T&S Brass B-0968 Installation Manual

Limited One Year Warranty
T&S warrants to the original purchaser (other than for purposes of resale) that such product is free from defects in material and workmanship for a period of one (1) year from the date of purchase. During this one-year warranty period, if the product is found to be defective, T&S shall, at its options, repair and/or replace it. To obtain warranty service, products must be returned to...
T&S Brass and Bronze Works, Inc. Attn: Warranty Repair Department
2 Saddleback Cove
Travelers Rest, SC 29690
Shipping, freight, insurance, and other transportation charges of the product to T&S and the return of repaired or replaced product to the purchaser are the responsibility of the purchaser. Repair and/or replacement shall be made within a reasonable time after receipt by T&S of the returned product. This warranty does not cover Items which have received secondary nishing or have been altered or modifi ed after purchase, or for defects caused by physical abuse to or misuse of the product, or shipment of the products. Any express warranty not provided herein, and any remedy for Breach of Contract which might arise, is hereby excluded and disclaimed. Any implied warranties of merchantability or fi tness for a particular purpose are limited to one year in duration. Under no circumstances shall T&S be liable for loss of use or any special consequential costs, expenses or damages. Some states do not allow limitations on how long and implied warranty lasts or the exclusion or limitation of incidental or consequential dam­ages, so the above limitations or exclusions may not apply to you. Specifi c rights under this war- ranty and other rights vary from state to state.
Installation and
Maintenance
Instructions
ATMOSPHERIC VACUUM BREAKERS
B-0968 & B-0968-RK01 (3/8”) B-0969 & B-0969-RK01 (1/2”)
Deutsch: Installations- und
Wartungsanleitungen
strucciones de Man­tenimiento
P/N: 098-009549-45 Rev.6 Date: 01-08-08 Drawn: TEH Checked: GEF 01-08-08 Approved: JHB 01-08-08
Français: les Instructions
d’Installation et d’Entretien
Exploded View
3/8" Vacuum Breaker
Repair Kit
B-0968-RK01
1/2" Vacuum Breaker
Repair Kit
B-0969-RK01
1
2
3
4
5
6
7
8
B-0968 (3/8") B-0969 (1/2")
* Some items are listed for instructional purposes
and may not be sold as separate parts.
2
Part Number Guide
B-0968 Vacuum Breaker Assemblies & Kit
(*)
1 2 3
(*)
4
(*)
5
(*)
6
(*)
7 8
(*) Indicates those items that are included in the B-0968-RK01 Vacuum Breaker Repair Kit
Screws Nameplate Coverplate Insert Large O-Ring Small O-Ring Piston Body, Vacuum Breaker 3/8”
* * * * * * * *
B-0969 Vacuum Breaker Assemblies & Kit
(*)
1 2 3
(*)
4
(*)
5
(*)
6
(*)
7 8
Screws Nameplate Coverplate Insert O-Ring Sealing Disk Piston Body, Vacuum Breaker 1/2”
* * * * * * * *
(*) Indicates those items that are included in the B-0969-RK01 Vacuum Breaker Repair Kit
3
General Instructions
Typical Installation:
Single Vacuum Breaker
1. Vacuum breaker must be installed with the supply connected to the bot­tom and the outlet connected to the appliance, as shown below:
8
not less than 6” (CIL)
supply valve
2. The bottom of the no.8 should be at least 6” above the fl ood rim of the xture or appliance.
3. When using a portable appliance, no.8 should be installed at least 6” above the highest point to which the outlet can be raised, as shown:
overfl ow
or fl ood
rim
xture or appliance
Note: Where the device is a separate unit, in the absence of a Critical Installation Level (CIL) mark, the extreme bottom of the no.8 casting should be used to determine its installed position. Where the device is incorporated in an outlet tube furnished by the manufacturer, the extreme bot­tom of the internal unit should be noted on the outside of the tube by a CIL line, for use in determining its installed position.
4. The water supply valve must be installed on the supply side (ahead) of the vacuum breaker, and no shut­off valve should be installed on the outlet side (downstream).
5. The vacuum breaker should not be subjected to continuous pressure for more than twelve (12) hours.
Note: This device should not be installed in a concealed or inac­cessible location, nor where the venting water from the device during its normal functioning may be deemed objectionable.
8
supply valve
highest position of appliance not less than 6” (CIL)
4