T&S warrants to the original purchaser (other
than for purposes of resale) of this Safe-T-Link
product that such product is free from leaks
or defects in material and workmanship for a
period of fi ve (5) years from the original date
of purchase. However, T&S does not warrant
deterioration to the outer plastic cover caused
by normal wear and tear or misuse. During this
warranty period, if this Safe-T-Link product is
found to be defective, T&S shall, at its options,
repair and/or replace it. To obtain warranty
service, products must be returned to...
T&S Brass and Bronze Works, Inc.
Attn: Warranty Repair Department
2 Saddleback Cove
Travelers Rest, SC 29690
Shipping, freight, insurance, and other
transportation charges of the product to T&S
and the return of repaired or replaced product
to the purchaser are the responsibility of the
purchaser. Repair and/or replacement shall
be made within a reasonable time after receipt
by T&S of the returned product. For items and
components incorporated in the products and
not manufactured by T&S, the only warranty
extended is that of the original manufacturer
This warranty does not cover Items which have
received secondary finishing or have been
altered or modifi ed after purchase, or for defects
caused by physical abuse to or misuse of the
product, or shipment of the products.
Any express warranty not provided herein, and
any remedy for Breach of Contract which might
arise, is hereby excluded and disclaimed. Any
implied warranties of merchantability or fi tness
for a particular purpose are limited to one year in
duration. Under no circumstances shall T&S be
liable for loss of use or any special consequential
costs, expenses or damages whether arising
out of breach of warranty, breach of contract or
otherwise incurred by the purchaser or any other
user.
Some states do not allow limitations on how
long and implied warranty lasts or the exclusion
or limitation of incidental or consequential
damages, so the above limitations or exclusions
may not apply to you. Specifi c rights under this
warranty and other rights vary from state to state.
Attention California Residents:
“WARNING: This product contains chemicals
known to the State of California to cause cancer,
and birth defects or other reproductive harm.”
** This accessory should be purchased separately by installer, if
necessary.
3
General Instructions
Important Safety Instructions:
WARNING: Please read all
instructions carefully. Failure to fully
read instructions and follow them could
result in severe injury or death.
1. Gas connectors and accessories must
be installed in strict accordance with
the National Fuel Gas Code (ANSI
Z223.1 or latest edition) and applicable
state or local gas installation codes.
These T&S connectors comply with the
standard for connector for Movable Gas
Appliances, ANSI Z21.69•CSA 6.16.
WARNING: Per the ANSI Z21.69 • CSA
6.16 Standard, Gas Connectors cannot
be reused when an appliance is being
replaced or moved to a new location.
2. As with any other gas transmission
line or device, it is recommended that
installation and testing be done by
qualifi ed personnel.
3. An approved accessible manual gas
shut-off valve must be installed at the
outlet of the gas supply piping system
upstream of the connector. Each piece
of equipment must have its own shut-off
valve. The Quick Disconnect coupling
is not to be used as the primary shut-off
for all types of moveable gas appliances.
(ANSI Z233.1 and ANSI Z21.69).
4. The T&S Safe-T-Link Restraining Device, Model AG-RC, is the
recommended restraining device
for castered appliances. Installation
Instructions for the restraining device
are included with Model AG-RC. This
restrainer should be inspected as part
of regular maintenance and safety
procedures. Restraining cable must be
connected at all times when appliance is
in use.
5. With these Gas Connection, AVOID:
* Flexing, excessive bending and vibration.
* Movement after installation on fi xed
appliances.
* Movement on moveable appliances
(those with factory equipped casters)
except for repair or cleaning.
6. Final assembly must be tested for
leaks.
CAUTION: Matches, candles, open
fl ame or other sources of ignition shall
not be used for this purpose. Leak test
solutions may cause corrosion - rinse
with water after test.
To check gas supply piping system for
leakage see National Fuel Code ANSI
Z233.1/NFPA 54 or CAN/CGA-B149.1
Natural Gas and Propane Inst. Code.
Before Installation:
Safe Safe-T-Link Gas Connectors
with SwiveLink Fittings
The gas outlet must be in the same room
as the gas-fi red equipment and the con-
nector must not be concealed within or
run through any wall, fl oor or partition.
All parts of the union supplied with the
connector must be used, and no attempt
shall be made to assembly union nuts
directly to pipe threads.
The connector must not be kinked,
twisted or torqued.
Connectors are for use only on piping
systems having fuel gas pressures not in
excess of 1/2psi (3.5kPa).
4
General Instructions
For movable appliance installation (e.g.
appliances factory-equipped with casters),
fl exing and bending should be limited
to the needs of pulling and pushing
the appliance in and out for cleaning,
maintenance or installation.
Contact with foreign objects or substances
must be avoided.
Choose one of the following three setup
appropriate to your installation of a T&S
Safe-T-Link Gas Hose Connector with
SwiveLink fi ttings:
Installation:
Safe Safe-T-Link Gas Connectors
with SwiveLink Fittings
General
1. Shut the manual gas shut-off valve on
gas manifold line to “OFF”. If there is
no gas shut-off valve, main gas supply
line valve should be turned off. Do not
proceed unless gas is turned off.
2. Carefully read these entire
installation instructions.
3. Location of the two connection points
for gas appliance connectors (the gas
supply line and the equipment stubout) can vary greatly. For installations
which result in a sharp bend, a T&S
SwiveLink Gas Connector is ideal.
4. To be able to position gas appliance
as close to the wall as possible, the two
ends of the SwiveLink Gas Connector
should be offset from each other.
Connector
Appliance
Wall
5. Each piece of equipment must have
its own approved manual shut-off valve
off the main gas supply line.
Gas Supply Side
1. If pipe tee is already male, apply
Tefl on tape or pipe joint compound on
pipe threads at gas supply line.
5
Offset
General Instructions
2. If pipe tee is female, fi rst apply Tefl on tape or pipe joint compound to threads of pipe
nipple (not supplied), and thread pipe nipple into female pipe tee. Then thread (gas) no.7
valve onto pipe nipple and tighten.
3. For “Vertical” or “Combination” loop
installations, attach no.5 (male/female elbow)
as shown to no.7 valve with Tefl on tape or
pipe joint compound.
4. Apply Tefl on tape or pipe joint compound
to male threads of no.4. Thread no.4 into no.7
valve or no.5 and tighten.
Appliance Side without Quick Disconnect
1. For chosen loop installation, attach
no.6 (female/female elbow) to the male
appliance stub-out with Tefl on tape or
pipe joint compound.
2. Thread male end of no.4 into no.6
(female elbow) at appliance and tighten.
Appliance Side with Quick Disconnect
1. For chosen loop installation, attach no.5 (female/female elbow) to the male appliance
stub-out with Tefl on tape or pipe joint compound.
2. Separate no.8 coupling. No.9 nipple (male) half will remain attached to no.4fi tting.
No.10 coupling (female) half will remain attached to no.1.
3.Apply Tefl on Tape or pipe joint compound to threads of no.4fi tting. Thread male end of
no.4 into female elbow at appliance and tighten.
4. Reconnect no.8 coupling to nipple.
Finishing
1. Check tightness of all connections and perform leak test.
2. After installation of no.8 Connector, carefully push appliance back to operating
position and check that no.1 is not kinked, overbent, or caught under appliance casters.
Set length of no.11 so no.1 is never fully extended.
3. Affi x Orange label “Installation Instruction for Heavy-Duty Gas Connector” to back
of appliance after installation. Affi x Yellow label to wall near no.7 or equivalent valve.
Installation:
Safe Safe-T-Link Gas Connectors without SwiveLink Fittings
General
Follow General Step 1 through 5 on page 5.
Review Comparison
See Diagram on following page.
WARNING: No.8 must be oriented so
fl uid enters no.10 coupling half and
exits no.9 nipple half. Follow fl ow
direction arrows marked below and on
no.10 itself.
10
Coupling Half
(female)
Gas Flow Direction
9
Nipple Half
(male)
6
General Instructions
Gas Supply Side
1. If pipe tee is already male, apply Tefl on Tape or pipe joint compound to pipe threads at
gas supply line. Thread no.7 valve onto male pipe nipple and tighten.
2. If pipe tee is female, fi rst apply Tefl on Tape to threads of pipe (not supplied) and thread
pipe nipple into female pipe tee. Then thread no.7 valve onto pipe nipple and tighten.
3. Apply Tefl on Tape or pipe joint compound to thread of no.2fi tting. Place no.2fi tting
into no.7 valve and tighten.
Installation Comparison
Wrong
Wrong
Wrong
Right
Right
Wrong
Wrong
Appliance Side without Quick Disconnect
1. Apply Tefl on Tape or pipe joint compound to male stub-out on appliance and thread
female/female elbow to male stub-out.
2. Thread male end of no.2 on no.5 or no.6 and attach to stub-out of appliance and
tighten.
Appliance Side with Quick Disconnect
1. Apply Tefl on Tape or pipe joint compound to male stub-out on appliance and thread
no.5 (male/female elbow) to male stub-out.
2. Separate no.9 coupling nipple (male) half from no.10 coupling (female) half. Apply
Tefl on Tape or pipe joint compound to male threads on no.5 (male/female elbow).
3. Thread no.9 of no.8 onto male elbow at appliance and tighten.
4. Reconnect no.8 coupling assembly to nipple.