TSI Alnor 9880 Data sheet

Features and Benefits
Accurate air velocity measurement
– Model AVM410 range 0 to 4,000 ft/min (0 to 20 m/s)
– Model 9880D range 0 to 2,000 ft/min
– Model 9880E range 0 to 10 m/s
Integrated probe attachment
Large, easy to read display
Intrinsically safe (9880 only)
Applications
HVAC system performance
Commissioning
Plant maintenance
Rugged. Reliable. Professional.
Model EBT721
Thermal Anemometers
Models AVM410 and 9880
The Models AVM410 and 9880 are a solid choice for a digital Air Velocity Meter, without compromising accuracy or precision. They are excellent for troubleshooting HVAC systems and conducting commissioning work.
Anemometers
Model AVM410
AVM410 9880D 9880E
Velocity range 0 to 2000 ft/min
Velocity range 0 to 10.00 m/s
Velocity range 0 to 4000 ft/min (0 to 20.00 m/s)
Temperature
Digital display
•••
Intrinsically safe
••
Certificate of Calibration
•••
Specifications
Models AVM410 and 9880
Velocity
Range (AVM410) 0 to 4,000 ft/min (0 to 20 m/s) Range (9880D) 0 to 2,000 ft/min Range (9880E) 0 to 10 m/s Accuracy
1&2
±5% of reading or ±5 ft/min (±0.025 m/s), whichever is greater
Resolution 1 ft/min (0.01 m/s)
Temperature (AVM410 only)
Range 0 to 200°F (-18 to 93°C) Accuracy
3
±0.5°F (±0.3°C)
Resolution 0.1°F (0.1°C)
Instrument Temperature Range
Operating (Electronics)
40 to 113°F (5 to 45°C)
Model AVM410 Operating (Probe)
0 to 200°F (-18 to 93°C)
Model 9880 Operating (Probe)
32 to 122°F (0 to 50°C)
Storage -4 to 140°F (-20 to 60°C)
External Meter Dimensions
Model AVM410 3.3 in. x 7.0 in. x 1.8 in. (8.4 cm x 17.8 cm x 4.4 cm) Model 9880 2.7 in. x 5.2 in. x 1.3 in. (6.8 cm x 13.2 cm x 3.3 cm)
Probe Dimensions (Model AVM410)
Length 40 in. (101.6 cm) Diameter at tip 0.28 in. (7 mm) Diameter at base 0.51 in. (13 mm)
Probe Dimensions (Model 9880)
Length 3.1 in. (79 cm) Diameter at tip 0.25 in. (6.4 mm) Diameter at base 0.25 in. (6.4 mm)
Meter Weight with Batteries
0.6 lbs (0.27 kg)
Power Requirements
Four AA-size batteries
Anemometers
Thermal Anemometers
A
lnor Products, TSI Incorporated
- 500 Cardigan Road Shoreview, MN 55126-3996 USA
USA Tel: +1 800
424 7427
E-mail: customerservice@alnor.com
Contact your local Alnor Distributor or visit our website
wwwwww..aallnnoorr..ccoomm
for more detailed specifications.
P/N 2980554 Rev B Copyright © 2007 by TSI Incorporated Printed in U.S.A.
Models AVM410 and 9880
1
Temperature compensated over an air temperature range of 40 to 150°F (5 to 65°C).
2
The accuracy statement begins at 30 ft/min through 4000 ft/min. (0.15 m/s through 20 m/s).
3
Accuracy with instrument case at 77°F (25°C), add uncertainty of 0.05°F/°F (0.03°C/°C) for change in instrument temperature
Specifications subject to change without notice.
Model 9880