TSI Alnor AVM410 Operating Manual

Page 1
Ventilation Testing

Air Velocity Meter

Alnor® Model AVM410
AIRFLOWTM Model TA410
Operation and Service Manual
Page 2
Copyright©
TSI Incorporated / 2007-2008 / All rights reserved.
Address
TSI Incorporated / 500 Cardigan Road / Shoreview, MN 55126 / USA
Fax No.
(651) 490-3824
LIMITATION OF WARRANTY AND LIABILITY (effective July 2000)
Seller warrants the goods sold hereunder, under normal use and service as described in the operator's manual, shall be free from defects in workmanship and material for twenty-four (24) months, or the length of time specified in the operator's manual, from the date of shipment to the customer. This warranty period is inclusive of any statutory warranty. This limited warranty is subject to the following exclusions: a. Hot-wire or hot-film sensors used with research anemometers, and certain other
components when indicated in specifications, are warranted for 90 days from the date of shipment.
b. Parts repaired or replaced as a result of repair services are warranted to be free from
defects in workmanship and material, under normal use, for 90 days from the date of shipment.
c. Seller does not provide any warranty on finished goods manufactured by others or on any
fuses, batteries or other consumable materials. Only the original manufacturer's warranty applies.
d. Unless specifically authorized in a separate writing by Seller, Seller makes no warranty
with respect to, and shall have no liability in connection with, goods which are incorporated into other products or equipment, or which are modified by any person other than Seller.
The foregoing is IN LIEU OF all other warranties and is subject to the LIMITATIONS stated herein. NO OTHER EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR PARTICULAR PURPOSE OR MERCHANTABILITY IS MADE.
TO THE EXTENT PERMITTED BY LAW, THE EXCLUSIVE REMEDY OF THE USER OR BUYER, AND THE LIMIT OF SELLER'S LIABILITY FOR ANY AND ALL LOSSES, INJURIES, OR DAMAGES CONCERNING THE GOODS (INCLUDING CLAIMS BASED ON CONTRACT, NEGLIGENCE, TORT, STRICT LIABILITY OR OTHERWISE) SHALL BE THE RETURN OF GOODS TO SELLER AND THE REFUND OF THE PURCHASE PRICE, OR, AT THE OPTION OF SELLER, THE REPAIR OR REPLACEMENT OF THE GOODS. IN NO EVENT SHALL SELLER BE LIABLE FOR ANY SPECIAL, CONSEQUENTIAL OR INCIDENTAL DAMAGES. SELLER SHALL NOT BE RESPONSIBLE FOR INSTALLATION, DISMANTLING OR REINSTALLATION COSTS OR CHARGES. No Action, regardless of form, may be brought against Seller more than 12 months after a cause of action has accrued. The goods returned under warranty to Seller's factory shall be at Buyer's risk of loss, and will be returned, if at all, at Seller's risk of loss.
Buyer and all users are deemed to have accepted this LIMITATION OF WARRANTY AND LIABILITY, which contains the complete and exclusive limited warranty of Seller. This LIMITATION OF WARRANTY AND LIABILITY may not be amended, modified or its terms waived, except by writing signed by an Officer of Seller.
Service Policy
Knowing that inoperative or defective instruments are as detrimental to TSI as they are to our customers, our service policy is designed to give prompt attention to any problems. If any malfunction is discovered, please contact your nearest sales office or representative, or call Customer Service department at +44 (0) 149 4 459200 (UK), (800) 874-2811 (USA), or (1) 651­490-2811 (International).
Page 3
CONTENTS
CHAPTER 1 UNPACKING AND PARTS IDENTIFICATION ............
CHAPTER 2 SETTING-UP................................................................. 3
Supplying Power to the Alnor AVM410/AIRFLOW TA410 ................3
Installing the Batteries ............................................................... 3
Using The Telescoping Probe ........................................................ 3
Extending The Probe................................................................. 3
Retracting The Probe ................................................................3
CHAPTER 3 OPERATION .................................................................5
Keypad Functions ...........................................................................5
CHAPTER 4 MAINTENANCE............................................................7
Recalibration...................................................................................7
Cases..............................................................................................7
Storage ...........................................................................................7
CHAPTER 5 TROUBLESHOOTING.................................................. 9
APPENDIX A SPECIFICATIONS..................................................... 11
1
iii
Page 4
Page 5
Chapter 1
Unpacking and Parts Identification
Carefully unpack the instrument and accessories from the shipping container. Check the individual parts against the list of components below. If anything is missing or damaged, notify TSI immediately.
1. Carrying case
2. Instrument
1
Page 6
Page 7
Chapter 2
Setting-up

Supplying Power to the Alnor AVM410/AIRFLOW TA410

The Alnor AVM410/A batteries.

Installing the Batteries

Insert four AA batteries as indicated by the diagram located on the inside of the battery compartment. The Alnor AVM410/A TA410 is designed to operate with either alkaline or NiMH rechargeable batteries, although it will not recharge NiMH batteries. Battery life will be shorter if NiMH batteries are used. Carbon-zinc batteries are not recommended because of the danger of battery acid leakage.

Using the Telescoping Probe

The telescoping probe contains the velocity, temperature, and humidity sensors. When using the probe, make sure the sensor window is fully exposed and the orientation dimple is facing upstream.
NOTE: For temperature measurements, make sure that at least 3 inches (7.5 cm) of the probe is in the flow to allow the temperature sensor to be in the air stream.
IRFLOW TA410 is powered with four size AA
IRFLOW

Extending the Probe

To extend the probe, hold the handle in one hand while pulling on the probe tip with the other hand. Do not hold the cable while extending the probe as this prevents the probe from extending.

Retracting the Probe

To retract the probe, hold the handle in one hand while gently pushing on the probe tip with the other hand. If you feel the probe antenna binding, pull gently on the probe cable until the smallest antenna section is retracted. Collapse the rest of the antenna by pressing the probe tip.
3
Page 8
Page 9
Chapter 3
Operation

Keypad Functions

ON/OFF Key
ft/min / m/s Key
°C / °F Key
Changing Units
Press to turn the Alnor AVM410/A on and off. During the power up sequence the display will show the following: Model Number, Serial Number, Software Revision, and Last Date Calibrated.
Pressing this key changes the display to read air velocity.
Pressing this key changes the display to read temperature.
To change units, first put the desired measurement (air velocity or temperature) on the display. Then press and hold the left, unlabelled key for five seconds. Finally, use the select the units.
ST and ENTER key to
IRFLOW TA410
5
Page 10
Page 11
Chapter 4
Maintenance
The Alnor AVM410/AIRFLOW TA410 requires very little maintenance to keep it performing well.

Recalibration

To maintain a high degree of accuracy in your measurements, we recommend that you return your Alnor AVM410/A for annual recalibration. Please contact one of TSI’s offices or your local distributor to make service arrangements and to receive a Return Material Authorization (RMA) number. To fill out an online RMA form, visit TSI’s website at
U.S. & International UK
TSI Incorporated Alnor Products Stirling Road 500 Cardigan Road Cressex Business Park Shoreview MN 55126-3996 High Wycombe Tel: (800) 874-2811 Bucks (651) 490-2811 HP12 3RT United Kingdom Fax: (651) 490-3824 Tel: +44 (0) 149 4 459200 Fax: +44 (0) 149 4 459700

Cases

If the instrument case or storage case needs cleaning, wipe it off with a soft cloth and isopropyl alcohol or a mild detergent. Never immerse the Alnor AVM410/A
IRFLOW TA410 becomes broken, it must be replaced immediately to
A prevent access to hazardous voltage.
http://service.tsi.com.
TSI Instruments Ltd.
IRFLOW TA410. If the enclosure of the Alnor AVM410/
IRFLOW TA410 to TSI

Storage

Remove the batteries when storing the unit for more than one month to prevent damage due to battery leakage.
7
Page 12
Page 13
Chapter 5
Troubleshooting
Table 5-1 lists the symptoms, possible causes, and recommended solutions for common problems encountered with the Alnor AVM410/A TA410. If your symptom is not listed, or if none of the solutions solves your problem, please contact TSI.
Table 5-1: Troubleshooting the Alnor AVM410/A
Symptom Possible Causes Corrective Action
No Display Unit not turned on Switch unit on. Low or dead batteries Replace batteries or plug
Dirty battery contacts Clean the battery
Velocity reading fluctuates unstable Instrument Error message appears
Fluctuating flow Reposition probe in
Fault in instrument Factory service required
IRFLOW TA410
in AC adapter.
contacts.
less-turbulent flow
on instrument.
WARNING!
Remove the probe from excessive temperature immediately: excessive heat can damage the sensor. Operating temperature limits can be found in Appendix A, Specifications.
IRFLOW
9
Page 14
Page 15
Appendix A
Specifications
Specifications are subject to change without notice.
Velocity:
Range: 0 to 4000 ft/min (0 to 20 m/s) Accuracy
Resolution: 1 ft/min (0.01 m/s)
Temperature:
Range: 0 to 200°F (-18 to 93°C) Accuracy Resolution: 0.1°F (0.1°C)
Instrument Temperature Range:
Operating (Electronics): 40 to 113°F (5 to 45°C) Operating (Probe): 0 to 200°F (-18 to 93°C) Storage: -4 to 140°F (-20 to 60°C)
Instrument Operating Conditions:
Altitude up to 4000 meters Relative humidity up to 80% RH, non-condensing Pollution degree 1 in accordance with IEC 664 Transient over voltage category II
1&2
: ±5% of reading or ±5 ft/min (±0.025 m/s),
whichever is greater
3
: ±0.5°F (±0.3°C)
External Meter Dimensions:
3.3 in. × 7.0 in. × 1.8 in. (8.4 cm × 17.8 cm × 4.4 cm)
Meter Weight:
Weight with batteries: 0.6 lbs (0.27 kg)
Power Requirements:
Four AA-size batteries (included)
1
Temperature compensated over an air temperature range of 40 to 150°F (5 to 65°C).
2
The accuracy statement of ±5.0% of reading or ±5 ft/min (±0.025 m/s), whichever is greater,
begins at 30 ft/min through 4000 ft/min (0.15 m/s through 20 m/s).
3
Accuracy with instrument case at 77°F (25°C), add uncertainty of 0.05°F/°F (0.03°C/°C) for
change in instrument temperature.
11
Page 16
TSI Incorporated 500 Cardigan Road Shoreview, MN 55126 USA Toll Free (800) 874-2811 Telephone (651) 490-2811 Fax: (651) 490-3824
E-mail: customerservice@alnor.com Web: www.alnor.com
France Tel: +33 491 95 21 90 E-mail: tsifrance@tsi.com Germany Tel: +49 241 523030 E-mail: tsigmbh@tsi.com
Part No. 1980575 Rev. C Copyright © 2008 by TSI Incorporated
TSI Instruments Ltd. Stirling Road Cressex Business Park High Wycombe Bucks HP12 3RT United Kingdom Tel: +44 (0) 149 4 459200 Fax: +44 (0) 149 4 459700
E-mail: info@airflowinstruments.co.uk Web: www.airflowinstruments.co.uk
Quality Assured to ISO 9001:2000
Website: www.tsiinc.fr
Website: www.tsiinc.de
Loading...