eciently. The Q-Trak monitor can store up to 38.9 days of data
collected at one-minute log intervals. The stored data can be recalled,
reviewed on screen, and downloaded for easy reporting.
TrakPro software helps you to generate professional graphs
for your reports.
Features and Benets
+ Pre-calibrated plug-and-play accessory probes for TSI Q-Trak
Monitor 7575, VelociCalc Meter 9565 and
Airow Instruments TA465 Meter
+ Compact design with ergonomic handle
+ Four versions available with multiple measurement capabilities
– Model 984 - Low concentration (ppb) VOC and temperature
– Model 985 - High concentration (ppm) VOC and temperature
– Model 986 - Low concentration (ppb) VOC, temperature,
CO2 and humidity
– Model 987 - High concentration (ppm) VOC, temperature,
CO2 and humidity
+ Two-year factory warranty
+ Send only the probe back for factory calibration
UNDERSTANDING, ACCELERATED
SPECIFICATIONS
VOLATILE ORGANIC COMPOUNDS VOC INDOOR AIR QUALITY PROBES MODELS 984, 985, 986, AND 987
Field Service
TSI VOC probes are competitively priced to others in the
marketplace but feature a lower cost of ownership due its compact
design and construction, which is geared for eld service capability.
+ Field calibration
– Temperature
– Relative humidity
– Volatile organic compounds (VOC)
– Carbon dioxide (CO2)
+ Replaceable sensors
+ Sensor maintenance
– Lamp cleaning
– Lamp replacement
Instrumentation
The Q-Trak Monitor 7575, VelociCalc Meter 9565 and Airow
Instruments TA465 Meter feature a menu-driven user interface
for easy operation. VOC probes are also compatible with Airow™
Instruments TA460 series and TSI’s discontinued 7565 and 9555
series, if instrument rmware is at revision 2.10 or higher.
Model 984 Low Concentration (ppb) VOC and Temperature
Range 10 to 20,000 ppb, 14 to 140°F (-10 to 60°C) Accuracy ±1.0°F (±0.5°C)
1
Resolution 10 ppb4, 0.1°F (0.1°C)
Model 985 High Concentration (ppm) VOC and Temperature
Range 1 to 2,000 ppm, 14 to 140°F (-10 to 60°C) Accuracy ±1.0°F (±0.5°C)
1
Resolution 1 ppm4, 0.1°F (0.1°C)
Model 986 Low Concentration (ppb) VOC, Temperature, CO2, and Humidity
Range 10 to 20,000 ppb VOC, 0 to 5,000 ppm CO 14 to 140°F (-10 to 60°C), 5 to 95% RH Accuracy ±3% of reading or 50 ppm CO whichever is greater ±1.0°F (±0.5°C)1, ±3% RH Resolution 10 ppb4 VOC, 0.1 ppm CO
0.1°F (0.1°C), 0.1% RH
Model 987 High Concentration (ppm) VOC, Temperature, CO2, and Humidity
2
,
2
3
2
,
2
Range 1 to 2,000 ppm VOC, 0 to 5,000 ppm CO 14 to 140°F (-10 to 60°C), 5 to 95% RH Accuracy ±3% of reading or 50 ppm CO
whichever is greater ±1.0°F (±0.5°C)1, ±3% RH
3
2
,
2
Resolution 1 ppm4 VOC, 0.1 ppm CO2,
0.1°F (0.1°C), 0.1% RH
2
2
On-screen prompts and step-by-step instructions guide the user
through operation and eld calibration. These instruments also
feature an ergonomic, over molded case design and a keypad
lockout to prevent tampering during unattended use.
+ Display up to ve measurements simultaneously
+ Log multiple parameters to investigate trends
+ Calculate dew point, wet bulb and percent outside air
(VOC models 986 and 987)
+ Store up to 38.9 days of data collected at one-minute
log intervals when used with the Q-Trak 7575 Meter
+ User selectable logging intervals and start/stop times
+ Internal barometric pressure sensor
+ Download data to TrakPro Data Analysis Software
– Report generation
– Graph creation
– Instrument programming
UNDERSTANDING, ACCELERATED
TSI Incorporated
USA Tel: +1 800 874 2811 UK Tel: +44 149 4 459200 France Tel: +33 1 41 19 21 99 Germany Tel: +49 241 523030
Printed in U.S.A.
P/N 5001365 Rev D ©2015 TSI Incorporated
- Visit our website www.tsi.com for more information.
India Tel: +91 80 67877200 China Tel: +86 10 8219 7688 Singapore Tel: +65 6595 6388
Probe Dimensions
Length 7.0 in. (17.8 cm) (excluding handle) Base Diameter 0.75 in. (1.9 cm) Tip Diameter 1.0 in. (2.54 cm)
Note: The 984 and 986 probes are designed to measure ppb concentrations of VOCs. The 10 to 20,000 ppb range corresponds to 0.01 to 20 ppm.
1
Accuracy with instrument case at 77°F (25°C), add uncertainty of 0.05°F/°F (0.05°C/°C)
for change in instrument temperature.
2
Accuracy with probe at 77°F (25°C). Add uncertainty of ±0.2%/°F (±0.36%/°C)
away from calibrated temperature
3
Accuracy with probe at 77°F (25°C). Add uncertainty of 0.1% RH/°F (0.2% RH/°C)
for change in probe temperature. Includes 1% hysteresis.
4
When response factor is set to 1.00.
Specications are subject to change without notice.
TSI, the TSI logo and Velocicalc are registered trademarks, and Airow, Q-Trak and TrakPro are trademarks of TSI Incorporated.
Loading...